Skip to content

All Devices and Entities

please read

Make sure you have read and understood the Disclaimer before sending ambiguous messages to your EMS bus as you could cause serious damage to your equipment.

Most Bosch branded boilers that support the Logamatic EMS bus protocols work with this design. This includes Nefit, Buderus, Worcester, Junkers and Sieger (all copyrighted).

EMS devices are being constantly added to the database on each new release.

The following device types are supported:

  • boiler
  • thermostat
  • heatpump
  • heatsource
  • solar
  • connect
  • mixer
  • controller
  • switch
  • gateway
  • alert
  • pump

All EMS Telegrams~

Download the full CSV file

telegram_type_id name is_fetched
0x04 UBAFactory fetched
0x06 RCTime
0x0A EasyMonitor fetched
0x10 UBAErrorMessage1
0x11 UBAErrorMessage2
0x12 RCErrorMessage
0x13 RCErrorMessage2
0x14 UBATotalUptime fetched
0x15 UBAMaintenanceData
0x16 UBAParameters fetched
0x18 UBAMonitorFast
0x19 UBAMonitorSlow
0x1A UBASetPoints
0x1C UBAMaintenanceStatus
0x1E HydrTemp
0x23 JunkersSetMixer fetched
0x26 UBASettingsWW fetched
0x28 WeatherComp fetched
0x2A MC110Status
0x2E Meters
0x33 UBAParameterWW fetched
0x34 UBAMonitorWW
0x35 UBAFlags
0x37 WWSettings fetched
0x38 WWTimer fetched
0x39 WWCircTimer fetched
0x3A RC30WWSettings fetched
0x3B Energy
0x3D RC35Set
0x3E RC35Monitor
0x3F RC35Timer
0x40 RC30Temp
0x41 RC30Monitor
0x42 RC35Timer2
0x47 RC35Set
0x48 RC35Monitor
0x49 RC35Timer
0x4C RC35Timer2
0x51 RC35Set
0x52 RC35Monitor
0x53 RC35Timer
0x56 RC35Timer2
0x5B RC35Set
0x5C RC35Monitor
0x5D RC35Timer
0x60 RC35Timer2
0x96 SM10Config fetched
0x97 SM10Monitor
0x9C WM10MonitorMessage
0x9D WM10SetMessage
0xA2 RCError
0xA3 RCOutdoorTemp
0xA5 IBASettings fetched
0xA7 RC30Set
0xA9 RC30Vacation fetched
0xAA MMConfigMessage fetched
0xAB MMStatusMessage
0xAC MMSetMessage
0xAF RC20Remote
0xB0 RC10Set
0xB1 RC10Monitor
0xBB HybridSettings fetched
0xBF ErrorMessage
0xC0 RCErrorMessage
0xC2 UBAErrorMessage3
0xC6 UBAErrorMessage3
0xD1 UBAOutdoorTemp
0xE3 UBAMonitorSlowPlus2
0xE4 UBAMonitorFastPlus
0xE5 UBAMonitorSlowPlus
0xE6 UBAParametersPlus fetched
0xE9 UBAMonitorWWPlus
0xEA UBAParameterWWPlus fetched
0x0101 ISM1Set fetched
0x0103 ISM1StatusMessage fetched
0x0104 ISM2StatusMessage
0x010C IPMStatusMessage
0x011E IPMTempMessage
0x012E HPEnergy1
0x013B HPEnergy2
0x0165 JunkersSet
0x0166 JunkersSet
0x0167 JunkersSet
0x0168 JunkersSet
0x016E Absent fetched
0x016F JunkersMonitor
0x0170 JunkersMonitor
0x0171 JunkersMonitor
0x0172 JunkersMonitor
0x0179 JunkersSet
0x017A JunkersSet
0x017B JunkersSet
0x017C JunkersSet
0x01D3 JunkersDhw fetched
0x023A RC300OutdoorTemp fetched
0x023E PVSettings fetched
0x0240 RC300Settings fetched
0x0241 RC300Settings fetched
0x0267 RC300Floordry
0x0269 RC300Holiday fetched
0x0291 HPMode fetched
0x0292 HPMode fetched
0x0293 HPMode fetched
0x0294 HPMode fetched
0x029B RC300Curves
0x029C RC300Curves
0x029D RC300Curves
0x029E RC300Curves
0x029F RC300Curves
0x02A0 RC300Curves
0x02A1 RC300Curves
0x02A2 RC300Curves
0x02A5 EasyMonitor
0x02A6 RC300Monitor
0x02A7 RC300Monitor
0x02A8 RC300Monitor
0x02A9 RC300Monitor
0x02AA RC300Monitor
0x02AB RC300Monitor
0x02AC RC300Monitor
0x02AF RC300Summer
0x02B0 RC300Summer
0x02B1 RC300Summer
0x02B2 RC300Summer
0x02B3 RC300Summer
0x02B4 RC300Summer
0x02B5 RC300Summer
0x02B6 RC300Summer
0x02B9 RC300Set
0x02BA RC300Set
0x02BB RC300Set
0x02BC RC300Set
0x02BD RC300Set
0x02BE RC300Set
0x02BF RC300Set
0x02C0 RC300Set
0x02CC RC300Set2
0x02CD MMPLUSConfigMessage fetched
0x02CE RC300Set2
0x02D0 RC300Set2
0x02D2 RC300Set2
0x02D6 HPPump2 fetched
0x02D7 MMPLUSStatusMessage
0x02F5 RC300WWmode fetched
0x02F6 RC300WW2mode fetched
0x0313 MMPLUSConfigMessage_WWC fetched
0x031B RC300WWtemp fetched
0x031D RC300WWmode2
0x031E RC300WWmode2
0x0331 MMPLUSStatusMessage_WWC
0x0358 SM100SystemConfig fetched
0x035A SM100CircuitConfig fetched
0x035C SM100HeatAssist fetched
0x035D SM100Circuit2Config fetched
0x035F SM100Config1 fetched
0x0361 SM100Differential fetched
0x0362 SM100Monitor
0x0363 SM100Monitor2
0x0364 SM100Status
0x0366 SM100Config
0x036A SM100Status2
0x0380 SM100CollectorConfig fetched
0x038E SM100Energy fetched
0x0391 SM100Time fetched
0x043F CRHolidays fetched
0x0467 HPSet
0x0468 HPSet
0x0469 HPSet
0x046A HPSet
0x0471 RC300Summer2
0x0472 RC300Summer2
0x0473 RC300Summer2
0x0474 RC300Summer2
0x0475 RC300Summer2
0x0476 RC300Summer2
0x0477 RC300Summer2
0x0478 RC300Summer2
0x047B HP2
0x0484 HPSilentMode fetched
0x0485 HpCooling fetched
0x0486 HpInConfig fetched
0x0488 HPValve fetched
0x048A HpPool fetched
0x048B HPPumps fetched
0x048D HpPower fetched
0x048F HpTemperatures
0x0491 HPAdditionalHeater fetched
0x0492 HpHeaterConfig fetched
0x0494 UBAEnergySupplied
0x0495 UBAInformation
0x0499 HPDhwSettings fetched
0x049C HPSettings2 fetched
0x049D HPSettings3 fetched
0x04A2 HpInput fetched
0x04A5 HPFan fetched
0x04A7 HPPowerLimit fetched
0x04AA HPPower2 fetched
0x04AE HPEnergy fetched
0x04AF HPMeters fetched
0x056B VentilationMode fetched
0x0583 VentilationMonitor
0x0585 Blowerspeed
0x0587 Bypass
0x05BA HpPoolStatus fetched
0x05D9 Airquality
0x0772 HIUSettings
0x0779 HIUMonitor
0x07A5 SM100wwCirc fetched
0x07A6 SM100wwParam fetched
0x07AA SM100wwStatus
0x07AB SM100wwCommand
0x07AC SM100wwParam1
0x07AD SM100ValveStatus
0x07AE SM100wwKeepWarm fetched
0x07D6 SM100wwTemperature
0x07E0 SM100wwStatus2 fetched
0x0935 EM100SetMessage fetched
0x0936 EM100OutMessage
0x0937 EM100TempMessage
0x0938 EM100InputMessage
0x0939 EM100MonitorMessage
0x093A EM100ConfigMessage
0x0998 HPSettings fetched
0x0999 HPFunctionTest fetched
0x099A HPStarts
0x099B HPFlowTemp
0x099C HPComp
0x09A0 HPTemperature

All devices and entities~

Download the full CSV file

device name device type product id shortname fullname type [options...] | (min/max) uom writeable discovery entityid v3.4 discovery entityid modbus unit identifier modbus block modbus scale factor modbus offset modbus count
CS800i, Logatherm WLW boiler 8 reset reset cmd [-|maintenance|error|history|message] True sensor.boiler_reset sensor.boiler_reset 5 0 1 0 1
CS800i, Logatherm WLW boiler 8 heatingoff force heating off boolean True switch.boiler_force_heating_off switch.boiler_heatingoff 5 0 1 1 1
CS800i, Logatherm WLW boiler 8 heatingactive heating active boolean False binary_sensor.boiler_heating_active binary_sensor.boiler_heatingactive 5 0 1 2 1
CS800i, Logatherm WLW boiler 8 tapwateractive tapwater active boolean False binary_sensor.boiler_tapwater_active binary_sensor.boiler_tapwateractive 5 0 1 3 1
CS800i, Logatherm WLW boiler 8 selflowtemp selected flow temperature uint8 (>=0<=90) C True number.boiler_selected_flow_temperature number.boiler_selflowtemp 5 0 1 4 1
CS800i, Logatherm WLW boiler 8 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.boiler_heating_pump_modulation sensor.boiler_heatingpumpmod 5 0 1 5 1
CS800i, Logatherm WLW boiler 8 outdoortemp outside temperature int16 (>=-3199<=3199) C False sensor.boiler_outside_temperature sensor.boiler_outdoortemp 5 0 1/10 6 1
CS800i, Logatherm WLW boiler 8 curflowtemp current flow temperature uint16 (>=0<=3199) C False sensor.boiler_current_flow_temperature sensor.boiler_curflowtemp 5 0 1/10 7 1
CS800i, Logatherm WLW boiler 8 rettemp return temperature uint16 (>=0<=3199) C False sensor.boiler_return_temperature sensor.boiler_rettemp 5 0 1/10 8 1
CS800i, Logatherm WLW boiler 8 switchtemp mixing switch temperature uint16 (>=0<=3199) C False sensor.boiler_mixing_switch_temperature sensor.boiler_switchtemp 5 0 1/10 9 1
CS800i, Logatherm WLW boiler 8 syspress system pressure uint8 (>=0<=25) bar False sensor.boiler_system_pressure sensor.boiler_syspress 5 0 1/10 10 1
CS800i, Logatherm WLW boiler 8 boiltemp actual boiler temperature uint16 (>=0<=3199) C False sensor.boiler_actual_boiler_temperature sensor.boiler_boiltemp 5 0 1/10 11 1
CS800i, Logatherm WLW boiler 8 headertemp low loss header uint16 (>=0<=3199) C False sensor.boiler_low_loss_header sensor.boiler_headertemp 5 0 1/10 12 1
CS800i, Logatherm WLW boiler 8 heatingactivated heating activated boolean True switch.boiler_heating_activated switch.boiler_heatingactivated 5 0 1 13 1
CS800i, Logatherm WLW boiler 8 heatingtemp heating temperature uint8 (>=0<=90) C True number.boiler_heating_temperature number.boiler_heatingtemp 5 0 1 14 1
CS800i, Logatherm WLW boiler 8 heatingpump heating pump boolean False binary_sensor.boiler_heating_pump binary_sensor.boiler_heatingpump 5 0 1 15 1
CS800i, Logatherm WLW boiler 8 pumpmodmax boiler pump max power uint8 (>=0<=100) % True number.boiler_boiler_pump_max_power number.boiler_pumpmodmax 5 0 1 16 1
CS800i, Logatherm WLW boiler 8 pumpmodmin boiler pump min power uint8 (>=0<=100) % True number.boiler_boiler_pump_min_power number.boiler_pumpmodmin 5 0 1 17 1
CS800i, Logatherm WLW boiler 8 pumpmode boiler pump mode enum [proportional|deltaP-1|deltaP-2|deltaP-3|deltaP-4] True select.boiler_boiler_pump_mode select.boiler_pumpmode 5 0 1 18 1
CS800i, Logatherm WLW boiler 8 pumpcharacter boiler pump characteristic enum [proportional|150mbar|200mbar|250mbar|300mbar|350mbar|400mbar] True select.boiler_boiler_pump_characteristic select.boiler_pumpcharacter 5 0 1 19 1
CS800i, Logatherm WLW boiler 8 pumpdelay pump delay uint8 (>=0<=60) minutes True number.boiler_pump_delay number.boiler_pumpdelay 5 0 1 20 1
CS800i, Logatherm WLW boiler 8 pumpontemp pump logic temperature uint8 (>=0<=60) C True number.boiler_pump_logic_temperature number.boiler_pumpontemp 5 0 1 21 1
CS800i, Logatherm WLW boiler 8 selburnpow burner selected max power uint8 (>=0<=254) % True number.boiler_burner_selected_max_power number.boiler_selburnpow 5 0 1 22 1
CS800i, Logatherm WLW boiler 8 curburnpow burner current power uint8 (>=0<=100) % False sensor.boiler_burner_current_power sensor.boiler_curburnpow 5 0 1 23 1
CS800i, Logatherm WLW boiler 8 burnstarts burner starts uint24 (>=0<=16777214) False sensor.boiler_burner_starts sensor.boiler_burnstarts 5 0 1 24 2
CS800i, Logatherm WLW boiler 8 burnworkmin total burner operating time time (>=0<=16777214) minutes False sensor.boiler_total_burner_operating_time sensor.boiler_burnworkmin 5 0 1 26 2
CS800i, Logatherm WLW boiler 8 burn2workmin burner stage 2 operating time time (>=0<=16777214) minutes False sensor.boiler_burner_stage_2_operating_time sensor.boiler_burn2workmin 5 0 1 28 2
CS800i, Logatherm WLW boiler 8 heatworkmin total heat operating time time (>=0<=16777214) minutes False sensor.boiler_total_heat_operating_time sensor.boiler_heatworkmin 5 0 1 30 2
CS800i, Logatherm WLW boiler 8 heatstarts burner starts heating uint24 (>=0<=16777214) False sensor.boiler_burner_starts_heating sensor.boiler_heatstarts 5 0 1 32 2
CS800i, Logatherm WLW boiler 8 ubauptime total UBA operating time time (>=0<=16777214) minutes False sensor.boiler_total_UBA_operating_time sensor.boiler_ubauptime 5 0 1 34 2
CS800i, Logatherm WLW boiler 8 lastcode last error code string False sensor.boiler_last_error_code sensor.boiler_lastcode 5 0 1 36 28
CS800i, Logatherm WLW boiler 8 servicecode service code string False sensor.boiler_service_code sensor.boiler_servicecode 5 0 1 64 2
CS800i, Logatherm WLW boiler 8 servicecodenumber service code number uint16 (>=0<=31999) False sensor.boiler_service_code_number sensor.boiler_servicecodenumber 5 0 1 66 1
CS800i, Logatherm WLW boiler 8 maintenancemessage maintenance message string False sensor.boiler_maintenance_message sensor.boiler_maintenancemessage 5 0 1 67 2
CS800i, Logatherm WLW boiler 8 maintenance maintenance scheduled enum [off|time|date|manual] True select.boiler_maintenance_scheduled select.boiler_maintenance 5 0 1 69 1
CS800i, Logatherm WLW boiler 8 maintenancetime time to next maintenance uint16 (>=0<=31999) hours True number.boiler_time_to_next_maintenance number.boiler_maintenancetime 5 0 1 70 1
CS800i, Logatherm WLW boiler 8 maintenancedate next maintenance date string True sensor.boiler_next_maintenance_date sensor.boiler_maintenancedate 5 0 1 71 6
CS800i, Logatherm WLW boiler 8 emergencyops emergency operation boolean True switch.boiler_emergency_operation switch.boiler_emergencyops 5 0 1 77 1
CS800i, Logatherm WLW boiler 8 emergencytemp emergency temperature uint8 (>=15<=70) C True number.boiler_emergency_temperature number.boiler_emergencytemp 5 0 1 78 1
CS800i, Logatherm WLW boiler 8 pc0flow Flow PC0 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC0 sensor.boiler_pc0flow 5 0 1 79 1
CS800i, Logatherm WLW boiler 8 pc1flow Flow PC1 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC1 sensor.boiler_pc1flow 5 0 1 80 1
CS800i, Logatherm WLW boiler 8 pc1on PC1 boolean False binary_sensor.boiler_PC1 binary_sensor.boiler_pc1on 5 0 1 81 1
CS800i, Logatherm WLW boiler 8 pc1rate PC1 rate uint8 (>=0<=100) % False sensor.boiler_PC1_rate sensor.boiler_pc1rate 5 0 1 82 1
CS800i, Logatherm WLW boiler 8 nrgtotal total energy uint24 (>=0<=167772) kWh False sensor.boiler_total_energy sensor.boiler_nrgtotal 5 0 1/100 83 2
CS800i, Logatherm WLW boiler 8 dhw.nrg energy uint24 (>=0<=167772) kWh False sensor.boiler_dhw_energy sensor.boiler_dhw_nrg 5 9 1/100 0 2
CS800i, Logatherm WLW boiler 8 nrgheat energy heating uint24 (>=0<=167772) kWh False sensor.boiler_energy_heating sensor.boiler_nrgheat 5 0 1/100 85 2
CS800i, Logatherm WLW boiler 8 nrgcool energy cooling uint24 (>=0<=167772) kWh False sensor.boiler_energy_cooling sensor.boiler_nrgcool 5 0 1/100 87 2
CS800i, Logatherm WLW boiler 8 metertotal meter total uint24 (>=0<=167772) kWh False sensor.boiler_meter_total sensor.boiler_metertotal 5 0 1/100 89 2
CS800i, Logatherm WLW boiler 8 metercomp meter compressor uint24 (>=0<=167772) kWh False sensor.boiler_meter_compressor sensor.boiler_metercomp 5 0 1/100 91 2
CS800i, Logatherm WLW boiler 8 metereheat meter e-heater uint24 (>=0<=167772) kWh False sensor.boiler_meter_e-heater sensor.boiler_metereheat 5 0 1/100 93 2
CS800i, Logatherm WLW boiler 8 meterheat meter heating uint24 (>=0<=167772) kWh False sensor.boiler_meter_heating sensor.boiler_meterheat 5 0 1/100 95 2
CS800i, Logatherm WLW boiler 8 metercool meter cooling uint24 (>=0<=167772) kWh False sensor.boiler_meter_cooling sensor.boiler_metercool 5 0 1/100 97 2
CS800i, Logatherm WLW boiler 8 dhw.meter meter uint24 (>=0<=167772) kWh False sensor.boiler_dhw_meter sensor.boiler_dhw_meter 5 9 1/100 2 2
CS800i, Logatherm WLW boiler 8 uptimetotal heatpump total uptime time (>=0<=279620) minutes False sensor.boiler_heatpump_total_uptime sensor.boiler_uptimetotal 5 0 1/60 99 2
CS800i, Logatherm WLW boiler 8 uptimecontrol total operating time heat time (>=0<=279620) minutes False sensor.boiler_total_operating_time_heat sensor.boiler_uptimecontrol 5 0 1/60 101 2
CS800i, Logatherm WLW boiler 8 uptimecompheating operating time compressor heating time (>=0<=279620) minutes False sensor.boiler_operating_time_compressor_heating sensor.boiler_uptimecompheating 5 0 1/60 103 2
CS800i, Logatherm WLW boiler 8 uptimecompcooling operating time compressor cooling time (>=0<=279620) minutes False sensor.boiler_operating_time_compressor_cooling sensor.boiler_uptimecompcooling 5 0 1/60 105 2
CS800i, Logatherm WLW boiler 8 dhw.uptimecomp operating time compressor time (>=0<=279620) minutes False sensor.boiler_dhw_operating_time_compressor sensor.boiler_dhw_uptimecomp 5 9 1/60 4 2
CS800i, Logatherm WLW boiler 8 uptimecomppool operating time compressor pool time (>=0<=279620) minutes False sensor.boiler_operating_time_compressor_pool sensor.boiler_uptimecomppool 5 0 1/60 107 2
CS800i, Logatherm WLW boiler 8 totalcompstarts total compressor control starts uint24 (>=0<=16777214) False sensor.boiler_total_compressor_control_starts sensor.boiler_totalcompstarts 5 0 1 109 2
CS800i, Logatherm WLW boiler 8 heatingstarts heating control starts uint24 (>=0<=16777214) False sensor.boiler_heating_control_starts sensor.boiler_heatingstarts 5 0 1 111 2
CS800i, Logatherm WLW boiler 8 coolingstarts cooling control starts uint24 (>=0<=16777214) False sensor.boiler_cooling_control_starts sensor.boiler_coolingstarts 5 0 1 113 2
CS800i, Logatherm WLW boiler 8 dhw.startshp starts hp uint24 (>=0<=16777214) False sensor.boiler_dhw_starts_hp sensor.boiler_dhw_startshp 5 9 1 6 2
CS800i, Logatherm WLW boiler 8 poolstarts pool control starts uint24 (>=0<=16777214) False sensor.boiler_pool_control_starts sensor.boiler_poolstarts 5 0 1 115 2
CS800i, Logatherm WLW boiler 8 nrgconstotal total energy consumption uint24 (>=0<=16777214) kWh False sensor.boiler_total_energy_consumption sensor.boiler_nrgconstotal 5 0 1 117 2
CS800i, Logatherm WLW boiler 8 nrgconscomptotal total energy consumption compressor uint24 (>=0<=16777214) kWh False sensor.boiler_total_energy_consumption_compressor sensor.boiler_nrgconscomptotal 5 0 1 119 2
CS800i, Logatherm WLW boiler 8 nrgconscompheating energy consumption compressor heating uint24 (>=0<=16777214) kWh False sensor.boiler_energy_consumption_compressor_heating sensor.boiler_nrgconscompheating 5 0 1 121 2
CS800i, Logatherm WLW boiler 8 dhw.nrgconscomp energy consumption compressor uint24 (>=0<=16777214) kWh False sensor.boiler_dhw_energy_consumption_compressor sensor.boiler_dhw_nrgconscomp 5 9 1 8 2
CS800i, Logatherm WLW boiler 8 nrgconscompcooling energy consumption compressor cooling uint24 (>=0<=16777214) kWh False sensor.boiler_energy_consumption_compressor_cooling sensor.boiler_nrgconscompcooling 5 0 1 123 2
CS800i, Logatherm WLW boiler 8 nrgconscomppool energy consumption compressor pool uint24 (>=0<=16777214) kWh False sensor.boiler_energy_consumption_compressor_pool sensor.boiler_nrgconscomppool 5 0 1 125 2
CS800i, Logatherm WLW boiler 8 auxelecheatnrgconstotal total aux elec. heater energy consumption uint24 (>=0<=16777214) kWh False sensor.boiler_total_aux_elec._heater_energy_consumption sensor.boiler_auxelecheatnrgconstotal 5 0 1 127 2
CS800i, Logatherm WLW boiler 8 auxelecheatnrgconsheating aux elec. heater energy consumption heating uint24 (>=0<=16777214) kWh False sensor.boiler_aux_elec._heater_energy_consumption_heating sensor.boiler_auxelecheatnrgconsheating 5 0 1 129 2
CS800i, Logatherm WLW boiler 8 dhw.auxelecheatnrgcons aux elec. heater energy consumption uint24 (>=0<=16777214) kWh False sensor.boiler_dhw_aux_elec._heater_energy_consumption sensor.boiler_dhw_auxelecheatnrgcons 5 9 1 10 2
CS800i, Logatherm WLW boiler 8 auxelecheatnrgconspool aux elec. heater energy consumption pool uint24 (>=0<=16777214) kWh False sensor.boiler_aux_elec._heater_energy_consumption_pool sensor.boiler_auxelecheatnrgconspool 5 0 1 131 2
CS800i, Logatherm WLW boiler 8 nrgsupptotal total energy supplied uint24 (>=0<=16777214) kWh False sensor.boiler_total_energy_supplied sensor.boiler_nrgsupptotal 5 0 1 133 2
CS800i, Logatherm WLW boiler 8 nrgsuppheating total energy supplied heating uint24 (>=0<=16777214) kWh False sensor.boiler_total_energy_supplied_heating sensor.boiler_nrgsuppheating 5 0 1 135 2
CS800i, Logatherm WLW boiler 8 dhw.nrgsupp total energy warm supplied uint24 (>=0<=16777214) kWh False sensor.boiler_dhw_total_energy_warm_supplied sensor.boiler_dhw_nrgsupp 5 9 1 12 2
CS800i, Logatherm WLW boiler 8 nrgsuppcooling total energy supplied cooling uint24 (>=0<=16777214) kWh False sensor.boiler_total_energy_supplied_cooling sensor.boiler_nrgsuppcooling 5 0 1 137 2
CS800i, Logatherm WLW boiler 8 nrgsupppool total energy supplied pool uint24 (>=0<=16777214) kWh False sensor.boiler_total_energy_supplied_pool sensor.boiler_nrgsupppool 5 0 1 139 2
CS800i, Logatherm WLW boiler 8 hppower compressor power output uint16 (>=0<=3199) kW False sensor.boiler_compressor_power_output sensor.boiler_hppower 5 0 1/10 141 1
CS800i, Logatherm WLW boiler 8 hpmaxpower compressor max power uint8 (>=0<=100) % True number.boiler_compressor_max_power number.boiler_hpmaxpower 5 0 1 142 1
CS800i, Logatherm WLW boiler 8 pvmaxcomp pv compressor max power uint8 (>=0<=25) kW True number.boiler_pv_compressor_max_power number.boiler_pvmaxcomp 5 0 1/10 143 1
CS800i, Logatherm WLW boiler 8 powerreduction power reduction uint8 (>=30<=60) % True number.boiler_power_reduction number.boiler_powerreduction 5 0 10 144 1
CS800i, Logatherm WLW boiler 8 hpsetdiffpress set differential pressure uint8 (>=150<=750) mbar True number.boiler_set_differential_pressure number.boiler_hpsetdiffpress 5 0 50 145 1
CS800i, Logatherm WLW boiler 8 hpcompon hp compressor boolean False binary_sensor.boiler_hp_compressor binary_sensor.boiler_hpcompon 5 0 1 146 1
CS800i, Logatherm WLW boiler 8 hpactivity compressor activity enum [off|heating|cooling|hot water|pool|pool heating|defrost|compressor alarm] False sensor.boiler_compressor_activity sensor.boiler_hpactivity 5 0 1 147 1
CS800i, Logatherm WLW boiler 8 hpbrinepumpspd brine pump speed uint8 (>=0<=100) % False sensor.boiler_brine_pump_speed sensor.boiler_hpbrinepumpspd 5 0 1 148 1
CS800i, Logatherm WLW boiler 8 hpswitchvalve switch valve boolean False binary_sensor.boiler_switch_valve binary_sensor.boiler_hpswitchvalve 5 0 1 149 1
CS800i, Logatherm WLW boiler 8 hpcompspd compressor speed uint8 (>=0<=100) % False sensor.boiler_compressor_speed sensor.boiler_hpcompspd 5 0 1 150 1
CS800i, Logatherm WLW boiler 8 hpcircspd circulation pump speed uint8 (>=0<=100) % False sensor.boiler_circulation_pump_speed sensor.boiler_hpcircspd 5 0 1 151 1
CS800i, Logatherm WLW boiler 8 hpbrinein brine in/evaporator int16 (>=-3199<=3199) C False sensor.boiler_brine_in/evaporator sensor.boiler_hpbrinein 5 0 1/10 152 1
CS800i, Logatherm WLW boiler 8 hpbrineout brine out/condenser int16 (>=-3199<=3199) C False sensor.boiler_brine_out/condenser sensor.boiler_hpbrineout 5 0 1/10 153 1
CS800i, Logatherm WLW boiler 8 hptc0 heat carrier return (TC0) int16 (>=-3199<=3199) C False sensor.boiler_heat_carrier_return_(TC0) sensor.boiler_hptc0 5 0 1/10 154 1
CS800i, Logatherm WLW boiler 8 hptc1 heat carrier forward (TC1) int16 (>=-3199<=3199) C False sensor.boiler_heat_carrier_forward_(TC1) sensor.boiler_hptc1 5 0 1/10 155 1
CS800i, Logatherm WLW boiler 8 hptc3 condenser temperature (TC3) int16 (>=-3199<=3199) C False sensor.boiler_condenser_temperature_(TC3) sensor.boiler_hptc3 5 0 1/10 156 1
CS800i, Logatherm WLW boiler 8 hptr1 compressor temperature (TR1) int16 (>=-3199<=3199) C False sensor.boiler_compressor_temperature_(TR1) sensor.boiler_hptr1 5 0 1/10 157 1
CS800i, Logatherm WLW boiler 8 hptr3 refrigerant temperature liquid side (condenser output) (TR3) int16 (>=-3199<=3199) C False sensor.boiler_refrigerant_temperature_liquid_side_(condenser_output)_(TR3) sensor.boiler_hptr3 5 0 1/10 158 1
CS800i, Logatherm WLW boiler 8 hptr4 evaporator inlet temperature (TR4) int16 (>=-3199<=3199) C False sensor.boiler_evaporator_inlet_temperature_(TR4) sensor.boiler_hptr4 5 0 1/10 159 1
CS800i, Logatherm WLW boiler 8 hptr5 compressor inlet temperature (TR5) int16 (>=-3199<=3199) C False sensor.boiler_compressor_inlet_temperature_(TR5) sensor.boiler_hptr5 5 0 1/10 160 1
CS800i, Logatherm WLW boiler 8 hptr6 compressor outlet temperature (TR6) int16 (>=-3199<=3199) C False sensor.boiler_compressor_outlet_temperature_(TR6) sensor.boiler_hptr6 5 0 1/10 161 1
CS800i, Logatherm WLW boiler 8 hptr7 refrigerant temperature gas side (condenser input) (TR7) int16 (>=-3199<=3199) C False sensor.boiler_refrigerant_temperature_gas_side_(condenser_input)_(TR7) sensor.boiler_hptr7 5 0 1/10 162 1
CS800i, Logatherm WLW boiler 8 hptl2 air inlet temperature (TL2) int16 (>=-3199<=3199) C False sensor.boiler_air_inlet_temperature_(TL2) sensor.boiler_hptl2 5 0 1/10 163 1
CS800i, Logatherm WLW boiler 8 hppl1 low pressure side temperature (PL1) int16 (>=-3199<=3199) C False sensor.boiler_low_pressure_side_temperature_(PL1) sensor.boiler_hppl1 5 0 1/10 164 1
CS800i, Logatherm WLW boiler 8 hpph1 high pressure side temperature (PH1) int16 (>=-3199<=3199) C False sensor.boiler_high_pressure_side_temperature_(PH1) sensor.boiler_hpph1 5 0 1/10 165 1
CS800i, Logatherm WLW boiler 8 hpta4 drain pan temp (TA4) int16 (>=-3199<=3199) C False sensor.boiler_drain_pan_temp_(TA4) sensor.boiler_hpta4 5 0 1/10 166 1
CS800i, Logatherm WLW boiler 8 hptw1 reservoir temp (TW1) int16 (>=-3199<=3199) C False sensor.boiler_reservoir_temp_(TW1) sensor.boiler_hptw1 5 0 1/10 167 1
CS800i, Logatherm WLW boiler 8 poolsettemp pool set temperature uint8 (>=0<=127) C True number.boiler_pool_set_temperature number.boiler_poolsettemp 5 0 1/2 168 1
CS800i, Logatherm WLW boiler 8 hp4way 4-way valve (VR4) enum [cooling & defrost|heating & dhw] False sensor.boiler_4-way_valve_(VR4) sensor.boiler_hp4way 5 0 1 169 1
CS800i, Logatherm WLW boiler 8 hpin1 input 1 state boolean False binary_sensor.boiler_input_1_state binary_sensor.boiler_hpin1 5 0 1 170 1
CS800i, Logatherm WLW boiler 8 hpin1opt input 1 options string True sensor.boiler_input_1_options sensor.boiler_hpin1opt 5 0 1 171 8
CS800i, Logatherm WLW boiler 8 hpin2 input 2 state boolean False binary_sensor.boiler_input_2_state binary_sensor.boiler_hpin2 5 0 1 179 1
CS800i, Logatherm WLW boiler 8 hpin2opt input 2 options string True sensor.boiler_input_2_options sensor.boiler_hpin2opt 5 0 1 180 8
CS800i, Logatherm WLW boiler 8 hpin3 input 3 state boolean False binary_sensor.boiler_input_3_state binary_sensor.boiler_hpin3 5 0 1 188 1
CS800i, Logatherm WLW boiler 8 hpin3opt input 3 options string True sensor.boiler_input_3_options sensor.boiler_hpin3opt 5 0 1 189 8
CS800i, Logatherm WLW boiler 8 hpin4 input 4 state boolean False binary_sensor.boiler_input_4_state binary_sensor.boiler_hpin4 5 0 1 197 1
CS800i, Logatherm WLW boiler 8 hpin4opt input 4 options string True sensor.boiler_input_4_options sensor.boiler_hpin4opt 5 0 1 198 8
CS800i, Logatherm WLW boiler 8 maxheatcomp heat limit compressor enum [0 kW|2 kW|3 kW|4 kW|6 kW|9 kW] True select.boiler_heat_limit_compressor select.boiler_maxheatcomp 5 0 1 206 1
CS800i, Logatherm WLW boiler 8 maxheatheat heat limit heating enum [0 kW|2 kW|3 kW|4 kW|6 kW|9 kW] True select.boiler_heat_limit_heating select.boiler_maxheatheat 5 0 1 207 1
CS800i, Logatherm WLW boiler 8 dhw.maxheat heat limit enum [0 kW|2 kW|3 kW|4 kW|6 kW|9 kW] True select.boiler_dhw_heat_limit select.boiler_dhw_maxheat 5 9 1 14 1
CS800i, Logatherm WLW boiler 8 auxheatersource aux heater source enum [not installed|electric heater|exclusive|parallel|hybrid] True select.boiler_aux_heater_source select.boiler_auxheatersource 5 0 1 208 1
CS800i, Logatherm WLW boiler 8 pvcooling cooling only with PV boolean True switch.boiler_cooling_only_with_PV switch.boiler_pvcooling 5 0 1 209 1
CS800i, Logatherm WLW boiler 8 auxheateronly aux heater only boolean True switch.boiler_aux_heater_only switch.boiler_auxheateronly 5 0 1 210 1
CS800i, Logatherm WLW boiler 8 auxheateroff disable aux heater boolean True switch.boiler_disable_aux_heater switch.boiler_auxheateroff 5 0 1 211 1
CS800i, Logatherm WLW boiler 8 auxheaterstatus aux heater status enum [off|heating|cooling|hot water|pool|pool heating|defrost|compressor alarm] False sensor.boiler_aux_heater_status sensor.boiler_auxheaterstatus 5 0 1 212 1
CS800i, Logatherm WLW boiler 8 auxheaterlevel aux heater level uint8 (>=0<=100) % False sensor.boiler_aux_heater_level sensor.boiler_auxheaterlevel 5 0 1 213 1
CS800i, Logatherm WLW boiler 8 auxheaterdelay aux heater on delay uint16 (>=10<=1000) K*min True number.boiler_aux_heater_on_delay number.boiler_auxheaterdelay 5 0 10 214 1
CS800i, Logatherm WLW boiler 8 auxmaxlimit aux heater max limit uint8 (>=0<=10) K True number.boiler_aux_heater_max_limit number.boiler_auxmaxlimit 5 0 1/10 215 1
CS800i, Logatherm WLW boiler 8 auxlimitstart aux heater limit start uint8 (>=0<=10) K True number.boiler_aux_heater_limit_start number.boiler_auxlimitstart 5 0 1/10 216 1
CS800i, Logatherm WLW boiler 8 auxheatrmode aux heater mode enum [eco|comfort] True select.boiler_aux_heater_mode select.boiler_auxheatrmode 5 0 1 217 1
CS800i, Logatherm WLW boiler 8 hphystheat on/off hyst heat uint16 (>=50<=1500) K*min True number.boiler_on/off_hyst_heat number.boiler_hphystheat 5 0 5 218 1
CS800i, Logatherm WLW boiler 8 hphystcool on/off hyst cool uint16 (>=50<=1500) K*min True number.boiler_on/off_hyst_cool number.boiler_hphystcool 5 0 5 219 1
CS800i, Logatherm WLW boiler 8 hphystpool on/off hyst pool uint16 (>=50<=1500) K*min True number.boiler_on/off_hyst_pool number.boiler_hphystpool 5 0 5 220 1
CS800i, Logatherm WLW boiler 8 silentmode silent mode enum [off|auto|on] True select.boiler_silent_mode select.boiler_silentmode 5 0 1 221 1
CS800i, Logatherm WLW boiler 8 silentfrom silent mode from uint8 (>=0<=3810) minutes True number.boiler_silent_mode_from number.boiler_silentfrom 5 0 15 222 1
CS800i, Logatherm WLW boiler 8 silentto silent mode to uint8 (>=0<=3810) minutes True number.boiler_silent_mode_to number.boiler_silentto 5 0 15 223 1
CS800i, Logatherm WLW boiler 8 mintempsilent min outside temp for silent mode int8 (>=-126<=126) C True number.boiler_min_outside_temp_for_silent_mode number.boiler_mintempsilent 5 0 1 224 1
CS800i, Logatherm WLW boiler 8 tempparmode outside temp parallel mode int8 (>=-126<=126) C True number.boiler_outside_temp_parallel_mode number.boiler_tempparmode 5 0 1 225 1
CS800i, Logatherm WLW boiler 8 auxheatmix aux heater mixing valve int8 (>=-100<=100) % False sensor.boiler_aux_heater_mixing_valve sensor.boiler_auxheatmix 5 0 1 226 1
CS800i, Logatherm WLW boiler 8 tempdiffheat temp diff TC3/TC0 heat uint8 (>=2<=10) K True number.boiler_temp_diff_TC3/TC0_heat number.boiler_tempdiffheat 5 0 1/10 227 1
CS800i, Logatherm WLW boiler 8 tempdiffcool temp diff TC3/TC0 cool uint8 (>=2<=10) K True number.boiler_temp_diff_TC3/TC0_cool number.boiler_tempdiffcool 5 0 1/10 228 1
CS800i, Logatherm WLW boiler 8 vpcooling valve/pump cooling boolean True switch.boiler_valve/pump_cooling switch.boiler_vpcooling 5 0 1 229 1
CS800i, Logatherm WLW boiler 8 heatcable heating cable boolean True switch.boiler_heating_cable switch.boiler_heatcable 5 0 1 230 1
CS800i, Logatherm WLW boiler 8 vc0valve VC0 valve boolean True switch.boiler_VC0_valve switch.boiler_vc0valve 5 0 1 231 1
CS800i, Logatherm WLW boiler 8 primepump primary heatpump boolean True switch.boiler_primary_heatpump switch.boiler_primepump 5 0 1 232 1
CS800i, Logatherm WLW boiler 8 primepumpmod primary heatpump modulation uint8 (>=0<=100) % True number.boiler_primary_heatpump_modulation number.boiler_primepumpmod 5 0 1 233 1
CS800i, Logatherm WLW boiler 8 hp3way 3-way valve boolean True switch.boiler_3-way_valve switch.boiler_hp3way 5 0 1 234 1
CS800i, Logatherm WLW boiler 8 elheatstep1 el. heater step 1 boolean True switch.boiler_el._heater_step_1 switch.boiler_elheatstep1 5 0 1 235 1
CS800i, Logatherm WLW boiler 8 elheatstep2 el. heater step 2 boolean True switch.boiler_el._heater_step_2 switch.boiler_elheatstep2 5 0 1 236 1
CS800i, Logatherm WLW boiler 8 elheatstep3 el. heater step 3 boolean True switch.boiler_el._heater_step_3 switch.boiler_elheatstep3 5 0 1 237 1
CS800i, Logatherm WLW boiler 8 hpea0 condensate reservoir heating (EA0) boolean False binary_sensor.boiler_condensate_reservoir_heating_(EA0) binary_sensor.boiler_hpea0 5 0 1 238 1
CS800i, Logatherm WLW boiler 8 hppumpmode primary heatpump mode enum [auto|continuous] True select.boiler_primary_heatpump_mode select.boiler_hppumpmode 5 0 1 239 1
CS800i, Logatherm WLW boiler 8 fan fan uint8 (>=20<=100) % True number.boiler_fan number.boiler_fan 5 0 1 240 1
CS800i, Logatherm WLW boiler 8 shutdown shutdown cmd [off|on] True sensor.boiler_shutdown sensor.boiler_shutdown 5 0 1 241 1
CS800i, Logatherm WLW boiler 8 hpcurrpower compressor current power uint16 (>=0<=31999) W False sensor.boiler_compressor_current_power sensor.boiler_hpcurrpower 5 0 1 242 1
CS800i, Logatherm WLW boiler 8 hppowerlimit power limit uint16 (>=0<=31999) W True number.boiler_power_limit number.boiler_hppowerlimit 5 0 1 243 1
CS800i, Logatherm WLW boiler 8 dhw.alternatingop alternating operation boolean True switch.boiler_dhw_alternating_operation switch.boiler_dhw_alternatingop 5 9 1 15 1
CS800i, Logatherm WLW boiler 8 dhw.altopprioheat prioritise heating during dhw uint8 (>=20<=120) minutes True number.boiler_dhw_prioritise_heating_during_dhw number.boiler_dhw_altopprioheat 5 9 1 16 1
CS800i, Logatherm WLW boiler 8 dhw.altopprio prioritise dhw during heating uint8 (>=30<=120) minutes True number.boiler_dhw_prioritise_dhw_during_heating number.boiler_dhw_altopprio 5 9 1 17 1
CS800i, Logatherm WLW boiler 8 dhw.comfoff comfort switch off uint8 (>=15<=65) C True number.boiler_dhw_comfort_switch_off number.boiler_dhw_comfoff 5 9 1 18 1
CS800i, Logatherm WLW boiler 8 dhw.ecooff eco switch off uint8 (>=15<=65) C True number.boiler_dhw_eco_switch_off number.boiler_dhw_ecooff 5 9 1 19 1
CS800i, Logatherm WLW boiler 8 dhw.ecoplusoff eco+ switch off uint8 (>=48<=63) C True number.boiler_dhw_eco+_switch_off number.boiler_dhw_ecoplusoff 5 9 1 20 1
CS800i, Logatherm WLW boiler 8 dhw.comfdiff comfort diff uint8 (>=6<=12) K True number.boiler_dhw_comfort_diff number.boiler_dhw_comfdiff 5 9 1 21 1
CS800i, Logatherm WLW boiler 8 dhw.ecodiff eco diff uint8 (>=6<=12) K True number.boiler_dhw_eco_diff number.boiler_dhw_ecodiff 5 9 1 22 1
CS800i, Logatherm WLW boiler 8 dhw.ecoplusdiff eco+ diff uint8 (>=6<=12) K True number.boiler_dhw_eco+_diff number.boiler_dhw_ecoplusdiff 5 9 1 23 1
CS800i, Logatherm WLW boiler 8 dhw.comfstop comfort stop temp uint8 (>=0<=254) C True number.boiler_dhw_comfort_stop_temp number.boiler_dhw_comfstop 5 9 1 24 1
CS800i, Logatherm WLW boiler 8 dhw.ecostop eco stop temp uint8 (>=0<=254) C True number.boiler_dhw_eco_stop_temp number.boiler_dhw_ecostop 5 9 1 25 1
CS800i, Logatherm WLW boiler 8 dhw.ecoplusstop eco+ stop temp uint8 (>=0<=254) C True number.boiler_dhw_eco+_stop_temp number.boiler_dhw_ecoplusstop 5 9 1 26 1
CS800i, Logatherm WLW boiler 8 dhw.hpcircpump circulation pump available during dhw boolean True switch.boiler_dhw_circulation_pump_available_during_dhw switch.boiler_dhw_hpcircpump 5 9 1 27 1
CS800i, Logatherm WLW boiler 8 dhw.tapactivated turn on/off boolean True switch.boiler_dhw_turn_on/off switch.boiler_dhw_tapactivated 5 9 1 28 1
CS800i, Logatherm WLW boiler 8 dhw.settemp set temperature uint8 (>=0<=254) C False sensor.boiler_dhw_set_temperature sensor.boiler_dhw_settemp 5 9 1 29 1
CS800i, Logatherm WLW boiler 8 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_temperature number.boiler_dhw_seltemp 5 9 1 30 1
CS800i, Logatherm WLW boiler 8 dhw.seltemplow selected lower temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_lower_temperature number.boiler_dhw_seltemplow 5 9 1 31 1
CS800i, Logatherm WLW boiler 8 dhw.tempecoplus selected eco+ temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_eco+_temperature number.boiler_dhw_tempecoplus 5 9 1 32 1
CS800i, Logatherm WLW boiler 8 dhw.seltempoff selected temperature for off uint8 (>=0<=254) C False sensor.boiler_dhw_selected_temperature_for_off sensor.boiler_dhw_seltempoff 5 9 1 33 1
CS800i, Logatherm WLW boiler 8 dhw.seltempsingle single charge temperature uint8 (>=0<=254) C True number.boiler_dhw_single_charge_temperature number.boiler_dhw_seltempsingle 5 9 1 34 1
CS800i, Logatherm WLW boiler 8 dhw.solartemp solar boiler temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_solar_boiler_temperature sensor.boiler_dhw_solartemp 5 9 1/10 35 1
CS800i, Logatherm WLW boiler 8 dhw.type type enum [off|flow|buffered flow|buffer|layered buffer] False sensor.boiler_dhw_type sensor.boiler_dhw_type 5 9 1 36 1
CS800i, Logatherm WLW boiler 8 dhw.comfort comfort enum [hot|eco|intelligent] True select.boiler_dhw_comfort select.boiler_dhw_comfort 5 9 1 37 1
CS800i, Logatherm WLW boiler 8 dhw.comfort1 comfort mode enum [high comfort|eco] True select.boiler_dhw_comfort_mode select.boiler_dhw_comfort1 5 9 1 38 1
CS800i, Logatherm WLW boiler 8 dhw.flowtempoffset flow temperature offset uint8 (>=0<=100) C True number.boiler_dhw_flow_temperature_offset number.boiler_dhw_flowtempoffset 5 9 1 39 1
CS800i, Logatherm WLW boiler 8 dhw.chargeoptimization charge optimization boolean True switch.boiler_dhw_charge_optimization switch.boiler_dhw_chargeoptimization 5 9 1 40 1
CS800i, Logatherm WLW boiler 8 dhw.maxpower max power uint8 (>=0<=254) % True number.boiler_dhw_max_power number.boiler_dhw_maxpower 5 9 1 41 1
CS800i, Logatherm WLW boiler 8 dhw.maxtemp maximum temperature uint8 (>=0<=80) C True number.boiler_dhw_maximum_temperature number.boiler_dhw_maxtemp 5 9 1 42 1
CS800i, Logatherm WLW boiler 8 dhw.circpump circulation pump available boolean True switch.boiler_dhw_circulation_pump_available switch.boiler_dhw_circpump 5 9 1 43 1
CS800i, Logatherm WLW boiler 8 dhw.chargetype charging type enum [chargepump|3-way valve] False sensor.boiler_dhw_charging_type sensor.boiler_dhw_chargetype 5 9 1 44 1
CS800i, Logatherm WLW boiler 8 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_on_temperature number.boiler_dhw_hyston 5 9 1 45 1
CS800i, Logatherm WLW boiler 8 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_off_temperature number.boiler_dhw_hystoff 5 9 1 46 1
CS800i, Logatherm WLW boiler 8 dhw.disinfectiontemp disinfection temperature uint8 (>=60<=80) C True number.boiler_dhw_disinfection_temperature number.boiler_dhw_disinfectiontemp 5 9 1 47 1
CS800i, Logatherm WLW boiler 8 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.boiler_dhw_circulation_pump_mode select.boiler_dhw_circmode 5 9 1 48 1
CS800i, Logatherm WLW boiler 8 dhw.circ circulation active boolean True switch.boiler_dhw_circulation_active switch.boiler_dhw_circ 5 9 1 49 1
CS800i, Logatherm WLW boiler 8 dhw.curtemp current intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_intern_temperature sensor.boiler_dhw_curtemp 5 9 1/10 50 1
CS800i, Logatherm WLW boiler 8 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_extern_temperature sensor.boiler_dhw_curtemp2 5 9 1/10 51 1
CS800i, Logatherm WLW boiler 8 dhw.curflow current tap water flow uint8 (>=0<=25) l/min False sensor.boiler_dhw_current_tap_water_flow sensor.boiler_dhw_curflow 5 9 1/10 52 1
CS800i, Logatherm WLW boiler 8 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_intern_temperature sensor.boiler_dhw_storagetemp1 5 9 1/10 53 1
CS800i, Logatherm WLW boiler 8 dhw.storagetemp2 storage extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_extern_temperature sensor.boiler_dhw_storagetemp2 5 9 1/10 54 1
CS800i, Logatherm WLW boiler 8 dhw.activated activated boolean True switch.boiler_dhw_activated switch.boiler_dhw_activated 5 9 1 55 1
CS800i, Logatherm WLW boiler 8 dhw.onetime one time charging boolean True switch.boiler_dhw_one_time_charging switch.boiler_dhw_onetime 5 9 1 56 1
CS800i, Logatherm WLW boiler 8 dhw.disinfecting disinfecting boolean True switch.boiler_dhw_disinfecting switch.boiler_dhw_disinfecting 5 9 1 57 1
CS800i, Logatherm WLW boiler 8 dhw.charging charging boolean False binary_sensor.boiler_dhw_charging binary_sensor.boiler_dhw_charging 5 9 1 58 1
CS800i, Logatherm WLW boiler 8 dhw.recharging recharging boolean False binary_sensor.boiler_dhw_recharging binary_sensor.boiler_dhw_recharging 5 9 1 59 1
CS800i, Logatherm WLW boiler 8 dhw.tempok temperature ok boolean False binary_sensor.boiler_dhw_temperature_ok binary_sensor.boiler_dhw_tempok 5 9 1 60 1
CS800i, Logatherm WLW boiler 8 dhw.active active boolean False binary_sensor.boiler_dhw_active binary_sensor.boiler_dhw_active 5 9 1 61 1
CS800i, Logatherm WLW boiler 8 dhw.3wayvalve 3-way valve active boolean False binary_sensor.boiler_dhw_3-way_valve_active binary_sensor.boiler_dhw_3wayvalve 5 9 1 62 1
CS800i, Logatherm WLW boiler 8 dhw.mixertemp mixer temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_mixer_temperature sensor.boiler_dhw_mixertemp 5 9 1/10 63 1
CS800i, Logatherm WLW boiler 8 dhw.cylmiddletemp cylinder middle temperature (TS3) uint16 (>=0<=3199) C False sensor.boiler_dhw_cylinder_middle_temperature_(TS3) sensor.boiler_dhw_cylmiddletemp 5 9 1/10 64 1
CS800i, Logatherm WLW boiler 8 dhw.starts starts uint24 (>=0<=16777214) False sensor.boiler_dhw_starts sensor.boiler_dhw_starts 5 9 1 65 2
CS800i, Logatherm WLW boiler 8 dhw.workm active time time (>=0<=16777214) minutes False sensor.boiler_dhw_active_time sensor.boiler_dhw_workm 5 9 1 67 2
C1200W boiler 12 reset reset cmd [-|maintenance|error|history|message] True sensor.boiler_reset sensor.boiler_reset 5 0 1 0 1
C1200W boiler 12 heatingoff force heating off boolean True switch.boiler_force_heating_off switch.boiler_heatingoff 5 0 1 1 1
C1200W boiler 12 heatingactive heating active boolean False binary_sensor.boiler_heating_active binary_sensor.boiler_heatingactive 5 0 1 2 1
C1200W boiler 12 tapwateractive tapwater active boolean False binary_sensor.boiler_tapwater_active binary_sensor.boiler_tapwateractive 5 0 1 3 1
C1200W boiler 12 selflowtemp selected flow temperature uint8 (>=0<=90) C True number.boiler_selected_flow_temperature number.boiler_selflowtemp 5 0 1 4 1
C1200W boiler 12 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.boiler_heating_pump_modulation sensor.boiler_heatingpumpmod 5 0 1 5 1
C1200W boiler 12 outdoortemp outside temperature int16 (>=-3199<=3199) C False sensor.boiler_outside_temperature sensor.boiler_outdoortemp 5 0 1/10 6 1
C1200W boiler 12 curflowtemp current flow temperature uint16 (>=0<=3199) C False sensor.boiler_current_flow_temperature sensor.boiler_curflowtemp 5 0 1/10 7 1
C1200W boiler 12 rettemp return temperature uint16 (>=0<=3199) C False sensor.boiler_return_temperature sensor.boiler_rettemp 5 0 1/10 8 1
C1200W boiler 12 switchtemp mixing switch temperature uint16 (>=0<=3199) C False sensor.boiler_mixing_switch_temperature sensor.boiler_switchtemp 5 0 1/10 9 1
C1200W boiler 12 syspress system pressure uint8 (>=0<=25) bar False sensor.boiler_system_pressure sensor.boiler_syspress 5 0 1/10 10 1
C1200W boiler 12 boiltemp actual boiler temperature uint16 (>=0<=3199) C False sensor.boiler_actual_boiler_temperature sensor.boiler_boiltemp 5 0 1/10 11 1
C1200W boiler 12 headertemp low loss header uint16 (>=0<=3199) C False sensor.boiler_low_loss_header sensor.boiler_headertemp 5 0 1/10 12 1
C1200W boiler 12 exhausttemp exhaust temperature uint16 (>=0<=3199) C False sensor.boiler_exhaust_temperature sensor.boiler_exhausttemp 5 0 1/10 244 1
C1200W boiler 12 burngas gas boolean False binary_sensor.boiler_gas binary_sensor.boiler_burngas 5 0 1 245 1
C1200W boiler 12 burngas2 gas stage 2 boolean False binary_sensor.boiler_gas_stage_2 binary_sensor.boiler_burngas2 5 0 1 246 1
C1200W boiler 12 flamecurr flame current uint16 (>=0<=3199) µA False sensor.boiler_flame_current sensor.boiler_flamecurr 5 0 1/10 247 1
C1200W boiler 12 fanwork fan boolean False binary_sensor.boiler_fan binary_sensor.boiler_fanwork 5 0 1 248 1
C1200W boiler 12 ignwork ignition boolean False binary_sensor.boiler_ignition binary_sensor.boiler_ignwork 5 0 1 249 1
C1200W boiler 12 oilpreheat oil preheating boolean False binary_sensor.boiler_oil_preheating binary_sensor.boiler_oilpreheat 5 0 1 250 1
C1200W boiler 12 burnminpower burner min power uint8 (>=0<=100) % True number.boiler_burner_min_power number.boiler_burnminpower 5 0 1 251 1
C1200W boiler 12 burnmaxpower burner max power uint8 (>=0<=254) % True number.boiler_burner_max_power number.boiler_burnmaxpower 5 0 1 252 1
C1200W boiler 12 burnminperiod burner min period uint8 (>=0<=120) minutes True number.boiler_burner_min_period number.boiler_burnminperiod 5 0 1 253 1
C1200W boiler 12 absburnpow burner current power (absolute) uint8 (>=0<=100) % False sensor.boiler_burner_current_power_(absolute) sensor.boiler_absburnpow 5 0 1 254 1
C1200W boiler 12 heatblock heating block uint16 (>=0<=3199) C False sensor.boiler_heating_block sensor.boiler_heatblock 5 0 1/10 255 1
C1200W boiler 12 boilhyston hysteresis on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_on_temperature number.boiler_boilhyston 5 0 1 256 1
C1200W boiler 12 boilhystoff hysteresis off temperature int8 (>=0<=20) C True number.boiler_hysteresis_off_temperature number.boiler_boilhystoff 5 0 1 257 1
C1200W boiler 12 boil2hyston hysteresis stage 2 on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_stage_2_on_temperature number.boiler_boil2hyston 5 0 1 258 1
C1200W boiler 12 boil2hystoff hysteresis stage 2 off temperature int8 (>=0<=20) C True number.boiler_hysteresis_stage_2_off_temperature number.boiler_boil2hystoff 5 0 1 259 1
C1200W boiler 12 curveon heatingcurve on boolean True switch.boiler_heatingcurve_on switch.boiler_curveon 5 0 1 260 1
C1200W boiler 12 curvebase heatingcurve base uint8 (>=20<=90) C True number.boiler_heatingcurve_base number.boiler_curvebase 5 0 1 261 1
C1200W boiler 12 curveend heatingcurve end uint8 (>=20<=90) C True number.boiler_heatingcurve_end number.boiler_curveend 5 0 1 262 1
C1200W boiler 12 summertemp summer temperature uint8 (>=0<=45) C True number.boiler_summer_temperature number.boiler_summertemp 5 0 1 263 1
C1200W boiler 12 nofrostmode nofrost mode boolean True switch.boiler_nofrost_mode switch.boiler_nofrostmode 5 0 1 264 1
C1200W boiler 12 nofrosttemp nofrost temperature uint8 (>=0<=10) C True number.boiler_nofrost_temperature number.boiler_nofrosttemp 5 0 1 265 1
C1200W boiler 12 heatingactivated heating activated boolean True switch.boiler_heating_activated switch.boiler_heatingactivated 5 0 1 13 1
C1200W boiler 12 heatingtemp heating temperature uint8 (>=0<=90) C True number.boiler_heating_temperature number.boiler_heatingtemp 5 0 1 14 1
C1200W boiler 12 heatingpump heating pump boolean False binary_sensor.boiler_heating_pump binary_sensor.boiler_heatingpump 5 0 1 15 1
C1200W boiler 12 pumpmodmax boiler pump max power uint8 (>=0<=100) % True number.boiler_boiler_pump_max_power number.boiler_pumpmodmax 5 0 1 16 1
C1200W boiler 12 pumpmodmin boiler pump min power uint8 (>=0<=100) % True number.boiler_boiler_pump_min_power number.boiler_pumpmodmin 5 0 1 17 1
C1200W boiler 12 pumpmode boiler pump mode enum [proportional|deltaP-1|deltaP-2|deltaP-3|deltaP-4] True select.boiler_boiler_pump_mode select.boiler_pumpmode 5 0 1 18 1
C1200W boiler 12 pumpcharacter boiler pump characteristic enum [proportional|150mbar|200mbar|250mbar|300mbar|350mbar|400mbar] True select.boiler_boiler_pump_characteristic select.boiler_pumpcharacter 5 0 1 19 1
C1200W boiler 12 pumpdelay pump delay uint8 (>=0<=60) minutes True number.boiler_pump_delay number.boiler_pumpdelay 5 0 1 20 1
C1200W boiler 12 pumpontemp pump logic temperature uint8 (>=0<=60) C True number.boiler_pump_logic_temperature number.boiler_pumpontemp 5 0 1 21 1
C1200W boiler 12 selburnpow burner selected max power uint8 (>=0<=254) % True number.boiler_burner_selected_max_power number.boiler_selburnpow 5 0 1 22 1
C1200W boiler 12 curburnpow burner current power uint8 (>=0<=100) % False sensor.boiler_burner_current_power sensor.boiler_curburnpow 5 0 1 23 1
C1200W boiler 12 burnstarts burner starts uint24 (>=0<=16777214) False sensor.boiler_burner_starts sensor.boiler_burnstarts 5 0 1 24 2
C1200W boiler 12 burnworkmin total burner operating time time (>=0<=16777214) minutes False sensor.boiler_total_burner_operating_time sensor.boiler_burnworkmin 5 0 1 26 2
C1200W boiler 12 burn2workmin burner stage 2 operating time time (>=0<=16777214) minutes False sensor.boiler_burner_stage_2_operating_time sensor.boiler_burn2workmin 5 0 1 28 2
C1200W boiler 12 heatworkmin total heat operating time time (>=0<=16777214) minutes False sensor.boiler_total_heat_operating_time sensor.boiler_heatworkmin 5 0 1 30 2
C1200W boiler 12 heatstarts burner starts heating uint24 (>=0<=16777214) False sensor.boiler_burner_starts_heating sensor.boiler_heatstarts 5 0 1 32 2
C1200W boiler 12 ubauptime total UBA operating time time (>=0<=16777214) minutes False sensor.boiler_total_UBA_operating_time sensor.boiler_ubauptime 5 0 1 34 2
C1200W boiler 12 lastcode last error code string False sensor.boiler_last_error_code sensor.boiler_lastcode 5 0 1 36 28
C1200W boiler 12 servicecode service code string False sensor.boiler_service_code sensor.boiler_servicecode 5 0 1 64 2
C1200W boiler 12 servicecodenumber service code number uint16 (>=0<=31999) False sensor.boiler_service_code_number sensor.boiler_servicecodenumber 5 0 1 66 1
C1200W boiler 12 maintenancemessage maintenance message string False sensor.boiler_maintenance_message sensor.boiler_maintenancemessage 5 0 1 67 2
C1200W boiler 12 maintenance maintenance scheduled enum [off|time|date|manual] True select.boiler_maintenance_scheduled select.boiler_maintenance 5 0 1 69 1
C1200W boiler 12 maintenancetime time to next maintenance uint16 (>=0<=31999) hours True number.boiler_time_to_next_maintenance number.boiler_maintenancetime 5 0 1 70 1
C1200W boiler 12 maintenancedate next maintenance date string True sensor.boiler_next_maintenance_date sensor.boiler_maintenancedate 5 0 1 71 6
C1200W boiler 12 emergencyops emergency operation boolean True switch.boiler_emergency_operation switch.boiler_emergencyops 5 0 1 77 1
C1200W boiler 12 emergencytemp emergency temperature uint8 (>=15<=70) C True number.boiler_emergency_temperature number.boiler_emergencytemp 5 0 1 78 1
C1200W boiler 12 pc0flow Flow PC0 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC0 sensor.boiler_pc0flow 5 0 1 79 1
C1200W boiler 12 pc1flow Flow PC1 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC1 sensor.boiler_pc1flow 5 0 1 80 1
C1200W boiler 12 pc1on PC1 boolean False binary_sensor.boiler_PC1 binary_sensor.boiler_pc1on 5 0 1 81 1
C1200W boiler 12 pc1rate PC1 rate uint8 (>=0<=100) % False sensor.boiler_PC1_rate sensor.boiler_pc1rate 5 0 1 82 1
C1200W boiler 12 meterheat meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_meter_heating sensor.boiler_meterheat 5 0 1/10 95 2
C1200W boiler 12 dhw.meter meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_meter sensor.boiler_dhw_meter 5 9 1/10 2 2
C1200W boiler 12 gasmeterheat gas meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_gas_meter_heating sensor.boiler_gasmeterheat 5 0 1/10 266 2
C1200W boiler 12 dhw.gasmeter gas meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_gas_meter sensor.boiler_dhw_gasmeter 5 9 1/10 69 2
C1200W boiler 12 nrgheat2 energy heating 2 uint24 (>=0<=1677721) kWh False sensor.boiler_energy_heating_2 sensor.boiler_nrgheat2 5 0 1/10 268 2
C1200W boiler 12 dhw.nrg2 energy 2 uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_energy_2 sensor.boiler_dhw_nrg2 5 9 1/10 71 2
C1200W boiler 12 dhw.tapactivated turn on/off boolean True switch.boiler_dhw_turn_on/off switch.boiler_dhw_tapactivated 5 9 1 28 1
C1200W boiler 12 dhw.settemp set temperature uint8 (>=0<=254) C False sensor.boiler_dhw_set_temperature sensor.boiler_dhw_settemp 5 9 1 29 1
C1200W boiler 12 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_temperature number.boiler_dhw_seltemp 5 9 1 30 1
C1200W boiler 12 dhw.seltemplow selected lower temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_lower_temperature number.boiler_dhw_seltemplow 5 9 1 31 1
C1200W boiler 12 dhw.tempecoplus selected eco+ temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_eco+_temperature number.boiler_dhw_tempecoplus 5 9 1 32 1
C1200W boiler 12 dhw.seltempoff selected temperature for off uint8 (>=0<=254) C False sensor.boiler_dhw_selected_temperature_for_off sensor.boiler_dhw_seltempoff 5 9 1 33 1
C1200W boiler 12 dhw.seltempsingle single charge temperature uint8 (>=0<=254) C True number.boiler_dhw_single_charge_temperature number.boiler_dhw_seltempsingle 5 9 1 34 1
C1200W boiler 12 dhw.solartemp solar boiler temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_solar_boiler_temperature sensor.boiler_dhw_solartemp 5 9 1/10 35 1
C1200W boiler 12 dhw.type type enum [off|flow|buffered flow|buffer|layered buffer] False sensor.boiler_dhw_type sensor.boiler_dhw_type 5 9 1 36 1
C1200W boiler 12 dhw.comfort comfort enum [hot|eco|intelligent] True select.boiler_dhw_comfort select.boiler_dhw_comfort 5 9 1 37 1
C1200W boiler 12 dhw.comfort1 comfort mode enum [high comfort|eco] True select.boiler_dhw_comfort_mode select.boiler_dhw_comfort1 5 9 1 38 1
C1200W boiler 12 dhw.flowtempoffset flow temperature offset uint8 (>=0<=100) C True number.boiler_dhw_flow_temperature_offset number.boiler_dhw_flowtempoffset 5 9 1 39 1
C1200W boiler 12 dhw.chargeoptimization charge optimization boolean True switch.boiler_dhw_charge_optimization switch.boiler_dhw_chargeoptimization 5 9 1 40 1
C1200W boiler 12 dhw.maxpower max power uint8 (>=0<=254) % True number.boiler_dhw_max_power number.boiler_dhw_maxpower 5 9 1 41 1
C1200W boiler 12 dhw.maxtemp maximum temperature uint8 (>=0<=80) C True number.boiler_dhw_maximum_temperature number.boiler_dhw_maxtemp 5 9 1 42 1
C1200W boiler 12 dhw.circpump circulation pump available boolean True switch.boiler_dhw_circulation_pump_available switch.boiler_dhw_circpump 5 9 1 43 1
C1200W boiler 12 dhw.chargetype charging type enum [chargepump|3-way valve] False sensor.boiler_dhw_charging_type sensor.boiler_dhw_chargetype 5 9 1 44 1
C1200W boiler 12 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_on_temperature number.boiler_dhw_hyston 5 9 1 45 1
C1200W boiler 12 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_off_temperature number.boiler_dhw_hystoff 5 9 1 46 1
C1200W boiler 12 dhw.disinfectiontemp disinfection temperature uint8 (>=60<=80) C True number.boiler_dhw_disinfection_temperature number.boiler_dhw_disinfectiontemp 5 9 1 47 1
C1200W boiler 12 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.boiler_dhw_circulation_pump_mode select.boiler_dhw_circmode 5 9 1 48 1
C1200W boiler 12 dhw.circ circulation active boolean True switch.boiler_dhw_circulation_active switch.boiler_dhw_circ 5 9 1 49 1
C1200W boiler 12 dhw.curtemp current intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_intern_temperature sensor.boiler_dhw_curtemp 5 9 1/10 50 1
C1200W boiler 12 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_extern_temperature sensor.boiler_dhw_curtemp2 5 9 1/10 51 1
C1200W boiler 12 dhw.curflow current tap water flow uint8 (>=0<=25) l/min False sensor.boiler_dhw_current_tap_water_flow sensor.boiler_dhw_curflow 5 9 1/10 52 1
C1200W boiler 12 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_intern_temperature sensor.boiler_dhw_storagetemp1 5 9 1/10 53 1
C1200W boiler 12 dhw.storagetemp2 storage extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_extern_temperature sensor.boiler_dhw_storagetemp2 5 9 1/10 54 1
C1200W boiler 12 dhw.activated activated boolean True switch.boiler_dhw_activated switch.boiler_dhw_activated 5 9 1 55 1
C1200W boiler 12 dhw.onetime one time charging boolean True switch.boiler_dhw_one_time_charging switch.boiler_dhw_onetime 5 9 1 56 1
C1200W boiler 12 dhw.disinfecting disinfecting boolean True switch.boiler_dhw_disinfecting switch.boiler_dhw_disinfecting 5 9 1 57 1
C1200W boiler 12 dhw.charging charging boolean False binary_sensor.boiler_dhw_charging binary_sensor.boiler_dhw_charging 5 9 1 58 1
C1200W boiler 12 dhw.recharging recharging boolean False binary_sensor.boiler_dhw_recharging binary_sensor.boiler_dhw_recharging 5 9 1 59 1
C1200W boiler 12 dhw.tempok temperature ok boolean False binary_sensor.boiler_dhw_temperature_ok binary_sensor.boiler_dhw_tempok 5 9 1 60 1
C1200W boiler 12 dhw.active active boolean False binary_sensor.boiler_dhw_active binary_sensor.boiler_dhw_active 5 9 1 61 1
C1200W boiler 12 dhw.3wayvalve 3-way valve active boolean False binary_sensor.boiler_dhw_3-way_valve_active binary_sensor.boiler_dhw_3wayvalve 5 9 1 62 1
C1200W boiler 12 dhw.mixertemp mixer temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_mixer_temperature sensor.boiler_dhw_mixertemp 5 9 1/10 63 1
C1200W boiler 12 dhw.cylmiddletemp cylinder middle temperature (TS3) uint16 (>=0<=3199) C False sensor.boiler_dhw_cylinder_middle_temperature_(TS3) sensor.boiler_dhw_cylmiddletemp 5 9 1/10 64 1
C1200W boiler 12 dhw.starts starts uint24 (>=0<=16777214) False sensor.boiler_dhw_starts sensor.boiler_dhw_starts 5 9 1 65 2
C1200W boiler 12 dhw.workm active time time (>=0<=16777214) minutes False sensor.boiler_dhw_active_time sensor.boiler_dhw_workm 5 9 1 67 2
C1200W boiler 12 nompower nominal Power uint8 (>=0<=254) kW True number.boiler_nominal_Power number.boiler_nompower 5 0 1 270 1
C1200W boiler 12 nrgtotal total energy uint24 (>=0<=167772) kWh False sensor.boiler_total_energy sensor.boiler_nrgtotal 5 0 1/100 83 2
C1200W boiler 12 nrgheat energy heating uint24 (>=0<=10000000) kWh True number.boiler_energy_heating number.boiler_nrgheat 5 0 1/100 85 2
C1200W boiler 12 dhw.nrg energy uint24 (>=0<=10000000) kWh True number.boiler_dhw_energy number.boiler_dhw_nrg 5 9 1/100 0 2
BK13/BK15, Smartline, GB1*2 boiler 64 reset reset cmd [-|maintenance|error|history|message] True sensor.boiler_reset sensor.boiler_reset 5 0 1 0 1
BK13/BK15, Smartline, GB1*2 boiler 64 heatingoff force heating off boolean True switch.boiler_force_heating_off switch.boiler_heatingoff 5 0 1 1 1
BK13/BK15, Smartline, GB1*2 boiler 64 heatingactive heating active boolean False binary_sensor.boiler_heating_active binary_sensor.boiler_heatingactive 5 0 1 2 1
BK13/BK15, Smartline, GB1*2 boiler 64 tapwateractive tapwater active boolean False binary_sensor.boiler_tapwater_active binary_sensor.boiler_tapwateractive 5 0 1 3 1
BK13/BK15, Smartline, GB1*2 boiler 64 selflowtemp selected flow temperature uint8 (>=0<=90) C True number.boiler_selected_flow_temperature number.boiler_selflowtemp 5 0 1 4 1
BK13/BK15, Smartline, GB1*2 boiler 64 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.boiler_heating_pump_modulation sensor.boiler_heatingpumpmod 5 0 1 5 1
BK13/BK15, Smartline, GB1*2 boiler 64 outdoortemp outside temperature int16 (>=-3199<=3199) C False sensor.boiler_outside_temperature sensor.boiler_outdoortemp 5 0 1/10 6 1
BK13/BK15, Smartline, GB1*2 boiler 64 curflowtemp current flow temperature uint16 (>=0<=3199) C False sensor.boiler_current_flow_temperature sensor.boiler_curflowtemp 5 0 1/10 7 1
BK13/BK15, Smartline, GB1*2 boiler 64 rettemp return temperature uint16 (>=0<=3199) C False sensor.boiler_return_temperature sensor.boiler_rettemp 5 0 1/10 8 1
BK13/BK15, Smartline, GB1*2 boiler 64 switchtemp mixing switch temperature uint16 (>=0<=3199) C False sensor.boiler_mixing_switch_temperature sensor.boiler_switchtemp 5 0 1/10 9 1
BK13/BK15, Smartline, GB1*2 boiler 64 syspress system pressure uint8 (>=0<=25) bar False sensor.boiler_system_pressure sensor.boiler_syspress 5 0 1/10 10 1
BK13/BK15, Smartline, GB1*2 boiler 64 boiltemp actual boiler temperature uint16 (>=0<=3199) C False sensor.boiler_actual_boiler_temperature sensor.boiler_boiltemp 5 0 1/10 11 1
BK13/BK15, Smartline, GB1*2 boiler 64 headertemp low loss header uint16 (>=0<=3199) C False sensor.boiler_low_loss_header sensor.boiler_headertemp 5 0 1/10 12 1
BK13/BK15, Smartline, GB1*2 boiler 64 exhausttemp exhaust temperature uint16 (>=0<=3199) C False sensor.boiler_exhaust_temperature sensor.boiler_exhausttemp 5 0 1/10 244 1
BK13/BK15, Smartline, GB1*2 boiler 64 burngas gas boolean False binary_sensor.boiler_gas binary_sensor.boiler_burngas 5 0 1 245 1
BK13/BK15, Smartline, GB1*2 boiler 64 burngas2 gas stage 2 boolean False binary_sensor.boiler_gas_stage_2 binary_sensor.boiler_burngas2 5 0 1 246 1
BK13/BK15, Smartline, GB1*2 boiler 64 flamecurr flame current uint16 (>=0<=3199) µA False sensor.boiler_flame_current sensor.boiler_flamecurr 5 0 1/10 247 1
BK13/BK15, Smartline, GB1*2 boiler 64 fanwork fan boolean False binary_sensor.boiler_fan binary_sensor.boiler_fanwork 5 0 1 248 1
BK13/BK15, Smartline, GB1*2 boiler 64 ignwork ignition boolean False binary_sensor.boiler_ignition binary_sensor.boiler_ignwork 5 0 1 249 1
BK13/BK15, Smartline, GB1*2 boiler 64 oilpreheat oil preheating boolean False binary_sensor.boiler_oil_preheating binary_sensor.boiler_oilpreheat 5 0 1 250 1
BK13/BK15, Smartline, GB1*2 boiler 64 burnminpower burner min power uint8 (>=0<=100) % True number.boiler_burner_min_power number.boiler_burnminpower 5 0 1 251 1
BK13/BK15, Smartline, GB1*2 boiler 64 burnmaxpower burner max power uint8 (>=0<=254) % True number.boiler_burner_max_power number.boiler_burnmaxpower 5 0 1 252 1
BK13/BK15, Smartline, GB1*2 boiler 64 burnminperiod burner min period uint8 (>=0<=120) minutes True number.boiler_burner_min_period number.boiler_burnminperiod 5 0 1 253 1
BK13/BK15, Smartline, GB1*2 boiler 64 absburnpow burner current power (absolute) uint8 (>=0<=100) % False sensor.boiler_burner_current_power_(absolute) sensor.boiler_absburnpow 5 0 1 254 1
BK13/BK15, Smartline, GB1*2 boiler 64 heatblock heating block uint16 (>=0<=3199) C False sensor.boiler_heating_block sensor.boiler_heatblock 5 0 1/10 255 1
BK13/BK15, Smartline, GB1*2 boiler 64 boilhyston hysteresis on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_on_temperature number.boiler_boilhyston 5 0 1 256 1
BK13/BK15, Smartline, GB1*2 boiler 64 boilhystoff hysteresis off temperature int8 (>=0<=20) C True number.boiler_hysteresis_off_temperature number.boiler_boilhystoff 5 0 1 257 1
BK13/BK15, Smartline, GB1*2 boiler 64 boil2hyston hysteresis stage 2 on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_stage_2_on_temperature number.boiler_boil2hyston 5 0 1 258 1
BK13/BK15, Smartline, GB1*2 boiler 64 boil2hystoff hysteresis stage 2 off temperature int8 (>=0<=20) C True number.boiler_hysteresis_stage_2_off_temperature number.boiler_boil2hystoff 5 0 1 259 1
BK13/BK15, Smartline, GB1*2 boiler 64 curveon heatingcurve on boolean True switch.boiler_heatingcurve_on switch.boiler_curveon 5 0 1 260 1
BK13/BK15, Smartline, GB1*2 boiler 64 curvebase heatingcurve base uint8 (>=20<=90) C True number.boiler_heatingcurve_base number.boiler_curvebase 5 0 1 261 1
BK13/BK15, Smartline, GB1*2 boiler 64 curveend heatingcurve end uint8 (>=20<=90) C True number.boiler_heatingcurve_end number.boiler_curveend 5 0 1 262 1
BK13/BK15, Smartline, GB1*2 boiler 64 summertemp summer temperature uint8 (>=0<=45) C True number.boiler_summer_temperature number.boiler_summertemp 5 0 1 263 1
BK13/BK15, Smartline, GB1*2 boiler 64 nofrostmode nofrost mode boolean True switch.boiler_nofrost_mode switch.boiler_nofrostmode 5 0 1 264 1
BK13/BK15, Smartline, GB1*2 boiler 64 nofrosttemp nofrost temperature uint8 (>=0<=10) C True number.boiler_nofrost_temperature number.boiler_nofrosttemp 5 0 1 265 1
BK13/BK15, Smartline, GB1*2 boiler 64 heatingactivated heating activated boolean True switch.boiler_heating_activated switch.boiler_heatingactivated 5 0 1 13 1
BK13/BK15, Smartline, GB1*2 boiler 64 heatingtemp heating temperature uint8 (>=0<=90) C True number.boiler_heating_temperature number.boiler_heatingtemp 5 0 1 14 1
BK13/BK15, Smartline, GB1*2 boiler 64 heatingpump heating pump boolean False binary_sensor.boiler_heating_pump binary_sensor.boiler_heatingpump 5 0 1 15 1
BK13/BK15, Smartline, GB1*2 boiler 64 pumpmodmax boiler pump max power uint8 (>=0<=100) % True number.boiler_boiler_pump_max_power number.boiler_pumpmodmax 5 0 1 16 1
BK13/BK15, Smartline, GB1*2 boiler 64 pumpmodmin boiler pump min power uint8 (>=0<=100) % True number.boiler_boiler_pump_min_power number.boiler_pumpmodmin 5 0 1 17 1
BK13/BK15, Smartline, GB1*2 boiler 64 pumpmode boiler pump mode enum [proportional|deltaP-1|deltaP-2|deltaP-3|deltaP-4] True select.boiler_boiler_pump_mode select.boiler_pumpmode 5 0 1 18 1
BK13/BK15, Smartline, GB1*2 boiler 64 pumpcharacter boiler pump characteristic enum [proportional|150mbar|200mbar|250mbar|300mbar|350mbar|400mbar] True select.boiler_boiler_pump_characteristic select.boiler_pumpcharacter 5 0 1 19 1
BK13/BK15, Smartline, GB1*2 boiler 64 pumpdelay pump delay uint8 (>=0<=60) minutes True number.boiler_pump_delay number.boiler_pumpdelay 5 0 1 20 1
BK13/BK15, Smartline, GB1*2 boiler 64 pumpontemp pump logic temperature uint8 (>=0<=60) C True number.boiler_pump_logic_temperature number.boiler_pumpontemp 5 0 1 21 1
BK13/BK15, Smartline, GB1*2 boiler 64 selburnpow burner selected max power uint8 (>=0<=254) % True number.boiler_burner_selected_max_power number.boiler_selburnpow 5 0 1 22 1
BK13/BK15, Smartline, GB1*2 boiler 64 curburnpow burner current power uint8 (>=0<=100) % False sensor.boiler_burner_current_power sensor.boiler_curburnpow 5 0 1 23 1
BK13/BK15, Smartline, GB1*2 boiler 64 burnstarts burner starts uint24 (>=0<=16777214) False sensor.boiler_burner_starts sensor.boiler_burnstarts 5 0 1 24 2
BK13/BK15, Smartline, GB1*2 boiler 64 burnworkmin total burner operating time time (>=0<=16777214) minutes False sensor.boiler_total_burner_operating_time sensor.boiler_burnworkmin 5 0 1 26 2
BK13/BK15, Smartline, GB1*2 boiler 64 burn2workmin burner stage 2 operating time time (>=0<=16777214) minutes False sensor.boiler_burner_stage_2_operating_time sensor.boiler_burn2workmin 5 0 1 28 2
BK13/BK15, Smartline, GB1*2 boiler 64 heatworkmin total heat operating time time (>=0<=16777214) minutes False sensor.boiler_total_heat_operating_time sensor.boiler_heatworkmin 5 0 1 30 2
BK13/BK15, Smartline, GB1*2 boiler 64 heatstarts burner starts heating uint24 (>=0<=16777214) False sensor.boiler_burner_starts_heating sensor.boiler_heatstarts 5 0 1 32 2
BK13/BK15, Smartline, GB1*2 boiler 64 ubauptime total UBA operating time time (>=0<=16777214) minutes False sensor.boiler_total_UBA_operating_time sensor.boiler_ubauptime 5 0 1 34 2
BK13/BK15, Smartline, GB1*2 boiler 64 lastcode last error code string False sensor.boiler_last_error_code sensor.boiler_lastcode 5 0 1 36 28
BK13/BK15, Smartline, GB1*2 boiler 64 servicecode service code string False sensor.boiler_service_code sensor.boiler_servicecode 5 0 1 64 2
BK13/BK15, Smartline, GB1*2 boiler 64 servicecodenumber service code number uint16 (>=0<=31999) False sensor.boiler_service_code_number sensor.boiler_servicecodenumber 5 0 1 66 1
BK13/BK15, Smartline, GB1*2 boiler 64 maintenancemessage maintenance message string False sensor.boiler_maintenance_message sensor.boiler_maintenancemessage 5 0 1 67 2
BK13/BK15, Smartline, GB1*2 boiler 64 maintenance maintenance scheduled enum [off|time|date|manual] True select.boiler_maintenance_scheduled select.boiler_maintenance 5 0 1 69 1
BK13/BK15, Smartline, GB1*2 boiler 64 maintenancetime time to next maintenance uint16 (>=0<=31999) hours True number.boiler_time_to_next_maintenance number.boiler_maintenancetime 5 0 1 70 1
BK13/BK15, Smartline, GB1*2 boiler 64 maintenancedate next maintenance date string True sensor.boiler_next_maintenance_date sensor.boiler_maintenancedate 5 0 1 71 6
BK13/BK15, Smartline, GB1*2 boiler 64 emergencyops emergency operation boolean True switch.boiler_emergency_operation switch.boiler_emergencyops 5 0 1 77 1
BK13/BK15, Smartline, GB1*2 boiler 64 emergencytemp emergency temperature uint8 (>=15<=70) C True number.boiler_emergency_temperature number.boiler_emergencytemp 5 0 1 78 1
BK13/BK15, Smartline, GB1*2 boiler 64 pc0flow Flow PC0 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC0 sensor.boiler_pc0flow 5 0 1 79 1
BK13/BK15, Smartline, GB1*2 boiler 64 pc1flow Flow PC1 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC1 sensor.boiler_pc1flow 5 0 1 80 1
BK13/BK15, Smartline, GB1*2 boiler 64 pc1on PC1 boolean False binary_sensor.boiler_PC1 binary_sensor.boiler_pc1on 5 0 1 81 1
BK13/BK15, Smartline, GB1*2 boiler 64 pc1rate PC1 rate uint8 (>=0<=100) % False sensor.boiler_PC1_rate sensor.boiler_pc1rate 5 0 1 82 1
BK13/BK15, Smartline, GB1*2 boiler 64 meterheat meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_meter_heating sensor.boiler_meterheat 5 0 1/10 95 2
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.meter meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_meter sensor.boiler_dhw_meter 5 9 1/10 2 2
BK13/BK15, Smartline, GB1*2 boiler 64 gasmeterheat gas meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_gas_meter_heating sensor.boiler_gasmeterheat 5 0 1/10 266 2
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.gasmeter gas meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_gas_meter sensor.boiler_dhw_gasmeter 5 9 1/10 69 2
BK13/BK15, Smartline, GB1*2 boiler 64 nrgheat2 energy heating 2 uint24 (>=0<=1677721) kWh False sensor.boiler_energy_heating_2 sensor.boiler_nrgheat2 5 0 1/10 268 2
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.nrg2 energy 2 uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_energy_2 sensor.boiler_dhw_nrg2 5 9 1/10 71 2
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.tapactivated turn on/off boolean True switch.boiler_dhw_turn_on/off switch.boiler_dhw_tapactivated 5 9 1 28 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.settemp set temperature uint8 (>=0<=254) C False sensor.boiler_dhw_set_temperature sensor.boiler_dhw_settemp 5 9 1 29 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_temperature number.boiler_dhw_seltemp 5 9 1 30 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.seltemplow selected lower temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_lower_temperature number.boiler_dhw_seltemplow 5 9 1 31 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.tempecoplus selected eco+ temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_eco+_temperature number.boiler_dhw_tempecoplus 5 9 1 32 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.seltempoff selected temperature for off uint8 (>=0<=254) C False sensor.boiler_dhw_selected_temperature_for_off sensor.boiler_dhw_seltempoff 5 9 1 33 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.seltempsingle single charge temperature uint8 (>=0<=254) C True number.boiler_dhw_single_charge_temperature number.boiler_dhw_seltempsingle 5 9 1 34 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.solartemp solar boiler temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_solar_boiler_temperature sensor.boiler_dhw_solartemp 5 9 1/10 35 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.type type enum [off|flow|buffered flow|buffer|layered buffer] False sensor.boiler_dhw_type sensor.boiler_dhw_type 5 9 1 36 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.comfort comfort enum [hot|eco|intelligent] True select.boiler_dhw_comfort select.boiler_dhw_comfort 5 9 1 37 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.comfort1 comfort mode enum [high comfort|eco] True select.boiler_dhw_comfort_mode select.boiler_dhw_comfort1 5 9 1 38 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.flowtempoffset flow temperature offset uint8 (>=0<=100) C True number.boiler_dhw_flow_temperature_offset number.boiler_dhw_flowtempoffset 5 9 1 39 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.chargeoptimization charge optimization boolean True switch.boiler_dhw_charge_optimization switch.boiler_dhw_chargeoptimization 5 9 1 40 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.maxpower max power uint8 (>=0<=254) % True number.boiler_dhw_max_power number.boiler_dhw_maxpower 5 9 1 41 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.maxtemp maximum temperature uint8 (>=0<=80) C True number.boiler_dhw_maximum_temperature number.boiler_dhw_maxtemp 5 9 1 42 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.circpump circulation pump available boolean True switch.boiler_dhw_circulation_pump_available switch.boiler_dhw_circpump 5 9 1 43 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.chargetype charging type enum [chargepump|3-way valve] False sensor.boiler_dhw_charging_type sensor.boiler_dhw_chargetype 5 9 1 44 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_on_temperature number.boiler_dhw_hyston 5 9 1 45 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_off_temperature number.boiler_dhw_hystoff 5 9 1 46 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.disinfectiontemp disinfection temperature uint8 (>=60<=80) C True number.boiler_dhw_disinfection_temperature number.boiler_dhw_disinfectiontemp 5 9 1 47 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.boiler_dhw_circulation_pump_mode select.boiler_dhw_circmode 5 9 1 48 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.circ circulation active boolean True switch.boiler_dhw_circulation_active switch.boiler_dhw_circ 5 9 1 49 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.curtemp current intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_intern_temperature sensor.boiler_dhw_curtemp 5 9 1/10 50 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_extern_temperature sensor.boiler_dhw_curtemp2 5 9 1/10 51 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.curflow current tap water flow uint8 (>=0<=25) l/min False sensor.boiler_dhw_current_tap_water_flow sensor.boiler_dhw_curflow 5 9 1/10 52 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_intern_temperature sensor.boiler_dhw_storagetemp1 5 9 1/10 53 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.storagetemp2 storage extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_extern_temperature sensor.boiler_dhw_storagetemp2 5 9 1/10 54 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.activated activated boolean True switch.boiler_dhw_activated switch.boiler_dhw_activated 5 9 1 55 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.onetime one time charging boolean True switch.boiler_dhw_one_time_charging switch.boiler_dhw_onetime 5 9 1 56 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.disinfecting disinfecting boolean True switch.boiler_dhw_disinfecting switch.boiler_dhw_disinfecting 5 9 1 57 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.charging charging boolean False binary_sensor.boiler_dhw_charging binary_sensor.boiler_dhw_charging 5 9 1 58 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.recharging recharging boolean False binary_sensor.boiler_dhw_recharging binary_sensor.boiler_dhw_recharging 5 9 1 59 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.tempok temperature ok boolean False binary_sensor.boiler_dhw_temperature_ok binary_sensor.boiler_dhw_tempok 5 9 1 60 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.active active boolean False binary_sensor.boiler_dhw_active binary_sensor.boiler_dhw_active 5 9 1 61 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.3wayvalve 3-way valve active boolean False binary_sensor.boiler_dhw_3-way_valve_active binary_sensor.boiler_dhw_3wayvalve 5 9 1 62 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.mixertemp mixer temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_mixer_temperature sensor.boiler_dhw_mixertemp 5 9 1/10 63 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.cylmiddletemp cylinder middle temperature (TS3) uint16 (>=0<=3199) C False sensor.boiler_dhw_cylinder_middle_temperature_(TS3) sensor.boiler_dhw_cylmiddletemp 5 9 1/10 64 1
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.starts starts uint24 (>=0<=16777214) False sensor.boiler_dhw_starts sensor.boiler_dhw_starts 5 9 1 65 2
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.workm active time time (>=0<=16777214) minutes False sensor.boiler_dhw_active_time sensor.boiler_dhw_workm 5 9 1 67 2
BK13/BK15, Smartline, GB1*2 boiler 64 nompower nominal Power uint8 (>=0<=254) kW True number.boiler_nominal_Power number.boiler_nompower 5 0 1 270 1
BK13/BK15, Smartline, GB1*2 boiler 64 nrgtotal total energy uint24 (>=0<=167772) kWh False sensor.boiler_total_energy sensor.boiler_nrgtotal 5 0 1/100 83 2
BK13/BK15, Smartline, GB1*2 boiler 64 nrgheat energy heating uint24 (>=0<=10000000) kWh True number.boiler_energy_heating number.boiler_nrgheat 5 0 1/100 85 2
BK13/BK15, Smartline, GB1*2 boiler 64 dhw.nrg energy uint24 (>=0<=10000000) kWh True number.boiler_dhw_energy number.boiler_dhw_nrg 5 9 1/100 0 2
Logano GB1*5, Logamatic MC10 boiler 72 reset reset cmd [-|maintenance|error|history|message] True sensor.boiler_reset sensor.boiler_reset 5 0 1 0 1
Logano GB1*5, Logamatic MC10 boiler 72 heatingoff force heating off boolean True switch.boiler_force_heating_off switch.boiler_heatingoff 5 0 1 1 1
Logano GB1*5, Logamatic MC10 boiler 72 heatingactive heating active boolean False binary_sensor.boiler_heating_active binary_sensor.boiler_heatingactive 5 0 1 2 1
Logano GB1*5, Logamatic MC10 boiler 72 tapwateractive tapwater active boolean False binary_sensor.boiler_tapwater_active binary_sensor.boiler_tapwateractive 5 0 1 3 1
Logano GB1*5, Logamatic MC10 boiler 72 selflowtemp selected flow temperature uint8 (>=0<=90) C True number.boiler_selected_flow_temperature number.boiler_selflowtemp 5 0 1 4 1
Logano GB1*5, Logamatic MC10 boiler 72 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.boiler_heating_pump_modulation sensor.boiler_heatingpumpmod 5 0 1 5 1
Logano GB1*5, Logamatic MC10 boiler 72 outdoortemp outside temperature int16 (>=-3199<=3199) C False sensor.boiler_outside_temperature sensor.boiler_outdoortemp 5 0 1/10 6 1
Logano GB1*5, Logamatic MC10 boiler 72 curflowtemp current flow temperature uint16 (>=0<=3199) C False sensor.boiler_current_flow_temperature sensor.boiler_curflowtemp 5 0 1/10 7 1
Logano GB1*5, Logamatic MC10 boiler 72 rettemp return temperature uint16 (>=0<=3199) C False sensor.boiler_return_temperature sensor.boiler_rettemp 5 0 1/10 8 1
Logano GB1*5, Logamatic MC10 boiler 72 switchtemp mixing switch temperature uint16 (>=0<=3199) C False sensor.boiler_mixing_switch_temperature sensor.boiler_switchtemp 5 0 1/10 9 1
Logano GB1*5, Logamatic MC10 boiler 72 syspress system pressure uint8 (>=0<=25) bar False sensor.boiler_system_pressure sensor.boiler_syspress 5 0 1/10 10 1
Logano GB1*5, Logamatic MC10 boiler 72 boiltemp actual boiler temperature uint16 (>=0<=3199) C False sensor.boiler_actual_boiler_temperature sensor.boiler_boiltemp 5 0 1/10 11 1
Logano GB1*5, Logamatic MC10 boiler 72 headertemp low loss header uint16 (>=0<=3199) C False sensor.boiler_low_loss_header sensor.boiler_headertemp 5 0 1/10 12 1
Logano GB1*5, Logamatic MC10 boiler 72 exhausttemp exhaust temperature uint16 (>=0<=3199) C False sensor.boiler_exhaust_temperature sensor.boiler_exhausttemp 5 0 1/10 244 1
Logano GB1*5, Logamatic MC10 boiler 72 burngas gas boolean False binary_sensor.boiler_gas binary_sensor.boiler_burngas 5 0 1 245 1
Logano GB1*5, Logamatic MC10 boiler 72 burngas2 gas stage 2 boolean False binary_sensor.boiler_gas_stage_2 binary_sensor.boiler_burngas2 5 0 1 246 1
Logano GB1*5, Logamatic MC10 boiler 72 flamecurr flame current uint16 (>=0<=3199) µA False sensor.boiler_flame_current sensor.boiler_flamecurr 5 0 1/10 247 1
Logano GB1*5, Logamatic MC10 boiler 72 fanwork fan boolean False binary_sensor.boiler_fan binary_sensor.boiler_fanwork 5 0 1 248 1
Logano GB1*5, Logamatic MC10 boiler 72 ignwork ignition boolean False binary_sensor.boiler_ignition binary_sensor.boiler_ignwork 5 0 1 249 1
Logano GB1*5, Logamatic MC10 boiler 72 oilpreheat oil preheating boolean False binary_sensor.boiler_oil_preheating binary_sensor.boiler_oilpreheat 5 0 1 250 1
Logano GB1*5, Logamatic MC10 boiler 72 burnminpower burner min power uint8 (>=0<=100) % True number.boiler_burner_min_power number.boiler_burnminpower 5 0 1 251 1
Logano GB1*5, Logamatic MC10 boiler 72 burnmaxpower burner max power uint8 (>=0<=254) % True number.boiler_burner_max_power number.boiler_burnmaxpower 5 0 1 252 1
Logano GB1*5, Logamatic MC10 boiler 72 burnminperiod burner min period uint8 (>=0<=120) minutes True number.boiler_burner_min_period number.boiler_burnminperiod 5 0 1 253 1
Logano GB1*5, Logamatic MC10 boiler 72 absburnpow burner current power (absolute) uint8 (>=0<=100) % False sensor.boiler_burner_current_power_(absolute) sensor.boiler_absburnpow 5 0 1 254 1
Logano GB1*5, Logamatic MC10 boiler 72 heatblock heating block uint16 (>=0<=3199) C False sensor.boiler_heating_block sensor.boiler_heatblock 5 0 1/10 255 1
Logano GB1*5, Logamatic MC10 boiler 72 boilhyston hysteresis on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_on_temperature number.boiler_boilhyston 5 0 1 256 1
Logano GB1*5, Logamatic MC10 boiler 72 boilhystoff hysteresis off temperature int8 (>=0<=20) C True number.boiler_hysteresis_off_temperature number.boiler_boilhystoff 5 0 1 257 1
Logano GB1*5, Logamatic MC10 boiler 72 boil2hyston hysteresis stage 2 on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_stage_2_on_temperature number.boiler_boil2hyston 5 0 1 258 1
Logano GB1*5, Logamatic MC10 boiler 72 boil2hystoff hysteresis stage 2 off temperature int8 (>=0<=20) C True number.boiler_hysteresis_stage_2_off_temperature number.boiler_boil2hystoff 5 0 1 259 1
Logano GB1*5, Logamatic MC10 boiler 72 curveon heatingcurve on boolean True switch.boiler_heatingcurve_on switch.boiler_curveon 5 0 1 260 1
Logano GB1*5, Logamatic MC10 boiler 72 curvebase heatingcurve base uint8 (>=20<=90) C True number.boiler_heatingcurve_base number.boiler_curvebase 5 0 1 261 1
Logano GB1*5, Logamatic MC10 boiler 72 curveend heatingcurve end uint8 (>=20<=90) C True number.boiler_heatingcurve_end number.boiler_curveend 5 0 1 262 1
Logano GB1*5, Logamatic MC10 boiler 72 summertemp summer temperature uint8 (>=0<=45) C True number.boiler_summer_temperature number.boiler_summertemp 5 0 1 263 1
Logano GB1*5, Logamatic MC10 boiler 72 nofrostmode nofrost mode boolean True switch.boiler_nofrost_mode switch.boiler_nofrostmode 5 0 1 264 1
Logano GB1*5, Logamatic MC10 boiler 72 nofrosttemp nofrost temperature uint8 (>=0<=10) C True number.boiler_nofrost_temperature number.boiler_nofrosttemp 5 0 1 265 1
Logano GB1*5, Logamatic MC10 boiler 72 heatingactivated heating activated boolean True switch.boiler_heating_activated switch.boiler_heatingactivated 5 0 1 13 1
Logano GB1*5, Logamatic MC10 boiler 72 heatingtemp heating temperature uint8 (>=0<=90) C True number.boiler_heating_temperature number.boiler_heatingtemp 5 0 1 14 1
Logano GB1*5, Logamatic MC10 boiler 72 heatingpump heating pump boolean False binary_sensor.boiler_heating_pump binary_sensor.boiler_heatingpump 5 0 1 15 1
Logano GB1*5, Logamatic MC10 boiler 72 pumpmodmax boiler pump max power uint8 (>=0<=100) % True number.boiler_boiler_pump_max_power number.boiler_pumpmodmax 5 0 1 16 1
Logano GB1*5, Logamatic MC10 boiler 72 pumpmodmin boiler pump min power uint8 (>=0<=100) % True number.boiler_boiler_pump_min_power number.boiler_pumpmodmin 5 0 1 17 1
Logano GB1*5, Logamatic MC10 boiler 72 pumpmode boiler pump mode enum [proportional|deltaP-1|deltaP-2|deltaP-3|deltaP-4] True select.boiler_boiler_pump_mode select.boiler_pumpmode 5 0 1 18 1
Logano GB1*5, Logamatic MC10 boiler 72 pumpcharacter boiler pump characteristic enum [proportional|150mbar|200mbar|250mbar|300mbar|350mbar|400mbar] True select.boiler_boiler_pump_characteristic select.boiler_pumpcharacter 5 0 1 19 1
Logano GB1*5, Logamatic MC10 boiler 72 pumpdelay pump delay uint8 (>=0<=60) minutes True number.boiler_pump_delay number.boiler_pumpdelay 5 0 1 20 1
Logano GB1*5, Logamatic MC10 boiler 72 pumpontemp pump logic temperature uint8 (>=0<=60) C True number.boiler_pump_logic_temperature number.boiler_pumpontemp 5 0 1 21 1
Logano GB1*5, Logamatic MC10 boiler 72 selburnpow burner selected max power uint8 (>=0<=254) % True number.boiler_burner_selected_max_power number.boiler_selburnpow 5 0 1 22 1
Logano GB1*5, Logamatic MC10 boiler 72 curburnpow burner current power uint8 (>=0<=100) % False sensor.boiler_burner_current_power sensor.boiler_curburnpow 5 0 1 23 1
Logano GB1*5, Logamatic MC10 boiler 72 burnstarts burner starts uint24 (>=0<=16777214) False sensor.boiler_burner_starts sensor.boiler_burnstarts 5 0 1 24 2
Logano GB1*5, Logamatic MC10 boiler 72 burnworkmin total burner operating time time (>=0<=16777214) minutes False sensor.boiler_total_burner_operating_time sensor.boiler_burnworkmin 5 0 1 26 2
Logano GB1*5, Logamatic MC10 boiler 72 burn2workmin burner stage 2 operating time time (>=0<=16777214) minutes False sensor.boiler_burner_stage_2_operating_time sensor.boiler_burn2workmin 5 0 1 28 2
Logano GB1*5, Logamatic MC10 boiler 72 heatworkmin total heat operating time time (>=0<=16777214) minutes False sensor.boiler_total_heat_operating_time sensor.boiler_heatworkmin 5 0 1 30 2
Logano GB1*5, Logamatic MC10 boiler 72 heatstarts burner starts heating uint24 (>=0<=16777214) False sensor.boiler_burner_starts_heating sensor.boiler_heatstarts 5 0 1 32 2
Logano GB1*5, Logamatic MC10 boiler 72 ubauptime total UBA operating time time (>=0<=16777214) minutes False sensor.boiler_total_UBA_operating_time sensor.boiler_ubauptime 5 0 1 34 2
Logano GB1*5, Logamatic MC10 boiler 72 lastcode last error code string False sensor.boiler_last_error_code sensor.boiler_lastcode 5 0 1 36 28
Logano GB1*5, Logamatic MC10 boiler 72 servicecode service code string False sensor.boiler_service_code sensor.boiler_servicecode 5 0 1 64 2
Logano GB1*5, Logamatic MC10 boiler 72 servicecodenumber service code number uint16 (>=0<=31999) False sensor.boiler_service_code_number sensor.boiler_servicecodenumber 5 0 1 66 1
Logano GB1*5, Logamatic MC10 boiler 72 maintenancemessage maintenance message string False sensor.boiler_maintenance_message sensor.boiler_maintenancemessage 5 0 1 67 2
Logano GB1*5, Logamatic MC10 boiler 72 maintenance maintenance scheduled enum [off|time|date|manual] True select.boiler_maintenance_scheduled select.boiler_maintenance 5 0 1 69 1
Logano GB1*5, Logamatic MC10 boiler 72 maintenancetime time to next maintenance uint16 (>=0<=31999) hours True number.boiler_time_to_next_maintenance number.boiler_maintenancetime 5 0 1 70 1
Logano GB1*5, Logamatic MC10 boiler 72 maintenancedate next maintenance date string True sensor.boiler_next_maintenance_date sensor.boiler_maintenancedate 5 0 1 71 6
Logano GB1*5, Logamatic MC10 boiler 72 emergencyops emergency operation boolean True switch.boiler_emergency_operation switch.boiler_emergencyops 5 0 1 77 1
Logano GB1*5, Logamatic MC10 boiler 72 emergencytemp emergency temperature uint8 (>=15<=70) C True number.boiler_emergency_temperature number.boiler_emergencytemp 5 0 1 78 1
Logano GB1*5, Logamatic MC10 boiler 72 pc0flow Flow PC0 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC0 sensor.boiler_pc0flow 5 0 1 79 1
Logano GB1*5, Logamatic MC10 boiler 72 pc1flow Flow PC1 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC1 sensor.boiler_pc1flow 5 0 1 80 1
Logano GB1*5, Logamatic MC10 boiler 72 pc1on PC1 boolean False binary_sensor.boiler_PC1 binary_sensor.boiler_pc1on 5 0 1 81 1
Logano GB1*5, Logamatic MC10 boiler 72 pc1rate PC1 rate uint8 (>=0<=100) % False sensor.boiler_PC1_rate sensor.boiler_pc1rate 5 0 1 82 1
Logano GB1*5, Logamatic MC10 boiler 72 meterheat meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_meter_heating sensor.boiler_meterheat 5 0 1/10 95 2
Logano GB1*5, Logamatic MC10 boiler 72 dhw.meter meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_meter sensor.boiler_dhw_meter 5 9 1/10 2 2
Logano GB1*5, Logamatic MC10 boiler 72 gasmeterheat gas meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_gas_meter_heating sensor.boiler_gasmeterheat 5 0 1/10 266 2
Logano GB1*5, Logamatic MC10 boiler 72 dhw.gasmeter gas meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_gas_meter sensor.boiler_dhw_gasmeter 5 9 1/10 69 2
Logano GB1*5, Logamatic MC10 boiler 72 nrgheat2 energy heating 2 uint24 (>=0<=1677721) kWh False sensor.boiler_energy_heating_2 sensor.boiler_nrgheat2 5 0 1/10 268 2
Logano GB1*5, Logamatic MC10 boiler 72 dhw.nrg2 energy 2 uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_energy_2 sensor.boiler_dhw_nrg2 5 9 1/10 71 2
Logano GB1*5, Logamatic MC10 boiler 72 dhw.tapactivated turn on/off boolean True switch.boiler_dhw_turn_on/off switch.boiler_dhw_tapactivated 5 9 1 28 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.settemp set temperature uint8 (>=0<=254) C False sensor.boiler_dhw_set_temperature sensor.boiler_dhw_settemp 5 9 1 29 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_temperature number.boiler_dhw_seltemp 5 9 1 30 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.seltemplow selected lower temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_lower_temperature number.boiler_dhw_seltemplow 5 9 1 31 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.tempecoplus selected eco+ temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_eco+_temperature number.boiler_dhw_tempecoplus 5 9 1 32 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.seltempoff selected temperature for off uint8 (>=0<=254) C False sensor.boiler_dhw_selected_temperature_for_off sensor.boiler_dhw_seltempoff 5 9 1 33 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.seltempsingle single charge temperature uint8 (>=0<=254) C True number.boiler_dhw_single_charge_temperature number.boiler_dhw_seltempsingle 5 9 1 34 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.solartemp solar boiler temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_solar_boiler_temperature sensor.boiler_dhw_solartemp 5 9 1/10 35 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.type type enum [off|flow|buffered flow|buffer|layered buffer] False sensor.boiler_dhw_type sensor.boiler_dhw_type 5 9 1 36 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.comfort comfort enum [hot|eco|intelligent] True select.boiler_dhw_comfort select.boiler_dhw_comfort 5 9 1 37 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.comfort1 comfort mode enum [high comfort|eco] True select.boiler_dhw_comfort_mode select.boiler_dhw_comfort1 5 9 1 38 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.flowtempoffset flow temperature offset uint8 (>=0<=100) C True number.boiler_dhw_flow_temperature_offset number.boiler_dhw_flowtempoffset 5 9 1 39 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.chargeoptimization charge optimization boolean True switch.boiler_dhw_charge_optimization switch.boiler_dhw_chargeoptimization 5 9 1 40 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.maxpower max power uint8 (>=0<=254) % True number.boiler_dhw_max_power number.boiler_dhw_maxpower 5 9 1 41 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.maxtemp maximum temperature uint8 (>=0<=80) C True number.boiler_dhw_maximum_temperature number.boiler_dhw_maxtemp 5 9 1 42 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.circpump circulation pump available boolean True switch.boiler_dhw_circulation_pump_available switch.boiler_dhw_circpump 5 9 1 43 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.chargetype charging type enum [chargepump|3-way valve] False sensor.boiler_dhw_charging_type sensor.boiler_dhw_chargetype 5 9 1 44 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_on_temperature number.boiler_dhw_hyston 5 9 1 45 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_off_temperature number.boiler_dhw_hystoff 5 9 1 46 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.disinfectiontemp disinfection temperature uint8 (>=60<=80) C True number.boiler_dhw_disinfection_temperature number.boiler_dhw_disinfectiontemp 5 9 1 47 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.boiler_dhw_circulation_pump_mode select.boiler_dhw_circmode 5 9 1 48 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.circ circulation active boolean True switch.boiler_dhw_circulation_active switch.boiler_dhw_circ 5 9 1 49 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.curtemp current intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_intern_temperature sensor.boiler_dhw_curtemp 5 9 1/10 50 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_extern_temperature sensor.boiler_dhw_curtemp2 5 9 1/10 51 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.curflow current tap water flow uint8 (>=0<=25) l/min False sensor.boiler_dhw_current_tap_water_flow sensor.boiler_dhw_curflow 5 9 1/10 52 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_intern_temperature sensor.boiler_dhw_storagetemp1 5 9 1/10 53 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.storagetemp2 storage extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_extern_temperature sensor.boiler_dhw_storagetemp2 5 9 1/10 54 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.activated activated boolean True switch.boiler_dhw_activated switch.boiler_dhw_activated 5 9 1 55 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.onetime one time charging boolean True switch.boiler_dhw_one_time_charging switch.boiler_dhw_onetime 5 9 1 56 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.disinfecting disinfecting boolean True switch.boiler_dhw_disinfecting switch.boiler_dhw_disinfecting 5 9 1 57 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.charging charging boolean False binary_sensor.boiler_dhw_charging binary_sensor.boiler_dhw_charging 5 9 1 58 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.recharging recharging boolean False binary_sensor.boiler_dhw_recharging binary_sensor.boiler_dhw_recharging 5 9 1 59 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.tempok temperature ok boolean False binary_sensor.boiler_dhw_temperature_ok binary_sensor.boiler_dhw_tempok 5 9 1 60 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.active active boolean False binary_sensor.boiler_dhw_active binary_sensor.boiler_dhw_active 5 9 1 61 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.3wayvalve 3-way valve active boolean False binary_sensor.boiler_dhw_3-way_valve_active binary_sensor.boiler_dhw_3wayvalve 5 9 1 62 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.mixertemp mixer temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_mixer_temperature sensor.boiler_dhw_mixertemp 5 9 1/10 63 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.cylmiddletemp cylinder middle temperature (TS3) uint16 (>=0<=3199) C False sensor.boiler_dhw_cylinder_middle_temperature_(TS3) sensor.boiler_dhw_cylmiddletemp 5 9 1/10 64 1
Logano GB1*5, Logamatic MC10 boiler 72 dhw.starts starts uint24 (>=0<=16777214) False sensor.boiler_dhw_starts sensor.boiler_dhw_starts 5 9 1 65 2
Logano GB1*5, Logamatic MC10 boiler 72 dhw.workm active time time (>=0<=16777214) minutes False sensor.boiler_dhw_active_time sensor.boiler_dhw_workm 5 9 1 67 2
Logano GB1*5, Logamatic MC10 boiler 72 nompower nominal Power uint8 (>=0<=254) kW True number.boiler_nominal_Power number.boiler_nompower 5 0 1 270 1
Logano GB1*5, Logamatic MC10 boiler 72 nrgtotal total energy uint24 (>=0<=167772) kWh False sensor.boiler_total_energy sensor.boiler_nrgtotal 5 0 1/100 83 2
Logano GB1*5, Logamatic MC10 boiler 72 nrgheat energy heating uint24 (>=0<=10000000) kWh True number.boiler_energy_heating number.boiler_nrgheat 5 0 1/100 85 2
Logano GB1*5, Logamatic MC10 boiler 72 dhw.nrg energy uint24 (>=0<=10000000) kWh True number.boiler_dhw_energy number.boiler_dhw_nrg 5 9 1/100 0 2
Cascade CM10 boiler 81 reset reset cmd [-|maintenance|error|history|message] True sensor.boiler_reset sensor.boiler_reset 5 0 1 0 1
Cascade CM10 boiler 81 heatingoff force heating off boolean True switch.boiler_force_heating_off switch.boiler_heatingoff 5 0 1 1 1
Cascade CM10 boiler 81 heatingactive heating active boolean False binary_sensor.boiler_heating_active binary_sensor.boiler_heatingactive 5 0 1 2 1
Cascade CM10 boiler 81 tapwateractive tapwater active boolean False binary_sensor.boiler_tapwater_active binary_sensor.boiler_tapwateractive 5 0 1 3 1
Cascade CM10 boiler 81 selflowtemp selected flow temperature uint8 (>=0<=90) C True number.boiler_selected_flow_temperature number.boiler_selflowtemp 5 0 1 4 1
Cascade CM10 boiler 81 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.boiler_heating_pump_modulation sensor.boiler_heatingpumpmod 5 0 1 5 1
Cascade CM10 boiler 81 outdoortemp outside temperature int16 (>=-3199<=3199) C False sensor.boiler_outside_temperature sensor.boiler_outdoortemp 5 0 1/10 6 1
Cascade CM10 boiler 81 curflowtemp current flow temperature uint16 (>=0<=3199) C False sensor.boiler_current_flow_temperature sensor.boiler_curflowtemp 5 0 1/10 7 1
Cascade CM10 boiler 81 rettemp return temperature uint16 (>=0<=3199) C False sensor.boiler_return_temperature sensor.boiler_rettemp 5 0 1/10 8 1
Cascade CM10 boiler 81 switchtemp mixing switch temperature uint16 (>=0<=3199) C False sensor.boiler_mixing_switch_temperature sensor.boiler_switchtemp 5 0 1/10 9 1
Cascade CM10 boiler 81 syspress system pressure uint8 (>=0<=25) bar False sensor.boiler_system_pressure sensor.boiler_syspress 5 0 1/10 10 1
Cascade CM10 boiler 81 boiltemp actual boiler temperature uint16 (>=0<=3199) C False sensor.boiler_actual_boiler_temperature sensor.boiler_boiltemp 5 0 1/10 11 1
Cascade CM10 boiler 81 headertemp low loss header uint16 (>=0<=3199) C False sensor.boiler_low_loss_header sensor.boiler_headertemp 5 0 1/10 12 1
Cascade CM10 boiler 81 exhausttemp exhaust temperature uint16 (>=0<=3199) C False sensor.boiler_exhaust_temperature sensor.boiler_exhausttemp 5 0 1/10 244 1
Cascade CM10 boiler 81 burngas gas boolean False binary_sensor.boiler_gas binary_sensor.boiler_burngas 5 0 1 245 1
Cascade CM10 boiler 81 burngas2 gas stage 2 boolean False binary_sensor.boiler_gas_stage_2 binary_sensor.boiler_burngas2 5 0 1 246 1
Cascade CM10 boiler 81 flamecurr flame current uint16 (>=0<=3199) µA False sensor.boiler_flame_current sensor.boiler_flamecurr 5 0 1/10 247 1
Cascade CM10 boiler 81 fanwork fan boolean False binary_sensor.boiler_fan binary_sensor.boiler_fanwork 5 0 1 248 1
Cascade CM10 boiler 81 ignwork ignition boolean False binary_sensor.boiler_ignition binary_sensor.boiler_ignwork 5 0 1 249 1
Cascade CM10 boiler 81 oilpreheat oil preheating boolean False binary_sensor.boiler_oil_preheating binary_sensor.boiler_oilpreheat 5 0 1 250 1
Cascade CM10 boiler 81 burnminpower burner min power uint8 (>=0<=100) % True number.boiler_burner_min_power number.boiler_burnminpower 5 0 1 251 1
Cascade CM10 boiler 81 burnmaxpower burner max power uint8 (>=0<=254) % True number.boiler_burner_max_power number.boiler_burnmaxpower 5 0 1 252 1
Cascade CM10 boiler 81 burnminperiod burner min period uint8 (>=0<=120) minutes True number.boiler_burner_min_period number.boiler_burnminperiod 5 0 1 253 1
Cascade CM10 boiler 81 absburnpow burner current power (absolute) uint8 (>=0<=100) % False sensor.boiler_burner_current_power_(absolute) sensor.boiler_absburnpow 5 0 1 254 1
Cascade CM10 boiler 81 heatblock heating block uint16 (>=0<=3199) C False sensor.boiler_heating_block sensor.boiler_heatblock 5 0 1/10 255 1
Cascade CM10 boiler 81 boilhyston hysteresis on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_on_temperature number.boiler_boilhyston 5 0 1 256 1
Cascade CM10 boiler 81 boilhystoff hysteresis off temperature int8 (>=0<=20) C True number.boiler_hysteresis_off_temperature number.boiler_boilhystoff 5 0 1 257 1
Cascade CM10 boiler 81 boil2hyston hysteresis stage 2 on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_stage_2_on_temperature number.boiler_boil2hyston 5 0 1 258 1
Cascade CM10 boiler 81 boil2hystoff hysteresis stage 2 off temperature int8 (>=0<=20) C True number.boiler_hysteresis_stage_2_off_temperature number.boiler_boil2hystoff 5 0 1 259 1
Cascade CM10 boiler 81 curveon heatingcurve on boolean True switch.boiler_heatingcurve_on switch.boiler_curveon 5 0 1 260 1
Cascade CM10 boiler 81 curvebase heatingcurve base uint8 (>=20<=90) C True number.boiler_heatingcurve_base number.boiler_curvebase 5 0 1 261 1
Cascade CM10 boiler 81 curveend heatingcurve end uint8 (>=20<=90) C True number.boiler_heatingcurve_end number.boiler_curveend 5 0 1 262 1
Cascade CM10 boiler 81 summertemp summer temperature uint8 (>=0<=45) C True number.boiler_summer_temperature number.boiler_summertemp 5 0 1 263 1
Cascade CM10 boiler 81 nofrostmode nofrost mode boolean True switch.boiler_nofrost_mode switch.boiler_nofrostmode 5 0 1 264 1
Cascade CM10 boiler 81 nofrosttemp nofrost temperature uint8 (>=0<=10) C True number.boiler_nofrost_temperature number.boiler_nofrosttemp 5 0 1 265 1
Cascade CM10 boiler 81 heatingactivated heating activated boolean True switch.boiler_heating_activated switch.boiler_heatingactivated 5 0 1 13 1
Cascade CM10 boiler 81 heatingtemp heating temperature uint8 (>=0<=90) C True number.boiler_heating_temperature number.boiler_heatingtemp 5 0 1 14 1
Cascade CM10 boiler 81 heatingpump heating pump boolean False binary_sensor.boiler_heating_pump binary_sensor.boiler_heatingpump 5 0 1 15 1
Cascade CM10 boiler 81 pumpmodmax boiler pump max power uint8 (>=0<=100) % True number.boiler_boiler_pump_max_power number.boiler_pumpmodmax 5 0 1 16 1
Cascade CM10 boiler 81 pumpmodmin boiler pump min power uint8 (>=0<=100) % True number.boiler_boiler_pump_min_power number.boiler_pumpmodmin 5 0 1 17 1
Cascade CM10 boiler 81 pumpmode boiler pump mode enum [proportional|deltaP-1|deltaP-2|deltaP-3|deltaP-4] True select.boiler_boiler_pump_mode select.boiler_pumpmode 5 0 1 18 1
Cascade CM10 boiler 81 pumpcharacter boiler pump characteristic enum [proportional|150mbar|200mbar|250mbar|300mbar|350mbar|400mbar] True select.boiler_boiler_pump_characteristic select.boiler_pumpcharacter 5 0 1 19 1
Cascade CM10 boiler 81 pumpdelay pump delay uint8 (>=0<=60) minutes True number.boiler_pump_delay number.boiler_pumpdelay 5 0 1 20 1
Cascade CM10 boiler 81 pumpontemp pump logic temperature uint8 (>=0<=60) C True number.boiler_pump_logic_temperature number.boiler_pumpontemp 5 0 1 21 1
Cascade CM10 boiler 81 selburnpow burner selected max power uint8 (>=0<=254) % True number.boiler_burner_selected_max_power number.boiler_selburnpow 5 0 1 22 1
Cascade CM10 boiler 81 curburnpow burner current power uint8 (>=0<=100) % False sensor.boiler_burner_current_power sensor.boiler_curburnpow 5 0 1 23 1
Cascade CM10 boiler 81 burnstarts burner starts uint24 (>=0<=16777214) False sensor.boiler_burner_starts sensor.boiler_burnstarts 5 0 1 24 2
Cascade CM10 boiler 81 burnworkmin total burner operating time time (>=0<=16777214) minutes False sensor.boiler_total_burner_operating_time sensor.boiler_burnworkmin 5 0 1 26 2
Cascade CM10 boiler 81 burn2workmin burner stage 2 operating time time (>=0<=16777214) minutes False sensor.boiler_burner_stage_2_operating_time sensor.boiler_burn2workmin 5 0 1 28 2
Cascade CM10 boiler 81 heatworkmin total heat operating time time (>=0<=16777214) minutes False sensor.boiler_total_heat_operating_time sensor.boiler_heatworkmin 5 0 1 30 2
Cascade CM10 boiler 81 heatstarts burner starts heating uint24 (>=0<=16777214) False sensor.boiler_burner_starts_heating sensor.boiler_heatstarts 5 0 1 32 2
Cascade CM10 boiler 81 ubauptime total UBA operating time time (>=0<=16777214) minutes False sensor.boiler_total_UBA_operating_time sensor.boiler_ubauptime 5 0 1 34 2
Cascade CM10 boiler 81 lastcode last error code string False sensor.boiler_last_error_code sensor.boiler_lastcode 5 0 1 36 28
Cascade CM10 boiler 81 servicecode service code string False sensor.boiler_service_code sensor.boiler_servicecode 5 0 1 64 2
Cascade CM10 boiler 81 servicecodenumber service code number uint16 (>=0<=31999) False sensor.boiler_service_code_number sensor.boiler_servicecodenumber 5 0 1 66 1
Cascade CM10 boiler 81 maintenancemessage maintenance message string False sensor.boiler_maintenance_message sensor.boiler_maintenancemessage 5 0 1 67 2
Cascade CM10 boiler 81 maintenance maintenance scheduled enum [off|time|date|manual] True select.boiler_maintenance_scheduled select.boiler_maintenance 5 0 1 69 1
Cascade CM10 boiler 81 maintenancetime time to next maintenance uint16 (>=0<=31999) hours True number.boiler_time_to_next_maintenance number.boiler_maintenancetime 5 0 1 70 1
Cascade CM10 boiler 81 maintenancedate next maintenance date string True sensor.boiler_next_maintenance_date sensor.boiler_maintenancedate 5 0 1 71 6
Cascade CM10 boiler 81 emergencyops emergency operation boolean True switch.boiler_emergency_operation switch.boiler_emergencyops 5 0 1 77 1
Cascade CM10 boiler 81 emergencytemp emergency temperature uint8 (>=15<=70) C True number.boiler_emergency_temperature number.boiler_emergencytemp 5 0 1 78 1
Cascade CM10 boiler 81 pc0flow Flow PC0 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC0 sensor.boiler_pc0flow 5 0 1 79 1
Cascade CM10 boiler 81 pc1flow Flow PC1 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC1 sensor.boiler_pc1flow 5 0 1 80 1
Cascade CM10 boiler 81 pc1on PC1 boolean False binary_sensor.boiler_PC1 binary_sensor.boiler_pc1on 5 0 1 81 1
Cascade CM10 boiler 81 pc1rate PC1 rate uint8 (>=0<=100) % False sensor.boiler_PC1_rate sensor.boiler_pc1rate 5 0 1 82 1
Cascade CM10 boiler 81 meterheat meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_meter_heating sensor.boiler_meterheat 5 0 1/10 95 2
Cascade CM10 boiler 81 dhw.meter meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_meter sensor.boiler_dhw_meter 5 9 1/10 2 2
Cascade CM10 boiler 81 gasmeterheat gas meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_gas_meter_heating sensor.boiler_gasmeterheat 5 0 1/10 266 2
Cascade CM10 boiler 81 dhw.gasmeter gas meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_gas_meter sensor.boiler_dhw_gasmeter 5 9 1/10 69 2
Cascade CM10 boiler 81 nrgheat2 energy heating 2 uint24 (>=0<=1677721) kWh False sensor.boiler_energy_heating_2 sensor.boiler_nrgheat2 5 0 1/10 268 2
Cascade CM10 boiler 81 dhw.nrg2 energy 2 uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_energy_2 sensor.boiler_dhw_nrg2 5 9 1/10 71 2
Cascade CM10 boiler 81 dhw.tapactivated turn on/off boolean True switch.boiler_dhw_turn_on/off switch.boiler_dhw_tapactivated 5 9 1 28 1
Cascade CM10 boiler 81 dhw.settemp set temperature uint8 (>=0<=254) C False sensor.boiler_dhw_set_temperature sensor.boiler_dhw_settemp 5 9 1 29 1
Cascade CM10 boiler 81 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_temperature number.boiler_dhw_seltemp 5 9 1 30 1
Cascade CM10 boiler 81 dhw.seltemplow selected lower temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_lower_temperature number.boiler_dhw_seltemplow 5 9 1 31 1
Cascade CM10 boiler 81 dhw.tempecoplus selected eco+ temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_eco+_temperature number.boiler_dhw_tempecoplus 5 9 1 32 1
Cascade CM10 boiler 81 dhw.seltempoff selected temperature for off uint8 (>=0<=254) C False sensor.boiler_dhw_selected_temperature_for_off sensor.boiler_dhw_seltempoff 5 9 1 33 1
Cascade CM10 boiler 81 dhw.seltempsingle single charge temperature uint8 (>=0<=254) C True number.boiler_dhw_single_charge_temperature number.boiler_dhw_seltempsingle 5 9 1 34 1
Cascade CM10 boiler 81 dhw.solartemp solar boiler temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_solar_boiler_temperature sensor.boiler_dhw_solartemp 5 9 1/10 35 1
Cascade CM10 boiler 81 dhw.type type enum [off|flow|buffered flow|buffer|layered buffer] False sensor.boiler_dhw_type sensor.boiler_dhw_type 5 9 1 36 1
Cascade CM10 boiler 81 dhw.comfort comfort enum [hot|eco|intelligent] True select.boiler_dhw_comfort select.boiler_dhw_comfort 5 9 1 37 1
Cascade CM10 boiler 81 dhw.comfort1 comfort mode enum [high comfort|eco] True select.boiler_dhw_comfort_mode select.boiler_dhw_comfort1 5 9 1 38 1
Cascade CM10 boiler 81 dhw.flowtempoffset flow temperature offset uint8 (>=0<=100) C True number.boiler_dhw_flow_temperature_offset number.boiler_dhw_flowtempoffset 5 9 1 39 1
Cascade CM10 boiler 81 dhw.chargeoptimization charge optimization boolean True switch.boiler_dhw_charge_optimization switch.boiler_dhw_chargeoptimization 5 9 1 40 1
Cascade CM10 boiler 81 dhw.maxpower max power uint8 (>=0<=254) % True number.boiler_dhw_max_power number.boiler_dhw_maxpower 5 9 1 41 1
Cascade CM10 boiler 81 dhw.maxtemp maximum temperature uint8 (>=0<=80) C True number.boiler_dhw_maximum_temperature number.boiler_dhw_maxtemp 5 9 1 42 1
Cascade CM10 boiler 81 dhw.circpump circulation pump available boolean True switch.boiler_dhw_circulation_pump_available switch.boiler_dhw_circpump 5 9 1 43 1
Cascade CM10 boiler 81 dhw.chargetype charging type enum [chargepump|3-way valve] False sensor.boiler_dhw_charging_type sensor.boiler_dhw_chargetype 5 9 1 44 1
Cascade CM10 boiler 81 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_on_temperature number.boiler_dhw_hyston 5 9 1 45 1
Cascade CM10 boiler 81 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_off_temperature number.boiler_dhw_hystoff 5 9 1 46 1
Cascade CM10 boiler 81 dhw.disinfectiontemp disinfection temperature uint8 (>=60<=80) C True number.boiler_dhw_disinfection_temperature number.boiler_dhw_disinfectiontemp 5 9 1 47 1
Cascade CM10 boiler 81 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.boiler_dhw_circulation_pump_mode select.boiler_dhw_circmode 5 9 1 48 1
Cascade CM10 boiler 81 dhw.circ circulation active boolean True switch.boiler_dhw_circulation_active switch.boiler_dhw_circ 5 9 1 49 1
Cascade CM10 boiler 81 dhw.curtemp current intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_intern_temperature sensor.boiler_dhw_curtemp 5 9 1/10 50 1
Cascade CM10 boiler 81 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_extern_temperature sensor.boiler_dhw_curtemp2 5 9 1/10 51 1
Cascade CM10 boiler 81 dhw.curflow current tap water flow uint8 (>=0<=25) l/min False sensor.boiler_dhw_current_tap_water_flow sensor.boiler_dhw_curflow 5 9 1/10 52 1
Cascade CM10 boiler 81 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_intern_temperature sensor.boiler_dhw_storagetemp1 5 9 1/10 53 1
Cascade CM10 boiler 81 dhw.storagetemp2 storage extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_extern_temperature sensor.boiler_dhw_storagetemp2 5 9 1/10 54 1
Cascade CM10 boiler 81 dhw.activated activated boolean True switch.boiler_dhw_activated switch.boiler_dhw_activated 5 9 1 55 1
Cascade CM10 boiler 81 dhw.onetime one time charging boolean True switch.boiler_dhw_one_time_charging switch.boiler_dhw_onetime 5 9 1 56 1
Cascade CM10 boiler 81 dhw.disinfecting disinfecting boolean True switch.boiler_dhw_disinfecting switch.boiler_dhw_disinfecting 5 9 1 57 1
Cascade CM10 boiler 81 dhw.charging charging boolean False binary_sensor.boiler_dhw_charging binary_sensor.boiler_dhw_charging 5 9 1 58 1
Cascade CM10 boiler 81 dhw.recharging recharging boolean False binary_sensor.boiler_dhw_recharging binary_sensor.boiler_dhw_recharging 5 9 1 59 1
Cascade CM10 boiler 81 dhw.tempok temperature ok boolean False binary_sensor.boiler_dhw_temperature_ok binary_sensor.boiler_dhw_tempok 5 9 1 60 1
Cascade CM10 boiler 81 dhw.active active boolean False binary_sensor.boiler_dhw_active binary_sensor.boiler_dhw_active 5 9 1 61 1
Cascade CM10 boiler 81 dhw.3wayvalve 3-way valve active boolean False binary_sensor.boiler_dhw_3-way_valve_active binary_sensor.boiler_dhw_3wayvalve 5 9 1 62 1
Cascade CM10 boiler 81 dhw.mixertemp mixer temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_mixer_temperature sensor.boiler_dhw_mixertemp 5 9 1/10 63 1
Cascade CM10 boiler 81 dhw.cylmiddletemp cylinder middle temperature (TS3) uint16 (>=0<=3199) C False sensor.boiler_dhw_cylinder_middle_temperature_(TS3) sensor.boiler_dhw_cylmiddletemp 5 9 1/10 64 1
Cascade CM10 boiler 81 dhw.starts starts uint24 (>=0<=16777214) False sensor.boiler_dhw_starts sensor.boiler_dhw_starts 5 9 1 65 2
Cascade CM10 boiler 81 dhw.workm active time time (>=0<=16777214) minutes False sensor.boiler_dhw_active_time sensor.boiler_dhw_workm 5 9 1 67 2
Cascade CM10 boiler 81 nompower nominal Power uint8 (>=0<=254) kW True number.boiler_nominal_Power number.boiler_nompower 5 0 1 270 1
Cascade CM10 boiler 81 nrgtotal total energy uint24 (>=0<=167772) kWh False sensor.boiler_total_energy sensor.boiler_nrgtotal 5 0 1/100 83 2
Cascade CM10 boiler 81 nrgheat energy heating uint24 (>=0<=10000000) kWh True number.boiler_energy_heating number.boiler_nrgheat 5 0 1/100 85 2
Cascade CM10 boiler 81 dhw.nrg energy uint24 (>=0<=10000000) kWh True number.boiler_dhw_energy number.boiler_dhw_nrg 5 9 1/100 0 2
Logamax Plus GB022 boiler 84 reset reset cmd [-|maintenance|error|history|message] True sensor.boiler_reset sensor.boiler_reset 5 0 1 0 1
Logamax Plus GB022 boiler 84 heatingoff force heating off boolean True switch.boiler_force_heating_off switch.boiler_heatingoff 5 0 1 1 1
Logamax Plus GB022 boiler 84 heatingactive heating active boolean False binary_sensor.boiler_heating_active binary_sensor.boiler_heatingactive 5 0 1 2 1
Logamax Plus GB022 boiler 84 tapwateractive tapwater active boolean False binary_sensor.boiler_tapwater_active binary_sensor.boiler_tapwateractive 5 0 1 3 1
Logamax Plus GB022 boiler 84 selflowtemp selected flow temperature uint8 (>=0<=90) C True number.boiler_selected_flow_temperature number.boiler_selflowtemp 5 0 1 4 1
Logamax Plus GB022 boiler 84 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.boiler_heating_pump_modulation sensor.boiler_heatingpumpmod 5 0 1 5 1
Logamax Plus GB022 boiler 84 outdoortemp outside temperature int16 (>=-3199<=3199) C False sensor.boiler_outside_temperature sensor.boiler_outdoortemp 5 0 1/10 6 1
Logamax Plus GB022 boiler 84 curflowtemp current flow temperature uint16 (>=0<=3199) C False sensor.boiler_current_flow_temperature sensor.boiler_curflowtemp 5 0 1/10 7 1
Logamax Plus GB022 boiler 84 rettemp return temperature uint16 (>=0<=3199) C False sensor.boiler_return_temperature sensor.boiler_rettemp 5 0 1/10 8 1
Logamax Plus GB022 boiler 84 switchtemp mixing switch temperature uint16 (>=0<=3199) C False sensor.boiler_mixing_switch_temperature sensor.boiler_switchtemp 5 0 1/10 9 1
Logamax Plus GB022 boiler 84 syspress system pressure uint8 (>=0<=25) bar False sensor.boiler_system_pressure sensor.boiler_syspress 5 0 1/10 10 1
Logamax Plus GB022 boiler 84 boiltemp actual boiler temperature uint16 (>=0<=3199) C False sensor.boiler_actual_boiler_temperature sensor.boiler_boiltemp 5 0 1/10 11 1
Logamax Plus GB022 boiler 84 headertemp low loss header uint16 (>=0<=3199) C False sensor.boiler_low_loss_header sensor.boiler_headertemp 5 0 1/10 12 1
Logamax Plus GB022 boiler 84 exhausttemp exhaust temperature uint16 (>=0<=3199) C False sensor.boiler_exhaust_temperature sensor.boiler_exhausttemp 5 0 1/10 244 1
Logamax Plus GB022 boiler 84 burngas gas boolean False binary_sensor.boiler_gas binary_sensor.boiler_burngas 5 0 1 245 1
Logamax Plus GB022 boiler 84 burngas2 gas stage 2 boolean False binary_sensor.boiler_gas_stage_2 binary_sensor.boiler_burngas2 5 0 1 246 1
Logamax Plus GB022 boiler 84 flamecurr flame current uint16 (>=0<=3199) µA False sensor.boiler_flame_current sensor.boiler_flamecurr 5 0 1/10 247 1
Logamax Plus GB022 boiler 84 fanwork fan boolean False binary_sensor.boiler_fan binary_sensor.boiler_fanwork 5 0 1 248 1
Logamax Plus GB022 boiler 84 ignwork ignition boolean False binary_sensor.boiler_ignition binary_sensor.boiler_ignwork 5 0 1 249 1
Logamax Plus GB022 boiler 84 oilpreheat oil preheating boolean False binary_sensor.boiler_oil_preheating binary_sensor.boiler_oilpreheat 5 0 1 250 1
Logamax Plus GB022 boiler 84 burnminpower burner min power uint8 (>=0<=100) % True number.boiler_burner_min_power number.boiler_burnminpower 5 0 1 251 1
Logamax Plus GB022 boiler 84 burnmaxpower burner max power uint8 (>=0<=254) % True number.boiler_burner_max_power number.boiler_burnmaxpower 5 0 1 252 1
Logamax Plus GB022 boiler 84 burnminperiod burner min period uint8 (>=0<=120) minutes True number.boiler_burner_min_period number.boiler_burnminperiod 5 0 1 253 1
Logamax Plus GB022 boiler 84 absburnpow burner current power (absolute) uint8 (>=0<=100) % False sensor.boiler_burner_current_power_(absolute) sensor.boiler_absburnpow 5 0 1 254 1
Logamax Plus GB022 boiler 84 heatblock heating block uint16 (>=0<=3199) C False sensor.boiler_heating_block sensor.boiler_heatblock 5 0 1/10 255 1
Logamax Plus GB022 boiler 84 boilhyston hysteresis on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_on_temperature number.boiler_boilhyston 5 0 1 256 1
Logamax Plus GB022 boiler 84 boilhystoff hysteresis off temperature int8 (>=0<=20) C True number.boiler_hysteresis_off_temperature number.boiler_boilhystoff 5 0 1 257 1
Logamax Plus GB022 boiler 84 boil2hyston hysteresis stage 2 on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_stage_2_on_temperature number.boiler_boil2hyston 5 0 1 258 1
Logamax Plus GB022 boiler 84 boil2hystoff hysteresis stage 2 off temperature int8 (>=0<=20) C True number.boiler_hysteresis_stage_2_off_temperature number.boiler_boil2hystoff 5 0 1 259 1
Logamax Plus GB022 boiler 84 curveon heatingcurve on boolean True switch.boiler_heatingcurve_on switch.boiler_curveon 5 0 1 260 1
Logamax Plus GB022 boiler 84 curvebase heatingcurve base uint8 (>=20<=90) C True number.boiler_heatingcurve_base number.boiler_curvebase 5 0 1 261 1
Logamax Plus GB022 boiler 84 curveend heatingcurve end uint8 (>=20<=90) C True number.boiler_heatingcurve_end number.boiler_curveend 5 0 1 262 1
Logamax Plus GB022 boiler 84 summertemp summer temperature uint8 (>=0<=45) C True number.boiler_summer_temperature number.boiler_summertemp 5 0 1 263 1
Logamax Plus GB022 boiler 84 nofrostmode nofrost mode boolean True switch.boiler_nofrost_mode switch.boiler_nofrostmode 5 0 1 264 1
Logamax Plus GB022 boiler 84 nofrosttemp nofrost temperature uint8 (>=0<=10) C True number.boiler_nofrost_temperature number.boiler_nofrosttemp 5 0 1 265 1
Logamax Plus GB022 boiler 84 heatingactivated heating activated boolean True switch.boiler_heating_activated switch.boiler_heatingactivated 5 0 1 13 1
Logamax Plus GB022 boiler 84 heatingtemp heating temperature uint8 (>=0<=90) C True number.boiler_heating_temperature number.boiler_heatingtemp 5 0 1 14 1
Logamax Plus GB022 boiler 84 heatingpump heating pump boolean False binary_sensor.boiler_heating_pump binary_sensor.boiler_heatingpump 5 0 1 15 1
Logamax Plus GB022 boiler 84 pumpmodmax boiler pump max power uint8 (>=0<=100) % True number.boiler_boiler_pump_max_power number.boiler_pumpmodmax 5 0 1 16 1
Logamax Plus GB022 boiler 84 pumpmodmin boiler pump min power uint8 (>=0<=100) % True number.boiler_boiler_pump_min_power number.boiler_pumpmodmin 5 0 1 17 1
Logamax Plus GB022 boiler 84 pumpmode boiler pump mode enum [proportional|deltaP-1|deltaP-2|deltaP-3|deltaP-4] True select.boiler_boiler_pump_mode select.boiler_pumpmode 5 0 1 18 1
Logamax Plus GB022 boiler 84 pumpcharacter boiler pump characteristic enum [proportional|150mbar|200mbar|250mbar|300mbar|350mbar|400mbar] True select.boiler_boiler_pump_characteristic select.boiler_pumpcharacter 5 0 1 19 1
Logamax Plus GB022 boiler 84 pumpdelay pump delay uint8 (>=0<=60) minutes True number.boiler_pump_delay number.boiler_pumpdelay 5 0 1 20 1
Logamax Plus GB022 boiler 84 pumpontemp pump logic temperature uint8 (>=0<=60) C True number.boiler_pump_logic_temperature number.boiler_pumpontemp 5 0 1 21 1
Logamax Plus GB022 boiler 84 selburnpow burner selected max power uint8 (>=0<=254) % True number.boiler_burner_selected_max_power number.boiler_selburnpow 5 0 1 22 1
Logamax Plus GB022 boiler 84 curburnpow burner current power uint8 (>=0<=100) % False sensor.boiler_burner_current_power sensor.boiler_curburnpow 5 0 1 23 1
Logamax Plus GB022 boiler 84 burnstarts burner starts uint24 (>=0<=16777214) False sensor.boiler_burner_starts sensor.boiler_burnstarts 5 0 1 24 2
Logamax Plus GB022 boiler 84 burnworkmin total burner operating time time (>=0<=16777214) minutes False sensor.boiler_total_burner_operating_time sensor.boiler_burnworkmin 5 0 1 26 2
Logamax Plus GB022 boiler 84 burn2workmin burner stage 2 operating time time (>=0<=16777214) minutes False sensor.boiler_burner_stage_2_operating_time sensor.boiler_burn2workmin 5 0 1 28 2
Logamax Plus GB022 boiler 84 heatworkmin total heat operating time time (>=0<=16777214) minutes False sensor.boiler_total_heat_operating_time sensor.boiler_heatworkmin 5 0 1 30 2
Logamax Plus GB022 boiler 84 heatstarts burner starts heating uint24 (>=0<=16777214) False sensor.boiler_burner_starts_heating sensor.boiler_heatstarts 5 0 1 32 2
Logamax Plus GB022 boiler 84 ubauptime total UBA operating time time (>=0<=16777214) minutes False sensor.boiler_total_UBA_operating_time sensor.boiler_ubauptime 5 0 1 34 2
Logamax Plus GB022 boiler 84 lastcode last error code string False sensor.boiler_last_error_code sensor.boiler_lastcode 5 0 1 36 28
Logamax Plus GB022 boiler 84 servicecode service code string False sensor.boiler_service_code sensor.boiler_servicecode 5 0 1 64 2
Logamax Plus GB022 boiler 84 servicecodenumber service code number uint16 (>=0<=31999) False sensor.boiler_service_code_number sensor.boiler_servicecodenumber 5 0 1 66 1
Logamax Plus GB022 boiler 84 maintenancemessage maintenance message string False sensor.boiler_maintenance_message sensor.boiler_maintenancemessage 5 0 1 67 2
Logamax Plus GB022 boiler 84 maintenance maintenance scheduled enum [off|time|date|manual] True select.boiler_maintenance_scheduled select.boiler_maintenance 5 0 1 69 1
Logamax Plus GB022 boiler 84 maintenancetime time to next maintenance uint16 (>=0<=31999) hours True number.boiler_time_to_next_maintenance number.boiler_maintenancetime 5 0 1 70 1
Logamax Plus GB022 boiler 84 maintenancedate next maintenance date string True sensor.boiler_next_maintenance_date sensor.boiler_maintenancedate 5 0 1 71 6
Logamax Plus GB022 boiler 84 emergencyops emergency operation boolean True switch.boiler_emergency_operation switch.boiler_emergencyops 5 0 1 77 1
Logamax Plus GB022 boiler 84 emergencytemp emergency temperature uint8 (>=15<=70) C True number.boiler_emergency_temperature number.boiler_emergencytemp 5 0 1 78 1
Logamax Plus GB022 boiler 84 pc0flow Flow PC0 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC0 sensor.boiler_pc0flow 5 0 1 79 1
Logamax Plus GB022 boiler 84 pc1flow Flow PC1 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC1 sensor.boiler_pc1flow 5 0 1 80 1
Logamax Plus GB022 boiler 84 pc1on PC1 boolean False binary_sensor.boiler_PC1 binary_sensor.boiler_pc1on 5 0 1 81 1
Logamax Plus GB022 boiler 84 pc1rate PC1 rate uint8 (>=0<=100) % False sensor.boiler_PC1_rate sensor.boiler_pc1rate 5 0 1 82 1
Logamax Plus GB022 boiler 84 meterheat meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_meter_heating sensor.boiler_meterheat 5 0 1/10 95 2
Logamax Plus GB022 boiler 84 dhw.meter meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_meter sensor.boiler_dhw_meter 5 9 1/10 2 2
Logamax Plus GB022 boiler 84 gasmeterheat gas meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_gas_meter_heating sensor.boiler_gasmeterheat 5 0 1/10 266 2
Logamax Plus GB022 boiler 84 dhw.gasmeter gas meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_gas_meter sensor.boiler_dhw_gasmeter 5 9 1/10 69 2
Logamax Plus GB022 boiler 84 nrgheat2 energy heating 2 uint24 (>=0<=1677721) kWh False sensor.boiler_energy_heating_2 sensor.boiler_nrgheat2 5 0 1/10 268 2
Logamax Plus GB022 boiler 84 dhw.nrg2 energy 2 uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_energy_2 sensor.boiler_dhw_nrg2 5 9 1/10 71 2
Logamax Plus GB022 boiler 84 dhw.tapactivated turn on/off boolean True switch.boiler_dhw_turn_on/off switch.boiler_dhw_tapactivated 5 9 1 28 1
Logamax Plus GB022 boiler 84 dhw.settemp set temperature uint8 (>=0<=254) C False sensor.boiler_dhw_set_temperature sensor.boiler_dhw_settemp 5 9 1 29 1
Logamax Plus GB022 boiler 84 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_temperature number.boiler_dhw_seltemp 5 9 1 30 1
Logamax Plus GB022 boiler 84 dhw.seltemplow selected lower temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_lower_temperature number.boiler_dhw_seltemplow 5 9 1 31 1
Logamax Plus GB022 boiler 84 dhw.tempecoplus selected eco+ temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_eco+_temperature number.boiler_dhw_tempecoplus 5 9 1 32 1
Logamax Plus GB022 boiler 84 dhw.seltempoff selected temperature for off uint8 (>=0<=254) C False sensor.boiler_dhw_selected_temperature_for_off sensor.boiler_dhw_seltempoff 5 9 1 33 1
Logamax Plus GB022 boiler 84 dhw.seltempsingle single charge temperature uint8 (>=0<=254) C True number.boiler_dhw_single_charge_temperature number.boiler_dhw_seltempsingle 5 9 1 34 1
Logamax Plus GB022 boiler 84 dhw.solartemp solar boiler temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_solar_boiler_temperature sensor.boiler_dhw_solartemp 5 9 1/10 35 1
Logamax Plus GB022 boiler 84 dhw.type type enum [off|flow|buffered flow|buffer|layered buffer] False sensor.boiler_dhw_type sensor.boiler_dhw_type 5 9 1 36 1
Logamax Plus GB022 boiler 84 dhw.comfort comfort enum [hot|eco|intelligent] True select.boiler_dhw_comfort select.boiler_dhw_comfort 5 9 1 37 1
Logamax Plus GB022 boiler 84 dhw.comfort1 comfort mode enum [high comfort|eco] True select.boiler_dhw_comfort_mode select.boiler_dhw_comfort1 5 9 1 38 1
Logamax Plus GB022 boiler 84 dhw.flowtempoffset flow temperature offset uint8 (>=0<=100) C True number.boiler_dhw_flow_temperature_offset number.boiler_dhw_flowtempoffset 5 9 1 39 1
Logamax Plus GB022 boiler 84 dhw.chargeoptimization charge optimization boolean True switch.boiler_dhw_charge_optimization switch.boiler_dhw_chargeoptimization 5 9 1 40 1
Logamax Plus GB022 boiler 84 dhw.maxpower max power uint8 (>=0<=254) % True number.boiler_dhw_max_power number.boiler_dhw_maxpower 5 9 1 41 1
Logamax Plus GB022 boiler 84 dhw.maxtemp maximum temperature uint8 (>=0<=80) C True number.boiler_dhw_maximum_temperature number.boiler_dhw_maxtemp 5 9 1 42 1
Logamax Plus GB022 boiler 84 dhw.circpump circulation pump available boolean True switch.boiler_dhw_circulation_pump_available switch.boiler_dhw_circpump 5 9 1 43 1
Logamax Plus GB022 boiler 84 dhw.chargetype charging type enum [chargepump|3-way valve] False sensor.boiler_dhw_charging_type sensor.boiler_dhw_chargetype 5 9 1 44 1
Logamax Plus GB022 boiler 84 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_on_temperature number.boiler_dhw_hyston 5 9 1 45 1
Logamax Plus GB022 boiler 84 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_off_temperature number.boiler_dhw_hystoff 5 9 1 46 1
Logamax Plus GB022 boiler 84 dhw.disinfectiontemp disinfection temperature uint8 (>=60<=80) C True number.boiler_dhw_disinfection_temperature number.boiler_dhw_disinfectiontemp 5 9 1 47 1
Logamax Plus GB022 boiler 84 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.boiler_dhw_circulation_pump_mode select.boiler_dhw_circmode 5 9 1 48 1
Logamax Plus GB022 boiler 84 dhw.circ circulation active boolean True switch.boiler_dhw_circulation_active switch.boiler_dhw_circ 5 9 1 49 1
Logamax Plus GB022 boiler 84 dhw.curtemp current intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_intern_temperature sensor.boiler_dhw_curtemp 5 9 1/10 50 1
Logamax Plus GB022 boiler 84 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_extern_temperature sensor.boiler_dhw_curtemp2 5 9 1/10 51 1
Logamax Plus GB022 boiler 84 dhw.curflow current tap water flow uint8 (>=0<=25) l/min False sensor.boiler_dhw_current_tap_water_flow sensor.boiler_dhw_curflow 5 9 1/10 52 1
Logamax Plus GB022 boiler 84 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_intern_temperature sensor.boiler_dhw_storagetemp1 5 9 1/10 53 1
Logamax Plus GB022 boiler 84 dhw.storagetemp2 storage extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_extern_temperature sensor.boiler_dhw_storagetemp2 5 9 1/10 54 1
Logamax Plus GB022 boiler 84 dhw.activated activated boolean True switch.boiler_dhw_activated switch.boiler_dhw_activated 5 9 1 55 1
Logamax Plus GB022 boiler 84 dhw.onetime one time charging boolean True switch.boiler_dhw_one_time_charging switch.boiler_dhw_onetime 5 9 1 56 1
Logamax Plus GB022 boiler 84 dhw.disinfecting disinfecting boolean True switch.boiler_dhw_disinfecting switch.boiler_dhw_disinfecting 5 9 1 57 1
Logamax Plus GB022 boiler 84 dhw.charging charging boolean False binary_sensor.boiler_dhw_charging binary_sensor.boiler_dhw_charging 5 9 1 58 1
Logamax Plus GB022 boiler 84 dhw.recharging recharging boolean False binary_sensor.boiler_dhw_recharging binary_sensor.boiler_dhw_recharging 5 9 1 59 1
Logamax Plus GB022 boiler 84 dhw.tempok temperature ok boolean False binary_sensor.boiler_dhw_temperature_ok binary_sensor.boiler_dhw_tempok 5 9 1 60 1
Logamax Plus GB022 boiler 84 dhw.active active boolean False binary_sensor.boiler_dhw_active binary_sensor.boiler_dhw_active 5 9 1 61 1
Logamax Plus GB022 boiler 84 dhw.3wayvalve 3-way valve active boolean False binary_sensor.boiler_dhw_3-way_valve_active binary_sensor.boiler_dhw_3wayvalve 5 9 1 62 1
Logamax Plus GB022 boiler 84 dhw.mixertemp mixer temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_mixer_temperature sensor.boiler_dhw_mixertemp 5 9 1/10 63 1
Logamax Plus GB022 boiler 84 dhw.cylmiddletemp cylinder middle temperature (TS3) uint16 (>=0<=3199) C False sensor.boiler_dhw_cylinder_middle_temperature_(TS3) sensor.boiler_dhw_cylmiddletemp 5 9 1/10 64 1
Logamax Plus GB022 boiler 84 dhw.starts starts uint24 (>=0<=16777214) False sensor.boiler_dhw_starts sensor.boiler_dhw_starts 5 9 1 65 2
Logamax Plus GB022 boiler 84 dhw.workm active time time (>=0<=16777214) minutes False sensor.boiler_dhw_active_time sensor.boiler_dhw_workm 5 9 1 67 2
Logamax Plus GB022 boiler 84 nompower nominal Power uint8 (>=0<=254) kW True number.boiler_nominal_Power number.boiler_nompower 5 0 1 270 1
Logamax Plus GB022 boiler 84 nrgtotal total energy uint24 (>=0<=167772) kWh False sensor.boiler_total_energy sensor.boiler_nrgtotal 5 0 1/100 83 2
Logamax Plus GB022 boiler 84 nrgheat energy heating uint24 (>=0<=10000000) kWh True number.boiler_energy_heating number.boiler_nrgheat 5 0 1/100 85 2
Logamax Plus GB022 boiler 84 dhw.nrg energy uint24 (>=0<=10000000) kWh True number.boiler_dhw_energy number.boiler_dhw_nrg 5 9 1/100 0 2
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 reset reset cmd [-|maintenance|error|history|message] True sensor.boiler_reset sensor.boiler_reset 5 0 1 0 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 heatingoff force heating off boolean True switch.boiler_force_heating_off switch.boiler_heatingoff 5 0 1 1 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 heatingactive heating active boolean False binary_sensor.boiler_heating_active binary_sensor.boiler_heatingactive 5 0 1 2 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 tapwateractive tapwater active boolean False binary_sensor.boiler_tapwater_active binary_sensor.boiler_tapwateractive 5 0 1 3 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 selflowtemp selected flow temperature uint8 (>=0<=90) C True number.boiler_selected_flow_temperature number.boiler_selflowtemp 5 0 1 4 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.boiler_heating_pump_modulation sensor.boiler_heatingpumpmod 5 0 1 5 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 outdoortemp outside temperature int16 (>=-3199<=3199) C False sensor.boiler_outside_temperature sensor.boiler_outdoortemp 5 0 1/10 6 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 curflowtemp current flow temperature uint16 (>=0<=3199) C False sensor.boiler_current_flow_temperature sensor.boiler_curflowtemp 5 0 1/10 7 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 rettemp return temperature uint16 (>=0<=3199) C False sensor.boiler_return_temperature sensor.boiler_rettemp 5 0 1/10 8 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 switchtemp mixing switch temperature uint16 (>=0<=3199) C False sensor.boiler_mixing_switch_temperature sensor.boiler_switchtemp 5 0 1/10 9 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 syspress system pressure uint8 (>=0<=25) bar False sensor.boiler_system_pressure sensor.boiler_syspress 5 0 1/10 10 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 boiltemp actual boiler temperature uint16 (>=0<=3199) C False sensor.boiler_actual_boiler_temperature sensor.boiler_boiltemp 5 0 1/10 11 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 headertemp low loss header uint16 (>=0<=3199) C False sensor.boiler_low_loss_header sensor.boiler_headertemp 5 0 1/10 12 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 exhausttemp exhaust temperature uint16 (>=0<=3199) C False sensor.boiler_exhaust_temperature sensor.boiler_exhausttemp 5 0 1/10 244 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 burngas gas boolean False binary_sensor.boiler_gas binary_sensor.boiler_burngas 5 0 1 245 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 burngas2 gas stage 2 boolean False binary_sensor.boiler_gas_stage_2 binary_sensor.boiler_burngas2 5 0 1 246 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 flamecurr flame current uint16 (>=0<=3199) µA False sensor.boiler_flame_current sensor.boiler_flamecurr 5 0 1/10 247 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 fanwork fan boolean False binary_sensor.boiler_fan binary_sensor.boiler_fanwork 5 0 1 248 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 ignwork ignition boolean False binary_sensor.boiler_ignition binary_sensor.boiler_ignwork 5 0 1 249 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 oilpreheat oil preheating boolean False binary_sensor.boiler_oil_preheating binary_sensor.boiler_oilpreheat 5 0 1 250 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 burnminpower burner min power uint8 (>=0<=100) % True number.boiler_burner_min_power number.boiler_burnminpower 5 0 1 251 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 burnmaxpower burner max power uint8 (>=0<=254) % True number.boiler_burner_max_power number.boiler_burnmaxpower 5 0 1 252 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 burnminperiod burner min period uint8 (>=0<=120) minutes True number.boiler_burner_min_period number.boiler_burnminperiod 5 0 1 253 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 absburnpow burner current power (absolute) uint8 (>=0<=100) % False sensor.boiler_burner_current_power_(absolute) sensor.boiler_absburnpow 5 0 1 254 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 heatblock heating block uint16 (>=0<=3199) C False sensor.boiler_heating_block sensor.boiler_heatblock 5 0 1/10 255 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 boilhyston hysteresis on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_on_temperature number.boiler_boilhyston 5 0 1 256 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 boilhystoff hysteresis off temperature int8 (>=0<=20) C True number.boiler_hysteresis_off_temperature number.boiler_boilhystoff 5 0 1 257 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 boil2hyston hysteresis stage 2 on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_stage_2_on_temperature number.boiler_boil2hyston 5 0 1 258 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 boil2hystoff hysteresis stage 2 off temperature int8 (>=0<=20) C True number.boiler_hysteresis_stage_2_off_temperature number.boiler_boil2hystoff 5 0 1 259 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 curveon heatingcurve on boolean True switch.boiler_heatingcurve_on switch.boiler_curveon 5 0 1 260 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 curvebase heatingcurve base uint8 (>=20<=90) C True number.boiler_heatingcurve_base number.boiler_curvebase 5 0 1 261 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 curveend heatingcurve end uint8 (>=20<=90) C True number.boiler_heatingcurve_end number.boiler_curveend 5 0 1 262 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 summertemp summer temperature uint8 (>=0<=45) C True number.boiler_summer_temperature number.boiler_summertemp 5 0 1 263 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 nofrostmode nofrost mode boolean True switch.boiler_nofrost_mode switch.boiler_nofrostmode 5 0 1 264 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 nofrosttemp nofrost temperature uint8 (>=0<=10) C True number.boiler_nofrost_temperature number.boiler_nofrosttemp 5 0 1 265 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 heatingactivated heating activated boolean True switch.boiler_heating_activated switch.boiler_heatingactivated 5 0 1 13 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 heatingtemp heating temperature uint8 (>=0<=90) C True number.boiler_heating_temperature number.boiler_heatingtemp 5 0 1 14 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 heatingpump heating pump boolean False binary_sensor.boiler_heating_pump binary_sensor.boiler_heatingpump 5 0 1 15 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 pumpmodmax boiler pump max power uint8 (>=0<=100) % True number.boiler_boiler_pump_max_power number.boiler_pumpmodmax 5 0 1 16 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 pumpmodmin boiler pump min power uint8 (>=0<=100) % True number.boiler_boiler_pump_min_power number.boiler_pumpmodmin 5 0 1 17 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 pumpmode boiler pump mode enum [proportional|deltaP-1|deltaP-2|deltaP-3|deltaP-4] True select.boiler_boiler_pump_mode select.boiler_pumpmode 5 0 1 18 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 pumpcharacter boiler pump characteristic enum [proportional|150mbar|200mbar|250mbar|300mbar|350mbar|400mbar] True select.boiler_boiler_pump_characteristic select.boiler_pumpcharacter 5 0 1 19 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 pumpdelay pump delay uint8 (>=0<=60) minutes True number.boiler_pump_delay number.boiler_pumpdelay 5 0 1 20 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 pumpontemp pump logic temperature uint8 (>=0<=60) C True number.boiler_pump_logic_temperature number.boiler_pumpontemp 5 0 1 21 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 selburnpow burner selected max power uint8 (>=0<=254) % True number.boiler_burner_selected_max_power number.boiler_selburnpow 5 0 1 22 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 curburnpow burner current power uint8 (>=0<=100) % False sensor.boiler_burner_current_power sensor.boiler_curburnpow 5 0 1 23 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 burnstarts burner starts uint24 (>=0<=16777214) False sensor.boiler_burner_starts sensor.boiler_burnstarts 5 0 1 24 2
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 burnworkmin total burner operating time time (>=0<=16777214) minutes False sensor.boiler_total_burner_operating_time sensor.boiler_burnworkmin 5 0 1 26 2
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 burn2workmin burner stage 2 operating time time (>=0<=16777214) minutes False sensor.boiler_burner_stage_2_operating_time sensor.boiler_burn2workmin 5 0 1 28 2
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 heatworkmin total heat operating time time (>=0<=16777214) minutes False sensor.boiler_total_heat_operating_time sensor.boiler_heatworkmin 5 0 1 30 2
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 heatstarts burner starts heating uint24 (>=0<=16777214) False sensor.boiler_burner_starts_heating sensor.boiler_heatstarts 5 0 1 32 2
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 ubauptime total UBA operating time time (>=0<=16777214) minutes False sensor.boiler_total_UBA_operating_time sensor.boiler_ubauptime 5 0 1 34 2
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 lastcode last error code string False sensor.boiler_last_error_code sensor.boiler_lastcode 5 0 1 36 28
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 servicecode service code string False sensor.boiler_service_code sensor.boiler_servicecode 5 0 1 64 2
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 servicecodenumber service code number uint16 (>=0<=31999) False sensor.boiler_service_code_number sensor.boiler_servicecodenumber 5 0 1 66 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 maintenancemessage maintenance message string False sensor.boiler_maintenance_message sensor.boiler_maintenancemessage 5 0 1 67 2
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 maintenance maintenance scheduled enum [off|time|date|manual] True select.boiler_maintenance_scheduled select.boiler_maintenance 5 0 1 69 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 maintenancetime time to next maintenance uint16 (>=0<=31999) hours True number.boiler_time_to_next_maintenance number.boiler_maintenancetime 5 0 1 70 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 maintenancedate next maintenance date string True sensor.boiler_next_maintenance_date sensor.boiler_maintenancedate 5 0 1 71 6
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 emergencyops emergency operation boolean True switch.boiler_emergency_operation switch.boiler_emergencyops 5 0 1 77 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 emergencytemp emergency temperature uint8 (>=15<=70) C True number.boiler_emergency_temperature number.boiler_emergencytemp 5 0 1 78 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 pc0flow Flow PC0 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC0 sensor.boiler_pc0flow 5 0 1 79 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 pc1flow Flow PC1 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC1 sensor.boiler_pc1flow 5 0 1 80 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 pc1on PC1 boolean False binary_sensor.boiler_PC1 binary_sensor.boiler_pc1on 5 0 1 81 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 pc1rate PC1 rate uint8 (>=0<=100) % False sensor.boiler_PC1_rate sensor.boiler_pc1rate 5 0 1 82 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 meterheat meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_meter_heating sensor.boiler_meterheat 5 0 1/10 95 2
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.meter meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_meter sensor.boiler_dhw_meter 5 9 1/10 2 2
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 gasmeterheat gas meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_gas_meter_heating sensor.boiler_gasmeterheat 5 0 1/10 266 2
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.gasmeter gas meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_gas_meter sensor.boiler_dhw_gasmeter 5 9 1/10 69 2
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 nrgheat2 energy heating 2 uint24 (>=0<=1677721) kWh False sensor.boiler_energy_heating_2 sensor.boiler_nrgheat2 5 0 1/10 268 2
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.nrg2 energy 2 uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_energy_2 sensor.boiler_dhw_nrg2 5 9 1/10 71 2
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.tapactivated turn on/off boolean True switch.boiler_dhw_turn_on/off switch.boiler_dhw_tapactivated 5 9 1 28 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.settemp set temperature uint8 (>=0<=254) C False sensor.boiler_dhw_set_temperature sensor.boiler_dhw_settemp 5 9 1 29 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_temperature number.boiler_dhw_seltemp 5 9 1 30 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.seltemplow selected lower temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_lower_temperature number.boiler_dhw_seltemplow 5 9 1 31 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.tempecoplus selected eco+ temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_eco+_temperature number.boiler_dhw_tempecoplus 5 9 1 32 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.seltempoff selected temperature for off uint8 (>=0<=254) C False sensor.boiler_dhw_selected_temperature_for_off sensor.boiler_dhw_seltempoff 5 9 1 33 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.seltempsingle single charge temperature uint8 (>=0<=254) C True number.boiler_dhw_single_charge_temperature number.boiler_dhw_seltempsingle 5 9 1 34 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.solartemp solar boiler temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_solar_boiler_temperature sensor.boiler_dhw_solartemp 5 9 1/10 35 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.type type enum [off|flow|buffered flow|buffer|layered buffer] False sensor.boiler_dhw_type sensor.boiler_dhw_type 5 9 1 36 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.comfort comfort enum [hot|eco|intelligent] True select.boiler_dhw_comfort select.boiler_dhw_comfort 5 9 1 37 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.comfort1 comfort mode enum [high comfort|eco] True select.boiler_dhw_comfort_mode select.boiler_dhw_comfort1 5 9 1 38 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.flowtempoffset flow temperature offset uint8 (>=0<=100) C True number.boiler_dhw_flow_temperature_offset number.boiler_dhw_flowtempoffset 5 9 1 39 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.chargeoptimization charge optimization boolean True switch.boiler_dhw_charge_optimization switch.boiler_dhw_chargeoptimization 5 9 1 40 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.maxpower max power uint8 (>=0<=254) % True number.boiler_dhw_max_power number.boiler_dhw_maxpower 5 9 1 41 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.maxtemp maximum temperature uint8 (>=0<=80) C True number.boiler_dhw_maximum_temperature number.boiler_dhw_maxtemp 5 9 1 42 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.circpump circulation pump available boolean True switch.boiler_dhw_circulation_pump_available switch.boiler_dhw_circpump 5 9 1 43 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.chargetype charging type enum [chargepump|3-way valve] False sensor.boiler_dhw_charging_type sensor.boiler_dhw_chargetype 5 9 1 44 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_on_temperature number.boiler_dhw_hyston 5 9 1 45 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_off_temperature number.boiler_dhw_hystoff 5 9 1 46 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.disinfectiontemp disinfection temperature uint8 (>=60<=80) C True number.boiler_dhw_disinfection_temperature number.boiler_dhw_disinfectiontemp 5 9 1 47 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.boiler_dhw_circulation_pump_mode select.boiler_dhw_circmode 5 9 1 48 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.circ circulation active boolean True switch.boiler_dhw_circulation_active switch.boiler_dhw_circ 5 9 1 49 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.curtemp current intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_intern_temperature sensor.boiler_dhw_curtemp 5 9 1/10 50 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_extern_temperature sensor.boiler_dhw_curtemp2 5 9 1/10 51 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.curflow current tap water flow uint8 (>=0<=25) l/min False sensor.boiler_dhw_current_tap_water_flow sensor.boiler_dhw_curflow 5 9 1/10 52 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_intern_temperature sensor.boiler_dhw_storagetemp1 5 9 1/10 53 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.storagetemp2 storage extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_extern_temperature sensor.boiler_dhw_storagetemp2 5 9 1/10 54 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.activated activated boolean True switch.boiler_dhw_activated switch.boiler_dhw_activated 5 9 1 55 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.onetime one time charging boolean True switch.boiler_dhw_one_time_charging switch.boiler_dhw_onetime 5 9 1 56 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.disinfecting disinfecting boolean True switch.boiler_dhw_disinfecting switch.boiler_dhw_disinfecting 5 9 1 57 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.charging charging boolean False binary_sensor.boiler_dhw_charging binary_sensor.boiler_dhw_charging 5 9 1 58 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.recharging recharging boolean False binary_sensor.boiler_dhw_recharging binary_sensor.boiler_dhw_recharging 5 9 1 59 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.tempok temperature ok boolean False binary_sensor.boiler_dhw_temperature_ok binary_sensor.boiler_dhw_tempok 5 9 1 60 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.active active boolean False binary_sensor.boiler_dhw_active binary_sensor.boiler_dhw_active 5 9 1 61 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.3wayvalve 3-way valve active boolean False binary_sensor.boiler_dhw_3-way_valve_active binary_sensor.boiler_dhw_3wayvalve 5 9 1 62 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.mixertemp mixer temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_mixer_temperature sensor.boiler_dhw_mixertemp 5 9 1/10 63 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.cylmiddletemp cylinder middle temperature (TS3) uint16 (>=0<=3199) C False sensor.boiler_dhw_cylinder_middle_temperature_(TS3) sensor.boiler_dhw_cylmiddletemp 5 9 1/10 64 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.starts starts uint24 (>=0<=16777214) False sensor.boiler_dhw_starts sensor.boiler_dhw_starts 5 9 1 65 2
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.workm active time time (>=0<=16777214) minutes False sensor.boiler_dhw_active_time sensor.boiler_dhw_workm 5 9 1 67 2
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 nompower nominal Power uint8 (>=0<=254) kW True number.boiler_nominal_Power number.boiler_nompower 5 0 1 270 1
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 nrgtotal total energy uint24 (>=0<=167772) kWh False sensor.boiler_total_energy sensor.boiler_nrgtotal 5 0 1/100 83 2
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 nrgheat energy heating uint24 (>=0<=10000000) kWh True number.boiler_energy_heating number.boiler_nrgheat 5 0 1/100 85 2
Condens, Logamax/Logomatic, Cerapur Top, Greenstar, Generic HT3 boiler 95 dhw.nrg energy uint24 (>=0<=10000000) kWh True number.boiler_dhw_energy number.boiler_dhw_nrg 5 9 1/100 0 2
Topline, GB162 boiler 115 reset reset cmd [-|maintenance|error|history|message] True sensor.boiler_reset sensor.boiler_reset 5 0 1 0 1
Topline, GB162 boiler 115 heatingoff force heating off boolean True switch.boiler_force_heating_off switch.boiler_heatingoff 5 0 1 1 1
Topline, GB162 boiler 115 heatingactive heating active boolean False binary_sensor.boiler_heating_active binary_sensor.boiler_heatingactive 5 0 1 2 1
Topline, GB162 boiler 115 tapwateractive tapwater active boolean False binary_sensor.boiler_tapwater_active binary_sensor.boiler_tapwateractive 5 0 1 3 1
Topline, GB162 boiler 115 selflowtemp selected flow temperature uint8 (>=0<=90) C True number.boiler_selected_flow_temperature number.boiler_selflowtemp 5 0 1 4 1
Topline, GB162 boiler 115 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.boiler_heating_pump_modulation sensor.boiler_heatingpumpmod 5 0 1 5 1
Topline, GB162 boiler 115 outdoortemp outside temperature int16 (>=-3199<=3199) C False sensor.boiler_outside_temperature sensor.boiler_outdoortemp 5 0 1/10 6 1
Topline, GB162 boiler 115 curflowtemp current flow temperature uint16 (>=0<=3199) C False sensor.boiler_current_flow_temperature sensor.boiler_curflowtemp 5 0 1/10 7 1
Topline, GB162 boiler 115 rettemp return temperature uint16 (>=0<=3199) C False sensor.boiler_return_temperature sensor.boiler_rettemp 5 0 1/10 8 1
Topline, GB162 boiler 115 switchtemp mixing switch temperature uint16 (>=0<=3199) C False sensor.boiler_mixing_switch_temperature sensor.boiler_switchtemp 5 0 1/10 9 1
Topline, GB162 boiler 115 syspress system pressure uint8 (>=0<=25) bar False sensor.boiler_system_pressure sensor.boiler_syspress 5 0 1/10 10 1
Topline, GB162 boiler 115 boiltemp actual boiler temperature uint16 (>=0<=3199) C False sensor.boiler_actual_boiler_temperature sensor.boiler_boiltemp 5 0 1/10 11 1
Topline, GB162 boiler 115 headertemp low loss header uint16 (>=0<=3199) C False sensor.boiler_low_loss_header sensor.boiler_headertemp 5 0 1/10 12 1
Topline, GB162 boiler 115 exhausttemp exhaust temperature uint16 (>=0<=3199) C False sensor.boiler_exhaust_temperature sensor.boiler_exhausttemp 5 0 1/10 244 1
Topline, GB162 boiler 115 burngas gas boolean False binary_sensor.boiler_gas binary_sensor.boiler_burngas 5 0 1 245 1
Topline, GB162 boiler 115 burngas2 gas stage 2 boolean False binary_sensor.boiler_gas_stage_2 binary_sensor.boiler_burngas2 5 0 1 246 1
Topline, GB162 boiler 115 flamecurr flame current uint16 (>=0<=3199) µA False sensor.boiler_flame_current sensor.boiler_flamecurr 5 0 1/10 247 1
Topline, GB162 boiler 115 fanwork fan boolean False binary_sensor.boiler_fan binary_sensor.boiler_fanwork 5 0 1 248 1
Topline, GB162 boiler 115 ignwork ignition boolean False binary_sensor.boiler_ignition binary_sensor.boiler_ignwork 5 0 1 249 1
Topline, GB162 boiler 115 oilpreheat oil preheating boolean False binary_sensor.boiler_oil_preheating binary_sensor.boiler_oilpreheat 5 0 1 250 1
Topline, GB162 boiler 115 burnminpower burner min power uint8 (>=0<=100) % True number.boiler_burner_min_power number.boiler_burnminpower 5 0 1 251 1
Topline, GB162 boiler 115 burnmaxpower burner max power uint8 (>=0<=254) % True number.boiler_burner_max_power number.boiler_burnmaxpower 5 0 1 252 1
Topline, GB162 boiler 115 burnminperiod burner min period uint8 (>=0<=120) minutes True number.boiler_burner_min_period number.boiler_burnminperiod 5 0 1 253 1
Topline, GB162 boiler 115 absburnpow burner current power (absolute) uint8 (>=0<=100) % False sensor.boiler_burner_current_power_(absolute) sensor.boiler_absburnpow 5 0 1 254 1
Topline, GB162 boiler 115 heatblock heating block uint16 (>=0<=3199) C False sensor.boiler_heating_block sensor.boiler_heatblock 5 0 1/10 255 1
Topline, GB162 boiler 115 boilhyston hysteresis on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_on_temperature number.boiler_boilhyston 5 0 1 256 1
Topline, GB162 boiler 115 boilhystoff hysteresis off temperature int8 (>=0<=20) C True number.boiler_hysteresis_off_temperature number.boiler_boilhystoff 5 0 1 257 1
Topline, GB162 boiler 115 boil2hyston hysteresis stage 2 on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_stage_2_on_temperature number.boiler_boil2hyston 5 0 1 258 1
Topline, GB162 boiler 115 boil2hystoff hysteresis stage 2 off temperature int8 (>=0<=20) C True number.boiler_hysteresis_stage_2_off_temperature number.boiler_boil2hystoff 5 0 1 259 1
Topline, GB162 boiler 115 curveon heatingcurve on boolean True switch.boiler_heatingcurve_on switch.boiler_curveon 5 0 1 260 1
Topline, GB162 boiler 115 curvebase heatingcurve base uint8 (>=20<=90) C True number.boiler_heatingcurve_base number.boiler_curvebase 5 0 1 261 1
Topline, GB162 boiler 115 curveend heatingcurve end uint8 (>=20<=90) C True number.boiler_heatingcurve_end number.boiler_curveend 5 0 1 262 1
Topline, GB162 boiler 115 summertemp summer temperature uint8 (>=0<=45) C True number.boiler_summer_temperature number.boiler_summertemp 5 0 1 263 1
Topline, GB162 boiler 115 nofrostmode nofrost mode boolean True switch.boiler_nofrost_mode switch.boiler_nofrostmode 5 0 1 264 1
Topline, GB162 boiler 115 nofrosttemp nofrost temperature uint8 (>=0<=10) C True number.boiler_nofrost_temperature number.boiler_nofrosttemp 5 0 1 265 1
Topline, GB162 boiler 115 heatingactivated heating activated boolean True switch.boiler_heating_activated switch.boiler_heatingactivated 5 0 1 13 1
Topline, GB162 boiler 115 heatingtemp heating temperature uint8 (>=0<=90) C True number.boiler_heating_temperature number.boiler_heatingtemp 5 0 1 14 1
Topline, GB162 boiler 115 heatingpump heating pump boolean False binary_sensor.boiler_heating_pump binary_sensor.boiler_heatingpump 5 0 1 15 1
Topline, GB162 boiler 115 pumpmodmax boiler pump max power uint8 (>=0<=100) % True number.boiler_boiler_pump_max_power number.boiler_pumpmodmax 5 0 1 16 1
Topline, GB162 boiler 115 pumpmodmin boiler pump min power uint8 (>=0<=100) % True number.boiler_boiler_pump_min_power number.boiler_pumpmodmin 5 0 1 17 1
Topline, GB162 boiler 115 pumpmode boiler pump mode enum [proportional|deltaP-1|deltaP-2|deltaP-3|deltaP-4] True select.boiler_boiler_pump_mode select.boiler_pumpmode 5 0 1 18 1
Topline, GB162 boiler 115 pumpcharacter boiler pump characteristic enum [proportional|150mbar|200mbar|250mbar|300mbar|350mbar|400mbar] True select.boiler_boiler_pump_characteristic select.boiler_pumpcharacter 5 0 1 19 1
Topline, GB162 boiler 115 pumpdelay pump delay uint8 (>=0<=60) minutes True number.boiler_pump_delay number.boiler_pumpdelay 5 0 1 20 1
Topline, GB162 boiler 115 pumpontemp pump logic temperature uint8 (>=0<=60) C True number.boiler_pump_logic_temperature number.boiler_pumpontemp 5 0 1 21 1
Topline, GB162 boiler 115 selburnpow burner selected max power uint8 (>=0<=254) % True number.boiler_burner_selected_max_power number.boiler_selburnpow 5 0 1 22 1
Topline, GB162 boiler 115 curburnpow burner current power uint8 (>=0<=100) % False sensor.boiler_burner_current_power sensor.boiler_curburnpow 5 0 1 23 1
Topline, GB162 boiler 115 burnstarts burner starts uint24 (>=0<=16777214) False sensor.boiler_burner_starts sensor.boiler_burnstarts 5 0 1 24 2
Topline, GB162 boiler 115 burnworkmin total burner operating time time (>=0<=16777214) minutes False sensor.boiler_total_burner_operating_time sensor.boiler_burnworkmin 5 0 1 26 2
Topline, GB162 boiler 115 burn2workmin burner stage 2 operating time time (>=0<=16777214) minutes False sensor.boiler_burner_stage_2_operating_time sensor.boiler_burn2workmin 5 0 1 28 2
Topline, GB162 boiler 115 heatworkmin total heat operating time time (>=0<=16777214) minutes False sensor.boiler_total_heat_operating_time sensor.boiler_heatworkmin 5 0 1 30 2
Topline, GB162 boiler 115 heatstarts burner starts heating uint24 (>=0<=16777214) False sensor.boiler_burner_starts_heating sensor.boiler_heatstarts 5 0 1 32 2
Topline, GB162 boiler 115 ubauptime total UBA operating time time (>=0<=16777214) minutes False sensor.boiler_total_UBA_operating_time sensor.boiler_ubauptime 5 0 1 34 2
Topline, GB162 boiler 115 lastcode last error code string False sensor.boiler_last_error_code sensor.boiler_lastcode 5 0 1 36 28
Topline, GB162 boiler 115 servicecode service code string False sensor.boiler_service_code sensor.boiler_servicecode 5 0 1 64 2
Topline, GB162 boiler 115 servicecodenumber service code number uint16 (>=0<=31999) False sensor.boiler_service_code_number sensor.boiler_servicecodenumber 5 0 1 66 1
Topline, GB162 boiler 115 maintenancemessage maintenance message string False sensor.boiler_maintenance_message sensor.boiler_maintenancemessage 5 0 1 67 2
Topline, GB162 boiler 115 maintenance maintenance scheduled enum [off|time|date|manual] True select.boiler_maintenance_scheduled select.boiler_maintenance 5 0 1 69 1
Topline, GB162 boiler 115 maintenancetime time to next maintenance uint16 (>=0<=31999) hours True number.boiler_time_to_next_maintenance number.boiler_maintenancetime 5 0 1 70 1
Topline, GB162 boiler 115 maintenancedate next maintenance date string True sensor.boiler_next_maintenance_date sensor.boiler_maintenancedate 5 0 1 71 6
Topline, GB162 boiler 115 emergencyops emergency operation boolean True switch.boiler_emergency_operation switch.boiler_emergencyops 5 0 1 77 1
Topline, GB162 boiler 115 emergencytemp emergency temperature uint8 (>=15<=70) C True number.boiler_emergency_temperature number.boiler_emergencytemp 5 0 1 78 1
Topline, GB162 boiler 115 pc0flow Flow PC0 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC0 sensor.boiler_pc0flow 5 0 1 79 1
Topline, GB162 boiler 115 pc1flow Flow PC1 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC1 sensor.boiler_pc1flow 5 0 1 80 1
Topline, GB162 boiler 115 pc1on PC1 boolean False binary_sensor.boiler_PC1 binary_sensor.boiler_pc1on 5 0 1 81 1
Topline, GB162 boiler 115 pc1rate PC1 rate uint8 (>=0<=100) % False sensor.boiler_PC1_rate sensor.boiler_pc1rate 5 0 1 82 1
Topline, GB162 boiler 115 meterheat meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_meter_heating sensor.boiler_meterheat 5 0 1/10 95 2
Topline, GB162 boiler 115 dhw.meter meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_meter sensor.boiler_dhw_meter 5 9 1/10 2 2
Topline, GB162 boiler 115 gasmeterheat gas meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_gas_meter_heating sensor.boiler_gasmeterheat 5 0 1/10 266 2
Topline, GB162 boiler 115 dhw.gasmeter gas meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_gas_meter sensor.boiler_dhw_gasmeter 5 9 1/10 69 2
Topline, GB162 boiler 115 nrgheat2 energy heating 2 uint24 (>=0<=1677721) kWh False sensor.boiler_energy_heating_2 sensor.boiler_nrgheat2 5 0 1/10 268 2
Topline, GB162 boiler 115 dhw.nrg2 energy 2 uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_energy_2 sensor.boiler_dhw_nrg2 5 9 1/10 71 2
Topline, GB162 boiler 115 dhw.tapactivated turn on/off boolean True switch.boiler_dhw_turn_on/off switch.boiler_dhw_tapactivated 5 9 1 28 1
Topline, GB162 boiler 115 dhw.settemp set temperature uint8 (>=0<=254) C False sensor.boiler_dhw_set_temperature sensor.boiler_dhw_settemp 5 9 1 29 1
Topline, GB162 boiler 115 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_temperature number.boiler_dhw_seltemp 5 9 1 30 1
Topline, GB162 boiler 115 dhw.seltemplow selected lower temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_lower_temperature number.boiler_dhw_seltemplow 5 9 1 31 1
Topline, GB162 boiler 115 dhw.tempecoplus selected eco+ temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_eco+_temperature number.boiler_dhw_tempecoplus 5 9 1 32 1
Topline, GB162 boiler 115 dhw.seltempoff selected temperature for off uint8 (>=0<=254) C False sensor.boiler_dhw_selected_temperature_for_off sensor.boiler_dhw_seltempoff 5 9 1 33 1
Topline, GB162 boiler 115 dhw.seltempsingle single charge temperature uint8 (>=0<=254) C True number.boiler_dhw_single_charge_temperature number.boiler_dhw_seltempsingle 5 9 1 34 1
Topline, GB162 boiler 115 dhw.solartemp solar boiler temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_solar_boiler_temperature sensor.boiler_dhw_solartemp 5 9 1/10 35 1
Topline, GB162 boiler 115 dhw.type type enum [off|flow|buffered flow|buffer|layered buffer] False sensor.boiler_dhw_type sensor.boiler_dhw_type 5 9 1 36 1
Topline, GB162 boiler 115 dhw.comfort comfort enum [hot|eco|intelligent] True select.boiler_dhw_comfort select.boiler_dhw_comfort 5 9 1 37 1
Topline, GB162 boiler 115 dhw.comfort1 comfort mode enum [high comfort|eco] True select.boiler_dhw_comfort_mode select.boiler_dhw_comfort1 5 9 1 38 1
Topline, GB162 boiler 115 dhw.flowtempoffset flow temperature offset uint8 (>=0<=100) C True number.boiler_dhw_flow_temperature_offset number.boiler_dhw_flowtempoffset 5 9 1 39 1
Topline, GB162 boiler 115 dhw.chargeoptimization charge optimization boolean True switch.boiler_dhw_charge_optimization switch.boiler_dhw_chargeoptimization 5 9 1 40 1
Topline, GB162 boiler 115 dhw.maxpower max power uint8 (>=0<=254) % True number.boiler_dhw_max_power number.boiler_dhw_maxpower 5 9 1 41 1
Topline, GB162 boiler 115 dhw.maxtemp maximum temperature uint8 (>=0<=80) C True number.boiler_dhw_maximum_temperature number.boiler_dhw_maxtemp 5 9 1 42 1
Topline, GB162 boiler 115 dhw.circpump circulation pump available boolean True switch.boiler_dhw_circulation_pump_available switch.boiler_dhw_circpump 5 9 1 43 1
Topline, GB162 boiler 115 dhw.chargetype charging type enum [chargepump|3-way valve] False sensor.boiler_dhw_charging_type sensor.boiler_dhw_chargetype 5 9 1 44 1
Topline, GB162 boiler 115 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_on_temperature number.boiler_dhw_hyston 5 9 1 45 1
Topline, GB162 boiler 115 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_off_temperature number.boiler_dhw_hystoff 5 9 1 46 1
Topline, GB162 boiler 115 dhw.disinfectiontemp disinfection temperature uint8 (>=60<=80) C True number.boiler_dhw_disinfection_temperature number.boiler_dhw_disinfectiontemp 5 9 1 47 1
Topline, GB162 boiler 115 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.boiler_dhw_circulation_pump_mode select.boiler_dhw_circmode 5 9 1 48 1
Topline, GB162 boiler 115 dhw.circ circulation active boolean True switch.boiler_dhw_circulation_active switch.boiler_dhw_circ 5 9 1 49 1
Topline, GB162 boiler 115 dhw.curtemp current intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_intern_temperature sensor.boiler_dhw_curtemp 5 9 1/10 50 1
Topline, GB162 boiler 115 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_extern_temperature sensor.boiler_dhw_curtemp2 5 9 1/10 51 1
Topline, GB162 boiler 115 dhw.curflow current tap water flow uint8 (>=0<=25) l/min False sensor.boiler_dhw_current_tap_water_flow sensor.boiler_dhw_curflow 5 9 1/10 52 1
Topline, GB162 boiler 115 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_intern_temperature sensor.boiler_dhw_storagetemp1 5 9 1/10 53 1
Topline, GB162 boiler 115 dhw.storagetemp2 storage extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_extern_temperature sensor.boiler_dhw_storagetemp2 5 9 1/10 54 1
Topline, GB162 boiler 115 dhw.activated activated boolean True switch.boiler_dhw_activated switch.boiler_dhw_activated 5 9 1 55 1
Topline, GB162 boiler 115 dhw.onetime one time charging boolean True switch.boiler_dhw_one_time_charging switch.boiler_dhw_onetime 5 9 1 56 1
Topline, GB162 boiler 115 dhw.disinfecting disinfecting boolean True switch.boiler_dhw_disinfecting switch.boiler_dhw_disinfecting 5 9 1 57 1
Topline, GB162 boiler 115 dhw.charging charging boolean False binary_sensor.boiler_dhw_charging binary_sensor.boiler_dhw_charging 5 9 1 58 1
Topline, GB162 boiler 115 dhw.recharging recharging boolean False binary_sensor.boiler_dhw_recharging binary_sensor.boiler_dhw_recharging 5 9 1 59 1
Topline, GB162 boiler 115 dhw.tempok temperature ok boolean False binary_sensor.boiler_dhw_temperature_ok binary_sensor.boiler_dhw_tempok 5 9 1 60 1
Topline, GB162 boiler 115 dhw.active active boolean False binary_sensor.boiler_dhw_active binary_sensor.boiler_dhw_active 5 9 1 61 1
Topline, GB162 boiler 115 dhw.3wayvalve 3-way valve active boolean False binary_sensor.boiler_dhw_3-way_valve_active binary_sensor.boiler_dhw_3wayvalve 5 9 1 62 1
Topline, GB162 boiler 115 dhw.mixertemp mixer temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_mixer_temperature sensor.boiler_dhw_mixertemp 5 9 1/10 63 1
Topline, GB162 boiler 115 dhw.cylmiddletemp cylinder middle temperature (TS3) uint16 (>=0<=3199) C False sensor.boiler_dhw_cylinder_middle_temperature_(TS3) sensor.boiler_dhw_cylmiddletemp 5 9 1/10 64 1
Topline, GB162 boiler 115 dhw.starts starts uint24 (>=0<=16777214) False sensor.boiler_dhw_starts sensor.boiler_dhw_starts 5 9 1 65 2
Topline, GB162 boiler 115 dhw.workm active time time (>=0<=16777214) minutes False sensor.boiler_dhw_active_time sensor.boiler_dhw_workm 5 9 1 67 2
Topline, GB162 boiler 115 nompower nominal Power uint8 (>=0<=254) kW True number.boiler_nominal_Power number.boiler_nompower 5 0 1 270 1
Topline, GB162 boiler 115 nrgtotal total energy uint24 (>=0<=167772) kWh False sensor.boiler_total_energy sensor.boiler_nrgtotal 5 0 1/100 83 2
Topline, GB162 boiler 115 nrgheat energy heating uint24 (>=0<=10000000) kWh True number.boiler_energy_heating number.boiler_nrgheat 5 0 1/100 85 2
Topline, GB162 boiler 115 dhw.nrg energy uint24 (>=0<=10000000) kWh True number.boiler_dhw_energy number.boiler_dhw_nrg 5 9 1/100 0 2
Cascade MCM10 boiler 121 reset reset cmd [-|maintenance|error|history|message] True sensor.boiler_reset sensor.boiler_reset 5 0 1 0 1
Cascade MCM10 boiler 121 heatingoff force heating off boolean True switch.boiler_force_heating_off switch.boiler_heatingoff 5 0 1 1 1
Cascade MCM10 boiler 121 heatingactive heating active boolean False binary_sensor.boiler_heating_active binary_sensor.boiler_heatingactive 5 0 1 2 1
Cascade MCM10 boiler 121 tapwateractive tapwater active boolean False binary_sensor.boiler_tapwater_active binary_sensor.boiler_tapwateractive 5 0 1 3 1
Cascade MCM10 boiler 121 selflowtemp selected flow temperature uint8 (>=0<=90) C True number.boiler_selected_flow_temperature number.boiler_selflowtemp 5 0 1 4 1
Cascade MCM10 boiler 121 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.boiler_heating_pump_modulation sensor.boiler_heatingpumpmod 5 0 1 5 1
Cascade MCM10 boiler 121 outdoortemp outside temperature int16 (>=-3199<=3199) C False sensor.boiler_outside_temperature sensor.boiler_outdoortemp 5 0 1/10 6 1
Cascade MCM10 boiler 121 curflowtemp current flow temperature uint16 (>=0<=3199) C False sensor.boiler_current_flow_temperature sensor.boiler_curflowtemp 5 0 1/10 7 1
Cascade MCM10 boiler 121 rettemp return temperature uint16 (>=0<=3199) C False sensor.boiler_return_temperature sensor.boiler_rettemp 5 0 1/10 8 1
Cascade MCM10 boiler 121 switchtemp mixing switch temperature uint16 (>=0<=3199) C False sensor.boiler_mixing_switch_temperature sensor.boiler_switchtemp 5 0 1/10 9 1
Cascade MCM10 boiler 121 syspress system pressure uint8 (>=0<=25) bar False sensor.boiler_system_pressure sensor.boiler_syspress 5 0 1/10 10 1
Cascade MCM10 boiler 121 boiltemp actual boiler temperature uint16 (>=0<=3199) C False sensor.boiler_actual_boiler_temperature sensor.boiler_boiltemp 5 0 1/10 11 1
Cascade MCM10 boiler 121 headertemp low loss header uint16 (>=0<=3199) C False sensor.boiler_low_loss_header sensor.boiler_headertemp 5 0 1/10 12 1
Cascade MCM10 boiler 121 exhausttemp exhaust temperature uint16 (>=0<=3199) C False sensor.boiler_exhaust_temperature sensor.boiler_exhausttemp 5 0 1/10 244 1
Cascade MCM10 boiler 121 burngas gas boolean False binary_sensor.boiler_gas binary_sensor.boiler_burngas 5 0 1 245 1
Cascade MCM10 boiler 121 burngas2 gas stage 2 boolean False binary_sensor.boiler_gas_stage_2 binary_sensor.boiler_burngas2 5 0 1 246 1
Cascade MCM10 boiler 121 flamecurr flame current uint16 (>=0<=3199) µA False sensor.boiler_flame_current sensor.boiler_flamecurr 5 0 1/10 247 1
Cascade MCM10 boiler 121 fanwork fan boolean False binary_sensor.boiler_fan binary_sensor.boiler_fanwork 5 0 1 248 1
Cascade MCM10 boiler 121 ignwork ignition boolean False binary_sensor.boiler_ignition binary_sensor.boiler_ignwork 5 0 1 249 1
Cascade MCM10 boiler 121 oilpreheat oil preheating boolean False binary_sensor.boiler_oil_preheating binary_sensor.boiler_oilpreheat 5 0 1 250 1
Cascade MCM10 boiler 121 burnminpower burner min power uint8 (>=0<=100) % True number.boiler_burner_min_power number.boiler_burnminpower 5 0 1 251 1
Cascade MCM10 boiler 121 burnmaxpower burner max power uint8 (>=0<=254) % True number.boiler_burner_max_power number.boiler_burnmaxpower 5 0 1 252 1
Cascade MCM10 boiler 121 burnminperiod burner min period uint8 (>=0<=120) minutes True number.boiler_burner_min_period number.boiler_burnminperiod 5 0 1 253 1
Cascade MCM10 boiler 121 absburnpow burner current power (absolute) uint8 (>=0<=100) % False sensor.boiler_burner_current_power_(absolute) sensor.boiler_absburnpow 5 0 1 254 1
Cascade MCM10 boiler 121 heatblock heating block uint16 (>=0<=3199) C False sensor.boiler_heating_block sensor.boiler_heatblock 5 0 1/10 255 1
Cascade MCM10 boiler 121 boilhyston hysteresis on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_on_temperature number.boiler_boilhyston 5 0 1 256 1
Cascade MCM10 boiler 121 boilhystoff hysteresis off temperature int8 (>=0<=20) C True number.boiler_hysteresis_off_temperature number.boiler_boilhystoff 5 0 1 257 1
Cascade MCM10 boiler 121 boil2hyston hysteresis stage 2 on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_stage_2_on_temperature number.boiler_boil2hyston 5 0 1 258 1
Cascade MCM10 boiler 121 boil2hystoff hysteresis stage 2 off temperature int8 (>=0<=20) C True number.boiler_hysteresis_stage_2_off_temperature number.boiler_boil2hystoff 5 0 1 259 1
Cascade MCM10 boiler 121 curveon heatingcurve on boolean True switch.boiler_heatingcurve_on switch.boiler_curveon 5 0 1 260 1
Cascade MCM10 boiler 121 curvebase heatingcurve base uint8 (>=20<=90) C True number.boiler_heatingcurve_base number.boiler_curvebase 5 0 1 261 1
Cascade MCM10 boiler 121 curveend heatingcurve end uint8 (>=20<=90) C True number.boiler_heatingcurve_end number.boiler_curveend 5 0 1 262 1
Cascade MCM10 boiler 121 summertemp summer temperature uint8 (>=0<=45) C True number.boiler_summer_temperature number.boiler_summertemp 5 0 1 263 1
Cascade MCM10 boiler 121 nofrostmode nofrost mode boolean True switch.boiler_nofrost_mode switch.boiler_nofrostmode 5 0 1 264 1
Cascade MCM10 boiler 121 nofrosttemp nofrost temperature uint8 (>=0<=10) C True number.boiler_nofrost_temperature number.boiler_nofrosttemp 5 0 1 265 1
Cascade MCM10 boiler 121 heatingactivated heating activated boolean True switch.boiler_heating_activated switch.boiler_heatingactivated 5 0 1 13 1
Cascade MCM10 boiler 121 heatingtemp heating temperature uint8 (>=0<=90) C True number.boiler_heating_temperature number.boiler_heatingtemp 5 0 1 14 1
Cascade MCM10 boiler 121 heatingpump heating pump boolean False binary_sensor.boiler_heating_pump binary_sensor.boiler_heatingpump 5 0 1 15 1
Cascade MCM10 boiler 121 pumpmodmax boiler pump max power uint8 (>=0<=100) % True number.boiler_boiler_pump_max_power number.boiler_pumpmodmax 5 0 1 16 1
Cascade MCM10 boiler 121 pumpmodmin boiler pump min power uint8 (>=0<=100) % True number.boiler_boiler_pump_min_power number.boiler_pumpmodmin 5 0 1 17 1
Cascade MCM10 boiler 121 pumpmode boiler pump mode enum [proportional|deltaP-1|deltaP-2|deltaP-3|deltaP-4] True select.boiler_boiler_pump_mode select.boiler_pumpmode 5 0 1 18 1
Cascade MCM10 boiler 121 pumpcharacter boiler pump characteristic enum [proportional|150mbar|200mbar|250mbar|300mbar|350mbar|400mbar] True select.boiler_boiler_pump_characteristic select.boiler_pumpcharacter 5 0 1 19 1
Cascade MCM10 boiler 121 pumpdelay pump delay uint8 (>=0<=60) minutes True number.boiler_pump_delay number.boiler_pumpdelay 5 0 1 20 1
Cascade MCM10 boiler 121 pumpontemp pump logic temperature uint8 (>=0<=60) C True number.boiler_pump_logic_temperature number.boiler_pumpontemp 5 0 1 21 1
Cascade MCM10 boiler 121 selburnpow burner selected max power uint8 (>=0<=254) % True number.boiler_burner_selected_max_power number.boiler_selburnpow 5 0 1 22 1
Cascade MCM10 boiler 121 curburnpow burner current power uint8 (>=0<=100) % False sensor.boiler_burner_current_power sensor.boiler_curburnpow 5 0 1 23 1
Cascade MCM10 boiler 121 burnstarts burner starts uint24 (>=0<=16777214) False sensor.boiler_burner_starts sensor.boiler_burnstarts 5 0 1 24 2
Cascade MCM10 boiler 121 burnworkmin total burner operating time time (>=0<=16777214) minutes False sensor.boiler_total_burner_operating_time sensor.boiler_burnworkmin 5 0 1 26 2
Cascade MCM10 boiler 121 burn2workmin burner stage 2 operating time time (>=0<=16777214) minutes False sensor.boiler_burner_stage_2_operating_time sensor.boiler_burn2workmin 5 0 1 28 2
Cascade MCM10 boiler 121 heatworkmin total heat operating time time (>=0<=16777214) minutes False sensor.boiler_total_heat_operating_time sensor.boiler_heatworkmin 5 0 1 30 2
Cascade MCM10 boiler 121 heatstarts burner starts heating uint24 (>=0<=16777214) False sensor.boiler_burner_starts_heating sensor.boiler_heatstarts 5 0 1 32 2
Cascade MCM10 boiler 121 ubauptime total UBA operating time time (>=0<=16777214) minutes False sensor.boiler_total_UBA_operating_time sensor.boiler_ubauptime 5 0 1 34 2
Cascade MCM10 boiler 121 lastcode last error code string False sensor.boiler_last_error_code sensor.boiler_lastcode 5 0 1 36 28
Cascade MCM10 boiler 121 servicecode service code string False sensor.boiler_service_code sensor.boiler_servicecode 5 0 1 64 2
Cascade MCM10 boiler 121 servicecodenumber service code number uint16 (>=0<=31999) False sensor.boiler_service_code_number sensor.boiler_servicecodenumber 5 0 1 66 1
Cascade MCM10 boiler 121 maintenancemessage maintenance message string False sensor.boiler_maintenance_message sensor.boiler_maintenancemessage 5 0 1 67 2
Cascade MCM10 boiler 121 maintenance maintenance scheduled enum [off|time|date|manual] True select.boiler_maintenance_scheduled select.boiler_maintenance 5 0 1 69 1
Cascade MCM10 boiler 121 maintenancetime time to next maintenance uint16 (>=0<=31999) hours True number.boiler_time_to_next_maintenance number.boiler_maintenancetime 5 0 1 70 1
Cascade MCM10 boiler 121 maintenancedate next maintenance date string True sensor.boiler_next_maintenance_date sensor.boiler_maintenancedate 5 0 1 71 6
Cascade MCM10 boiler 121 emergencyops emergency operation boolean True switch.boiler_emergency_operation switch.boiler_emergencyops 5 0 1 77 1
Cascade MCM10 boiler 121 emergencytemp emergency temperature uint8 (>=15<=70) C True number.boiler_emergency_temperature number.boiler_emergencytemp 5 0 1 78 1
Cascade MCM10 boiler 121 pc0flow Flow PC0 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC0 sensor.boiler_pc0flow 5 0 1 79 1
Cascade MCM10 boiler 121 pc1flow Flow PC1 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC1 sensor.boiler_pc1flow 5 0 1 80 1
Cascade MCM10 boiler 121 pc1on PC1 boolean False binary_sensor.boiler_PC1 binary_sensor.boiler_pc1on 5 0 1 81 1
Cascade MCM10 boiler 121 pc1rate PC1 rate uint8 (>=0<=100) % False sensor.boiler_PC1_rate sensor.boiler_pc1rate 5 0 1 82 1
Cascade MCM10 boiler 121 meterheat meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_meter_heating sensor.boiler_meterheat 5 0 1/10 95 2
Cascade MCM10 boiler 121 dhw.meter meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_meter sensor.boiler_dhw_meter 5 9 1/10 2 2
Cascade MCM10 boiler 121 gasmeterheat gas meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_gas_meter_heating sensor.boiler_gasmeterheat 5 0 1/10 266 2
Cascade MCM10 boiler 121 dhw.gasmeter gas meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_gas_meter sensor.boiler_dhw_gasmeter 5 9 1/10 69 2
Cascade MCM10 boiler 121 nrgheat2 energy heating 2 uint24 (>=0<=1677721) kWh False sensor.boiler_energy_heating_2 sensor.boiler_nrgheat2 5 0 1/10 268 2
Cascade MCM10 boiler 121 dhw.nrg2 energy 2 uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_energy_2 sensor.boiler_dhw_nrg2 5 9 1/10 71 2
Cascade MCM10 boiler 121 dhw.tapactivated turn on/off boolean True switch.boiler_dhw_turn_on/off switch.boiler_dhw_tapactivated 5 9 1 28 1
Cascade MCM10 boiler 121 dhw.settemp set temperature uint8 (>=0<=254) C False sensor.boiler_dhw_set_temperature sensor.boiler_dhw_settemp 5 9 1 29 1
Cascade MCM10 boiler 121 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_temperature number.boiler_dhw_seltemp 5 9 1 30 1
Cascade MCM10 boiler 121 dhw.seltemplow selected lower temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_lower_temperature number.boiler_dhw_seltemplow 5 9 1 31 1
Cascade MCM10 boiler 121 dhw.tempecoplus selected eco+ temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_eco+_temperature number.boiler_dhw_tempecoplus 5 9 1 32 1
Cascade MCM10 boiler 121 dhw.seltempoff selected temperature for off uint8 (>=0<=254) C False sensor.boiler_dhw_selected_temperature_for_off sensor.boiler_dhw_seltempoff 5 9 1 33 1
Cascade MCM10 boiler 121 dhw.seltempsingle single charge temperature uint8 (>=0<=254) C True number.boiler_dhw_single_charge_temperature number.boiler_dhw_seltempsingle 5 9 1 34 1
Cascade MCM10 boiler 121 dhw.solartemp solar boiler temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_solar_boiler_temperature sensor.boiler_dhw_solartemp 5 9 1/10 35 1
Cascade MCM10 boiler 121 dhw.type type enum [off|flow|buffered flow|buffer|layered buffer] False sensor.boiler_dhw_type sensor.boiler_dhw_type 5 9 1 36 1
Cascade MCM10 boiler 121 dhw.comfort comfort enum [hot|eco|intelligent] True select.boiler_dhw_comfort select.boiler_dhw_comfort 5 9 1 37 1
Cascade MCM10 boiler 121 dhw.comfort1 comfort mode enum [high comfort|eco] True select.boiler_dhw_comfort_mode select.boiler_dhw_comfort1 5 9 1 38 1
Cascade MCM10 boiler 121 dhw.flowtempoffset flow temperature offset uint8 (>=0<=100) C True number.boiler_dhw_flow_temperature_offset number.boiler_dhw_flowtempoffset 5 9 1 39 1
Cascade MCM10 boiler 121 dhw.chargeoptimization charge optimization boolean True switch.boiler_dhw_charge_optimization switch.boiler_dhw_chargeoptimization 5 9 1 40 1
Cascade MCM10 boiler 121 dhw.maxpower max power uint8 (>=0<=254) % True number.boiler_dhw_max_power number.boiler_dhw_maxpower 5 9 1 41 1
Cascade MCM10 boiler 121 dhw.maxtemp maximum temperature uint8 (>=0<=80) C True number.boiler_dhw_maximum_temperature number.boiler_dhw_maxtemp 5 9 1 42 1
Cascade MCM10 boiler 121 dhw.circpump circulation pump available boolean True switch.boiler_dhw_circulation_pump_available switch.boiler_dhw_circpump 5 9 1 43 1
Cascade MCM10 boiler 121 dhw.chargetype charging type enum [chargepump|3-way valve] False sensor.boiler_dhw_charging_type sensor.boiler_dhw_chargetype 5 9 1 44 1
Cascade MCM10 boiler 121 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_on_temperature number.boiler_dhw_hyston 5 9 1 45 1
Cascade MCM10 boiler 121 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_off_temperature number.boiler_dhw_hystoff 5 9 1 46 1
Cascade MCM10 boiler 121 dhw.disinfectiontemp disinfection temperature uint8 (>=60<=80) C True number.boiler_dhw_disinfection_temperature number.boiler_dhw_disinfectiontemp 5 9 1 47 1
Cascade MCM10 boiler 121 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.boiler_dhw_circulation_pump_mode select.boiler_dhw_circmode 5 9 1 48 1
Cascade MCM10 boiler 121 dhw.circ circulation active boolean True switch.boiler_dhw_circulation_active switch.boiler_dhw_circ 5 9 1 49 1
Cascade MCM10 boiler 121 dhw.curtemp current intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_intern_temperature sensor.boiler_dhw_curtemp 5 9 1/10 50 1
Cascade MCM10 boiler 121 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_extern_temperature sensor.boiler_dhw_curtemp2 5 9 1/10 51 1
Cascade MCM10 boiler 121 dhw.curflow current tap water flow uint8 (>=0<=25) l/min False sensor.boiler_dhw_current_tap_water_flow sensor.boiler_dhw_curflow 5 9 1/10 52 1
Cascade MCM10 boiler 121 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_intern_temperature sensor.boiler_dhw_storagetemp1 5 9 1/10 53 1
Cascade MCM10 boiler 121 dhw.storagetemp2 storage extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_extern_temperature sensor.boiler_dhw_storagetemp2 5 9 1/10 54 1
Cascade MCM10 boiler 121 dhw.activated activated boolean True switch.boiler_dhw_activated switch.boiler_dhw_activated 5 9 1 55 1
Cascade MCM10 boiler 121 dhw.onetime one time charging boolean True switch.boiler_dhw_one_time_charging switch.boiler_dhw_onetime 5 9 1 56 1
Cascade MCM10 boiler 121 dhw.disinfecting disinfecting boolean True switch.boiler_dhw_disinfecting switch.boiler_dhw_disinfecting 5 9 1 57 1
Cascade MCM10 boiler 121 dhw.charging charging boolean False binary_sensor.boiler_dhw_charging binary_sensor.boiler_dhw_charging 5 9 1 58 1
Cascade MCM10 boiler 121 dhw.recharging recharging boolean False binary_sensor.boiler_dhw_recharging binary_sensor.boiler_dhw_recharging 5 9 1 59 1
Cascade MCM10 boiler 121 dhw.tempok temperature ok boolean False binary_sensor.boiler_dhw_temperature_ok binary_sensor.boiler_dhw_tempok 5 9 1 60 1
Cascade MCM10 boiler 121 dhw.active active boolean False binary_sensor.boiler_dhw_active binary_sensor.boiler_dhw_active 5 9 1 61 1
Cascade MCM10 boiler 121 dhw.3wayvalve 3-way valve active boolean False binary_sensor.boiler_dhw_3-way_valve_active binary_sensor.boiler_dhw_3wayvalve 5 9 1 62 1
Cascade MCM10 boiler 121 dhw.mixertemp mixer temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_mixer_temperature sensor.boiler_dhw_mixertemp 5 9 1/10 63 1
Cascade MCM10 boiler 121 dhw.cylmiddletemp cylinder middle temperature (TS3) uint16 (>=0<=3199) C False sensor.boiler_dhw_cylinder_middle_temperature_(TS3) sensor.boiler_dhw_cylmiddletemp 5 9 1/10 64 1
Cascade MCM10 boiler 121 dhw.starts starts uint24 (>=0<=16777214) False sensor.boiler_dhw_starts sensor.boiler_dhw_starts 5 9 1 65 2
Cascade MCM10 boiler 121 dhw.workm active time time (>=0<=16777214) minutes False sensor.boiler_dhw_active_time sensor.boiler_dhw_workm 5 9 1 67 2
Cascade MCM10 boiler 121 nompower nominal Power uint8 (>=0<=254) kW True number.boiler_nominal_Power number.boiler_nompower 5 0 1 270 1
Cascade MCM10 boiler 121 nrgtotal total energy uint24 (>=0<=167772) kWh False sensor.boiler_total_energy sensor.boiler_nrgtotal 5 0 1/100 83 2
Cascade MCM10 boiler 121 nrgheat energy heating uint24 (>=0<=10000000) kWh True number.boiler_energy_heating number.boiler_nrgheat 5 0 1/100 85 2
Cascade MCM10 boiler 121 dhw.nrg energy uint24 (>=0<=10000000) kWh True number.boiler_dhw_energy number.boiler_dhw_nrg 5 9 1/100 0 2
Proline boiler 122 reset reset cmd [-|maintenance|error|history|message] True sensor.boiler_reset sensor.boiler_reset 5 0 1 0 1
Proline boiler 122 heatingoff force heating off boolean True switch.boiler_force_heating_off switch.boiler_heatingoff 5 0 1 1 1
Proline boiler 122 heatingactive heating active boolean False binary_sensor.boiler_heating_active binary_sensor.boiler_heatingactive 5 0 1 2 1
Proline boiler 122 tapwateractive tapwater active boolean False binary_sensor.boiler_tapwater_active binary_sensor.boiler_tapwateractive 5 0 1 3 1
Proline boiler 122 selflowtemp selected flow temperature uint8 (>=0<=90) C True number.boiler_selected_flow_temperature number.boiler_selflowtemp 5 0 1 4 1
Proline boiler 122 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.boiler_heating_pump_modulation sensor.boiler_heatingpumpmod 5 0 1 5 1
Proline boiler 122 outdoortemp outside temperature int16 (>=-3199<=3199) C False sensor.boiler_outside_temperature sensor.boiler_outdoortemp 5 0 1/10 6 1
Proline boiler 122 curflowtemp current flow temperature uint16 (>=0<=3199) C False sensor.boiler_current_flow_temperature sensor.boiler_curflowtemp 5 0 1/10 7 1
Proline boiler 122 rettemp return temperature uint16 (>=0<=3199) C False sensor.boiler_return_temperature sensor.boiler_rettemp 5 0 1/10 8 1
Proline boiler 122 switchtemp mixing switch temperature uint16 (>=0<=3199) C False sensor.boiler_mixing_switch_temperature sensor.boiler_switchtemp 5 0 1/10 9 1
Proline boiler 122 syspress system pressure uint8 (>=0<=25) bar False sensor.boiler_system_pressure sensor.boiler_syspress 5 0 1/10 10 1
Proline boiler 122 boiltemp actual boiler temperature uint16 (>=0<=3199) C False sensor.boiler_actual_boiler_temperature sensor.boiler_boiltemp 5 0 1/10 11 1
Proline boiler 122 headertemp low loss header uint16 (>=0<=3199) C False sensor.boiler_low_loss_header sensor.boiler_headertemp 5 0 1/10 12 1
Proline boiler 122 exhausttemp exhaust temperature uint16 (>=0<=3199) C False sensor.boiler_exhaust_temperature sensor.boiler_exhausttemp 5 0 1/10 244 1
Proline boiler 122 burngas gas boolean False binary_sensor.boiler_gas binary_sensor.boiler_burngas 5 0 1 245 1
Proline boiler 122 burngas2 gas stage 2 boolean False binary_sensor.boiler_gas_stage_2 binary_sensor.boiler_burngas2 5 0 1 246 1
Proline boiler 122 flamecurr flame current uint16 (>=0<=3199) µA False sensor.boiler_flame_current sensor.boiler_flamecurr 5 0 1/10 247 1
Proline boiler 122 fanwork fan boolean False binary_sensor.boiler_fan binary_sensor.boiler_fanwork 5 0 1 248 1
Proline boiler 122 ignwork ignition boolean False binary_sensor.boiler_ignition binary_sensor.boiler_ignwork 5 0 1 249 1
Proline boiler 122 oilpreheat oil preheating boolean False binary_sensor.boiler_oil_preheating binary_sensor.boiler_oilpreheat 5 0 1 250 1
Proline boiler 122 burnminpower burner min power uint8 (>=0<=100) % True number.boiler_burner_min_power number.boiler_burnminpower 5 0 1 251 1
Proline boiler 122 burnmaxpower burner max power uint8 (>=0<=254) % True number.boiler_burner_max_power number.boiler_burnmaxpower 5 0 1 252 1
Proline boiler 122 burnminperiod burner min period uint8 (>=0<=120) minutes True number.boiler_burner_min_period number.boiler_burnminperiod 5 0 1 253 1
Proline boiler 122 absburnpow burner current power (absolute) uint8 (>=0<=100) % False sensor.boiler_burner_current_power_(absolute) sensor.boiler_absburnpow 5 0 1 254 1
Proline boiler 122 heatblock heating block uint16 (>=0<=3199) C False sensor.boiler_heating_block sensor.boiler_heatblock 5 0 1/10 255 1
Proline boiler 122 boilhyston hysteresis on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_on_temperature number.boiler_boilhyston 5 0 1 256 1
Proline boiler 122 boilhystoff hysteresis off temperature int8 (>=0<=20) C True number.boiler_hysteresis_off_temperature number.boiler_boilhystoff 5 0 1 257 1
Proline boiler 122 boil2hyston hysteresis stage 2 on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_stage_2_on_temperature number.boiler_boil2hyston 5 0 1 258 1
Proline boiler 122 boil2hystoff hysteresis stage 2 off temperature int8 (>=0<=20) C True number.boiler_hysteresis_stage_2_off_temperature number.boiler_boil2hystoff 5 0 1 259 1
Proline boiler 122 curveon heatingcurve on boolean True switch.boiler_heatingcurve_on switch.boiler_curveon 5 0 1 260 1
Proline boiler 122 curvebase heatingcurve base uint8 (>=20<=90) C True number.boiler_heatingcurve_base number.boiler_curvebase 5 0 1 261 1
Proline boiler 122 curveend heatingcurve end uint8 (>=20<=90) C True number.boiler_heatingcurve_end number.boiler_curveend 5 0 1 262 1
Proline boiler 122 summertemp summer temperature uint8 (>=0<=45) C True number.boiler_summer_temperature number.boiler_summertemp 5 0 1 263 1
Proline boiler 122 nofrostmode nofrost mode boolean True switch.boiler_nofrost_mode switch.boiler_nofrostmode 5 0 1 264 1
Proline boiler 122 nofrosttemp nofrost temperature uint8 (>=0<=10) C True number.boiler_nofrost_temperature number.boiler_nofrosttemp 5 0 1 265 1
Proline boiler 122 heatingactivated heating activated boolean True switch.boiler_heating_activated switch.boiler_heatingactivated 5 0 1 13 1
Proline boiler 122 heatingtemp heating temperature uint8 (>=0<=90) C True number.boiler_heating_temperature number.boiler_heatingtemp 5 0 1 14 1
Proline boiler 122 heatingpump heating pump boolean False binary_sensor.boiler_heating_pump binary_sensor.boiler_heatingpump 5 0 1 15 1
Proline boiler 122 pumpmodmax boiler pump max power uint8 (>=0<=100) % True number.boiler_boiler_pump_max_power number.boiler_pumpmodmax 5 0 1 16 1
Proline boiler 122 pumpmodmin boiler pump min power uint8 (>=0<=100) % True number.boiler_boiler_pump_min_power number.boiler_pumpmodmin 5 0 1 17 1
Proline boiler 122 pumpmode boiler pump mode enum [proportional|deltaP-1|deltaP-2|deltaP-3|deltaP-4] True select.boiler_boiler_pump_mode select.boiler_pumpmode 5 0 1 18 1
Proline boiler 122 pumpcharacter boiler pump characteristic enum [proportional|150mbar|200mbar|250mbar|300mbar|350mbar|400mbar] True select.boiler_boiler_pump_characteristic select.boiler_pumpcharacter 5 0 1 19 1
Proline boiler 122 pumpdelay pump delay uint8 (>=0<=60) minutes True number.boiler_pump_delay number.boiler_pumpdelay 5 0 1 20 1
Proline boiler 122 pumpontemp pump logic temperature uint8 (>=0<=60) C True number.boiler_pump_logic_temperature number.boiler_pumpontemp 5 0 1 21 1
Proline boiler 122 selburnpow burner selected max power uint8 (>=0<=254) % True number.boiler_burner_selected_max_power number.boiler_selburnpow 5 0 1 22 1
Proline boiler 122 curburnpow burner current power uint8 (>=0<=100) % False sensor.boiler_burner_current_power sensor.boiler_curburnpow 5 0 1 23 1
Proline boiler 122 burnstarts burner starts uint24 (>=0<=16777214) False sensor.boiler_burner_starts sensor.boiler_burnstarts 5 0 1 24 2
Proline boiler 122 burnworkmin total burner operating time time (>=0<=16777214) minutes False sensor.boiler_total_burner_operating_time sensor.boiler_burnworkmin 5 0 1 26 2
Proline boiler 122 burn2workmin burner stage 2 operating time time (>=0<=16777214) minutes False sensor.boiler_burner_stage_2_operating_time sensor.boiler_burn2workmin 5 0 1 28 2
Proline boiler 122 heatworkmin total heat operating time time (>=0<=16777214) minutes False sensor.boiler_total_heat_operating_time sensor.boiler_heatworkmin 5 0 1 30 2
Proline boiler 122 heatstarts burner starts heating uint24 (>=0<=16777214) False sensor.boiler_burner_starts_heating sensor.boiler_heatstarts 5 0 1 32 2
Proline boiler 122 ubauptime total UBA operating time time (>=0<=16777214) minutes False sensor.boiler_total_UBA_operating_time sensor.boiler_ubauptime 5 0 1 34 2
Proline boiler 122 lastcode last error code string False sensor.boiler_last_error_code sensor.boiler_lastcode 5 0 1 36 28
Proline boiler 122 servicecode service code string False sensor.boiler_service_code sensor.boiler_servicecode 5 0 1 64 2
Proline boiler 122 servicecodenumber service code number uint16 (>=0<=31999) False sensor.boiler_service_code_number sensor.boiler_servicecodenumber 5 0 1 66 1
Proline boiler 122 maintenancemessage maintenance message string False sensor.boiler_maintenance_message sensor.boiler_maintenancemessage 5 0 1 67 2
Proline boiler 122 maintenance maintenance scheduled enum [off|time|date|manual] True select.boiler_maintenance_scheduled select.boiler_maintenance 5 0 1 69 1
Proline boiler 122 maintenancetime time to next maintenance uint16 (>=0<=31999) hours True number.boiler_time_to_next_maintenance number.boiler_maintenancetime 5 0 1 70 1
Proline boiler 122 maintenancedate next maintenance date string True sensor.boiler_next_maintenance_date sensor.boiler_maintenancedate 5 0 1 71 6
Proline boiler 122 emergencyops emergency operation boolean True switch.boiler_emergency_operation switch.boiler_emergencyops 5 0 1 77 1
Proline boiler 122 emergencytemp emergency temperature uint8 (>=15<=70) C True number.boiler_emergency_temperature number.boiler_emergencytemp 5 0 1 78 1
Proline boiler 122 pc0flow Flow PC0 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC0 sensor.boiler_pc0flow 5 0 1 79 1
Proline boiler 122 pc1flow Flow PC1 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC1 sensor.boiler_pc1flow 5 0 1 80 1
Proline boiler 122 pc1on PC1 boolean False binary_sensor.boiler_PC1 binary_sensor.boiler_pc1on 5 0 1 81 1
Proline boiler 122 pc1rate PC1 rate uint8 (>=0<=100) % False sensor.boiler_PC1_rate sensor.boiler_pc1rate 5 0 1 82 1
Proline boiler 122 meterheat meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_meter_heating sensor.boiler_meterheat 5 0 1/10 95 2
Proline boiler 122 dhw.meter meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_meter sensor.boiler_dhw_meter 5 9 1/10 2 2
Proline boiler 122 gasmeterheat gas meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_gas_meter_heating sensor.boiler_gasmeterheat 5 0 1/10 266 2
Proline boiler 122 dhw.gasmeter gas meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_gas_meter sensor.boiler_dhw_gasmeter 5 9 1/10 69 2
Proline boiler 122 nrgheat2 energy heating 2 uint24 (>=0<=1677721) kWh False sensor.boiler_energy_heating_2 sensor.boiler_nrgheat2 5 0 1/10 268 2
Proline boiler 122 dhw.nrg2 energy 2 uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_energy_2 sensor.boiler_dhw_nrg2 5 9 1/10 71 2
Proline boiler 122 dhw.tapactivated turn on/off boolean True switch.boiler_dhw_turn_on/off switch.boiler_dhw_tapactivated 5 9 1 28 1
Proline boiler 122 dhw.settemp set temperature uint8 (>=0<=254) C False sensor.boiler_dhw_set_temperature sensor.boiler_dhw_settemp 5 9 1 29 1
Proline boiler 122 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_temperature number.boiler_dhw_seltemp 5 9 1 30 1
Proline boiler 122 dhw.seltemplow selected lower temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_lower_temperature number.boiler_dhw_seltemplow 5 9 1 31 1
Proline boiler 122 dhw.tempecoplus selected eco+ temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_eco+_temperature number.boiler_dhw_tempecoplus 5 9 1 32 1
Proline boiler 122 dhw.seltempoff selected temperature for off uint8 (>=0<=254) C False sensor.boiler_dhw_selected_temperature_for_off sensor.boiler_dhw_seltempoff 5 9 1 33 1
Proline boiler 122 dhw.seltempsingle single charge temperature uint8 (>=0<=254) C True number.boiler_dhw_single_charge_temperature number.boiler_dhw_seltempsingle 5 9 1 34 1
Proline boiler 122 dhw.solartemp solar boiler temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_solar_boiler_temperature sensor.boiler_dhw_solartemp 5 9 1/10 35 1
Proline boiler 122 dhw.type type enum [off|flow|buffered flow|buffer|layered buffer] False sensor.boiler_dhw_type sensor.boiler_dhw_type 5 9 1 36 1
Proline boiler 122 dhw.comfort comfort enum [hot|eco|intelligent] True select.boiler_dhw_comfort select.boiler_dhw_comfort 5 9 1 37 1
Proline boiler 122 dhw.comfort1 comfort mode enum [high comfort|eco] True select.boiler_dhw_comfort_mode select.boiler_dhw_comfort1 5 9 1 38 1
Proline boiler 122 dhw.flowtempoffset flow temperature offset uint8 (>=0<=100) C True number.boiler_dhw_flow_temperature_offset number.boiler_dhw_flowtempoffset 5 9 1 39 1
Proline boiler 122 dhw.chargeoptimization charge optimization boolean True switch.boiler_dhw_charge_optimization switch.boiler_dhw_chargeoptimization 5 9 1 40 1
Proline boiler 122 dhw.maxpower max power uint8 (>=0<=254) % True number.boiler_dhw_max_power number.boiler_dhw_maxpower 5 9 1 41 1
Proline boiler 122 dhw.maxtemp maximum temperature uint8 (>=0<=80) C True number.boiler_dhw_maximum_temperature number.boiler_dhw_maxtemp 5 9 1 42 1
Proline boiler 122 dhw.circpump circulation pump available boolean True switch.boiler_dhw_circulation_pump_available switch.boiler_dhw_circpump 5 9 1 43 1
Proline boiler 122 dhw.chargetype charging type enum [chargepump|3-way valve] False sensor.boiler_dhw_charging_type sensor.boiler_dhw_chargetype 5 9 1 44 1
Proline boiler 122 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_on_temperature number.boiler_dhw_hyston 5 9 1 45 1
Proline boiler 122 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_off_temperature number.boiler_dhw_hystoff 5 9 1 46 1
Proline boiler 122 dhw.disinfectiontemp disinfection temperature uint8 (>=60<=80) C True number.boiler_dhw_disinfection_temperature number.boiler_dhw_disinfectiontemp 5 9 1 47 1
Proline boiler 122 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.boiler_dhw_circulation_pump_mode select.boiler_dhw_circmode 5 9 1 48 1
Proline boiler 122 dhw.circ circulation active boolean True switch.boiler_dhw_circulation_active switch.boiler_dhw_circ 5 9 1 49 1
Proline boiler 122 dhw.curtemp current intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_intern_temperature sensor.boiler_dhw_curtemp 5 9 1/10 50 1
Proline boiler 122 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_extern_temperature sensor.boiler_dhw_curtemp2 5 9 1/10 51 1
Proline boiler 122 dhw.curflow current tap water flow uint8 (>=0<=25) l/min False sensor.boiler_dhw_current_tap_water_flow sensor.boiler_dhw_curflow 5 9 1/10 52 1
Proline boiler 122 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_intern_temperature sensor.boiler_dhw_storagetemp1 5 9 1/10 53 1
Proline boiler 122 dhw.storagetemp2 storage extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_extern_temperature sensor.boiler_dhw_storagetemp2 5 9 1/10 54 1
Proline boiler 122 dhw.activated activated boolean True switch.boiler_dhw_activated switch.boiler_dhw_activated 5 9 1 55 1
Proline boiler 122 dhw.onetime one time charging boolean True switch.boiler_dhw_one_time_charging switch.boiler_dhw_onetime 5 9 1 56 1
Proline boiler 122 dhw.disinfecting disinfecting boolean True switch.boiler_dhw_disinfecting switch.boiler_dhw_disinfecting 5 9 1 57 1
Proline boiler 122 dhw.charging charging boolean False binary_sensor.boiler_dhw_charging binary_sensor.boiler_dhw_charging 5 9 1 58 1
Proline boiler 122 dhw.recharging recharging boolean False binary_sensor.boiler_dhw_recharging binary_sensor.boiler_dhw_recharging 5 9 1 59 1
Proline boiler 122 dhw.tempok temperature ok boolean False binary_sensor.boiler_dhw_temperature_ok binary_sensor.boiler_dhw_tempok 5 9 1 60 1
Proline boiler 122 dhw.active active boolean False binary_sensor.boiler_dhw_active binary_sensor.boiler_dhw_active 5 9 1 61 1
Proline boiler 122 dhw.3wayvalve 3-way valve active boolean False binary_sensor.boiler_dhw_3-way_valve_active binary_sensor.boiler_dhw_3wayvalve 5 9 1 62 1
Proline boiler 122 dhw.mixertemp mixer temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_mixer_temperature sensor.boiler_dhw_mixertemp 5 9 1/10 63 1
Proline boiler 122 dhw.cylmiddletemp cylinder middle temperature (TS3) uint16 (>=0<=3199) C False sensor.boiler_dhw_cylinder_middle_temperature_(TS3) sensor.boiler_dhw_cylmiddletemp 5 9 1/10 64 1
Proline boiler 122 dhw.starts starts uint24 (>=0<=16777214) False sensor.boiler_dhw_starts sensor.boiler_dhw_starts 5 9 1 65 2
Proline boiler 122 dhw.workm active time time (>=0<=16777214) minutes False sensor.boiler_dhw_active_time sensor.boiler_dhw_workm 5 9 1 67 2
Proline boiler 122 nompower nominal Power uint8 (>=0<=254) kW True number.boiler_nominal_Power number.boiler_nompower 5 0 1 270 1
Proline boiler 122 nrgtotal total energy uint24 (>=0<=167772) kWh False sensor.boiler_total_energy sensor.boiler_nrgtotal 5 0 1/100 83 2
Proline boiler 122 nrgheat energy heating uint24 (>=0<=10000000) kWh True number.boiler_energy_heating number.boiler_nrgheat 5 0 1/100 85 2
Proline boiler 122 dhw.nrg energy uint24 (>=0<=10000000) kWh True number.boiler_dhw_energy number.boiler_dhw_nrg 5 9 1/100 0 2
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 reset reset cmd [-|maintenance|error|history|message] True sensor.boiler_reset sensor.boiler_reset 5 0 1 0 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 heatingoff force heating off boolean True switch.boiler_force_heating_off switch.boiler_heatingoff 5 0 1 1 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 heatingactive heating active boolean False binary_sensor.boiler_heating_active binary_sensor.boiler_heatingactive 5 0 1 2 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 tapwateractive tapwater active boolean False binary_sensor.boiler_tapwater_active binary_sensor.boiler_tapwateractive 5 0 1 3 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 selflowtemp selected flow temperature uint8 (>=0<=90) C True number.boiler_selected_flow_temperature number.boiler_selflowtemp 5 0 1 4 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.boiler_heating_pump_modulation sensor.boiler_heatingpumpmod 5 0 1 5 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 outdoortemp outside temperature int16 (>=-3199<=3199) C False sensor.boiler_outside_temperature sensor.boiler_outdoortemp 5 0 1/10 6 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 curflowtemp current flow temperature uint16 (>=0<=3199) C False sensor.boiler_current_flow_temperature sensor.boiler_curflowtemp 5 0 1/10 7 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 rettemp return temperature uint16 (>=0<=3199) C False sensor.boiler_return_temperature sensor.boiler_rettemp 5 0 1/10 8 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 switchtemp mixing switch temperature uint16 (>=0<=3199) C False sensor.boiler_mixing_switch_temperature sensor.boiler_switchtemp 5 0 1/10 9 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 syspress system pressure uint8 (>=0<=25) bar False sensor.boiler_system_pressure sensor.boiler_syspress 5 0 1/10 10 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 boiltemp actual boiler temperature uint16 (>=0<=3199) C False sensor.boiler_actual_boiler_temperature sensor.boiler_boiltemp 5 0 1/10 11 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 headertemp low loss header uint16 (>=0<=3199) C False sensor.boiler_low_loss_header sensor.boiler_headertemp 5 0 1/10 12 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 exhausttemp exhaust temperature uint16 (>=0<=3199) C False sensor.boiler_exhaust_temperature sensor.boiler_exhausttemp 5 0 1/10 244 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 burngas gas boolean False binary_sensor.boiler_gas binary_sensor.boiler_burngas 5 0 1 245 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 burngas2 gas stage 2 boolean False binary_sensor.boiler_gas_stage_2 binary_sensor.boiler_burngas2 5 0 1 246 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 flamecurr flame current uint16 (>=0<=3199) µA False sensor.boiler_flame_current sensor.boiler_flamecurr 5 0 1/10 247 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 fanwork fan boolean False binary_sensor.boiler_fan binary_sensor.boiler_fanwork 5 0 1 248 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 ignwork ignition boolean False binary_sensor.boiler_ignition binary_sensor.boiler_ignwork 5 0 1 249 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 oilpreheat oil preheating boolean False binary_sensor.boiler_oil_preheating binary_sensor.boiler_oilpreheat 5 0 1 250 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 burnminpower burner min power uint8 (>=0<=100) % True number.boiler_burner_min_power number.boiler_burnminpower 5 0 1 251 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 burnmaxpower burner max power uint8 (>=0<=254) % True number.boiler_burner_max_power number.boiler_burnmaxpower 5 0 1 252 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 burnminperiod burner min period uint8 (>=0<=120) minutes True number.boiler_burner_min_period number.boiler_burnminperiod 5 0 1 253 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 absburnpow burner current power (absolute) uint8 (>=0<=100) % False sensor.boiler_burner_current_power_(absolute) sensor.boiler_absburnpow 5 0 1 254 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 heatblock heating block uint16 (>=0<=3199) C False sensor.boiler_heating_block sensor.boiler_heatblock 5 0 1/10 255 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 boilhyston hysteresis on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_on_temperature number.boiler_boilhyston 5 0 1 256 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 boilhystoff hysteresis off temperature int8 (>=0<=20) C True number.boiler_hysteresis_off_temperature number.boiler_boilhystoff 5 0 1 257 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 boil2hyston hysteresis stage 2 on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_stage_2_on_temperature number.boiler_boil2hyston 5 0 1 258 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 boil2hystoff hysteresis stage 2 off temperature int8 (>=0<=20) C True number.boiler_hysteresis_stage_2_off_temperature number.boiler_boil2hystoff 5 0 1 259 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 curveon heatingcurve on boolean True switch.boiler_heatingcurve_on switch.boiler_curveon 5 0 1 260 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 curvebase heatingcurve base uint8 (>=20<=90) C True number.boiler_heatingcurve_base number.boiler_curvebase 5 0 1 261 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 curveend heatingcurve end uint8 (>=20<=90) C True number.boiler_heatingcurve_end number.boiler_curveend 5 0 1 262 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 summertemp summer temperature uint8 (>=0<=45) C True number.boiler_summer_temperature number.boiler_summertemp 5 0 1 263 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 nofrostmode nofrost mode boolean True switch.boiler_nofrost_mode switch.boiler_nofrostmode 5 0 1 264 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 nofrosttemp nofrost temperature uint8 (>=0<=10) C True number.boiler_nofrost_temperature number.boiler_nofrosttemp 5 0 1 265 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 heatingactivated heating activated boolean True switch.boiler_heating_activated switch.boiler_heatingactivated 5 0 1 13 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 heatingtemp heating temperature uint8 (>=0<=90) C True number.boiler_heating_temperature number.boiler_heatingtemp 5 0 1 14 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 heatingpump heating pump boolean False binary_sensor.boiler_heating_pump binary_sensor.boiler_heatingpump 5 0 1 15 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 pumpmodmax boiler pump max power uint8 (>=0<=100) % True number.boiler_boiler_pump_max_power number.boiler_pumpmodmax 5 0 1 16 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 pumpmodmin boiler pump min power uint8 (>=0<=100) % True number.boiler_boiler_pump_min_power number.boiler_pumpmodmin 5 0 1 17 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 pumpmode boiler pump mode enum [proportional|deltaP-1|deltaP-2|deltaP-3|deltaP-4] True select.boiler_boiler_pump_mode select.boiler_pumpmode 5 0 1 18 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 pumpcharacter boiler pump characteristic enum [proportional|150mbar|200mbar|250mbar|300mbar|350mbar|400mbar] True select.boiler_boiler_pump_characteristic select.boiler_pumpcharacter 5 0 1 19 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 pumpdelay pump delay uint8 (>=0<=60) minutes True number.boiler_pump_delay number.boiler_pumpdelay 5 0 1 20 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 pumpontemp pump logic temperature uint8 (>=0<=60) C True number.boiler_pump_logic_temperature number.boiler_pumpontemp 5 0 1 21 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 selburnpow burner selected max power uint8 (>=0<=254) % True number.boiler_burner_selected_max_power number.boiler_selburnpow 5 0 1 22 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 curburnpow burner current power uint8 (>=0<=100) % False sensor.boiler_burner_current_power sensor.boiler_curburnpow 5 0 1 23 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 burnstarts burner starts uint24 (>=0<=16777214) False sensor.boiler_burner_starts sensor.boiler_burnstarts 5 0 1 24 2
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 burnworkmin total burner operating time time (>=0<=16777214) minutes False sensor.boiler_total_burner_operating_time sensor.boiler_burnworkmin 5 0 1 26 2
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 burn2workmin burner stage 2 operating time time (>=0<=16777214) minutes False sensor.boiler_burner_stage_2_operating_time sensor.boiler_burn2workmin 5 0 1 28 2
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 heatworkmin total heat operating time time (>=0<=16777214) minutes False sensor.boiler_total_heat_operating_time sensor.boiler_heatworkmin 5 0 1 30 2
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 heatstarts burner starts heating uint24 (>=0<=16777214) False sensor.boiler_burner_starts_heating sensor.boiler_heatstarts 5 0 1 32 2
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 ubauptime total UBA operating time time (>=0<=16777214) minutes False sensor.boiler_total_UBA_operating_time sensor.boiler_ubauptime 5 0 1 34 2
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 lastcode last error code string False sensor.boiler_last_error_code sensor.boiler_lastcode 5 0 1 36 28
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 servicecode service code string False sensor.boiler_service_code sensor.boiler_servicecode 5 0 1 64 2
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 servicecodenumber service code number uint16 (>=0<=31999) False sensor.boiler_service_code_number sensor.boiler_servicecodenumber 5 0 1 66 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 maintenancemessage maintenance message string False sensor.boiler_maintenance_message sensor.boiler_maintenancemessage 5 0 1 67 2
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 maintenance maintenance scheduled enum [off|time|date|manual] True select.boiler_maintenance_scheduled select.boiler_maintenance 5 0 1 69 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 maintenancetime time to next maintenance uint16 (>=0<=31999) hours True number.boiler_time_to_next_maintenance number.boiler_maintenancetime 5 0 1 70 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 maintenancedate next maintenance date string True sensor.boiler_next_maintenance_date sensor.boiler_maintenancedate 5 0 1 71 6
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 emergencyops emergency operation boolean True switch.boiler_emergency_operation switch.boiler_emergencyops 5 0 1 77 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 emergencytemp emergency temperature uint8 (>=15<=70) C True number.boiler_emergency_temperature number.boiler_emergencytemp 5 0 1 78 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 pc0flow Flow PC0 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC0 sensor.boiler_pc0flow 5 0 1 79 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 pc1flow Flow PC1 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC1 sensor.boiler_pc1flow 5 0 1 80 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 pc1on PC1 boolean False binary_sensor.boiler_PC1 binary_sensor.boiler_pc1on 5 0 1 81 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 pc1rate PC1 rate uint8 (>=0<=100) % False sensor.boiler_PC1_rate sensor.boiler_pc1rate 5 0 1 82 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 meterheat meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_meter_heating sensor.boiler_meterheat 5 0 1/10 95 2
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.meter meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_meter sensor.boiler_dhw_meter 5 9 1/10 2 2
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 gasmeterheat gas meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_gas_meter_heating sensor.boiler_gasmeterheat 5 0 1/10 266 2
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.gasmeter gas meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_gas_meter sensor.boiler_dhw_gasmeter 5 9 1/10 69 2
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 nrgheat2 energy heating 2 uint24 (>=0<=1677721) kWh False sensor.boiler_energy_heating_2 sensor.boiler_nrgheat2 5 0 1/10 268 2
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.nrg2 energy 2 uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_energy_2 sensor.boiler_dhw_nrg2 5 9 1/10 71 2
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.tapactivated turn on/off boolean True switch.boiler_dhw_turn_on/off switch.boiler_dhw_tapactivated 5 9 1 28 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.settemp set temperature uint8 (>=0<=254) C False sensor.boiler_dhw_set_temperature sensor.boiler_dhw_settemp 5 9 1 29 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_temperature number.boiler_dhw_seltemp 5 9 1 30 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.seltemplow selected lower temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_lower_temperature number.boiler_dhw_seltemplow 5 9 1 31 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.tempecoplus selected eco+ temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_eco+_temperature number.boiler_dhw_tempecoplus 5 9 1 32 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.seltempoff selected temperature for off uint8 (>=0<=254) C False sensor.boiler_dhw_selected_temperature_for_off sensor.boiler_dhw_seltempoff 5 9 1 33 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.seltempsingle single charge temperature uint8 (>=0<=254) C True number.boiler_dhw_single_charge_temperature number.boiler_dhw_seltempsingle 5 9 1 34 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.solartemp solar boiler temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_solar_boiler_temperature sensor.boiler_dhw_solartemp 5 9 1/10 35 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.type type enum [off|flow|buffered flow|buffer|layered buffer] False sensor.boiler_dhw_type sensor.boiler_dhw_type 5 9 1 36 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.comfort comfort enum [hot|eco|intelligent] True select.boiler_dhw_comfort select.boiler_dhw_comfort 5 9 1 37 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.comfort1 comfort mode enum [high comfort|eco] True select.boiler_dhw_comfort_mode select.boiler_dhw_comfort1 5 9 1 38 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.flowtempoffset flow temperature offset uint8 (>=0<=100) C True number.boiler_dhw_flow_temperature_offset number.boiler_dhw_flowtempoffset 5 9 1 39 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.chargeoptimization charge optimization boolean True switch.boiler_dhw_charge_optimization switch.boiler_dhw_chargeoptimization 5 9 1 40 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.maxpower max power uint8 (>=0<=254) % True number.boiler_dhw_max_power number.boiler_dhw_maxpower 5 9 1 41 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.maxtemp maximum temperature uint8 (>=0<=80) C True number.boiler_dhw_maximum_temperature number.boiler_dhw_maxtemp 5 9 1 42 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.circpump circulation pump available boolean True switch.boiler_dhw_circulation_pump_available switch.boiler_dhw_circpump 5 9 1 43 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.chargetype charging type enum [chargepump|3-way valve] False sensor.boiler_dhw_charging_type sensor.boiler_dhw_chargetype 5 9 1 44 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_on_temperature number.boiler_dhw_hyston 5 9 1 45 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_off_temperature number.boiler_dhw_hystoff 5 9 1 46 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.disinfectiontemp disinfection temperature uint8 (>=60<=80) C True number.boiler_dhw_disinfection_temperature number.boiler_dhw_disinfectiontemp 5 9 1 47 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.boiler_dhw_circulation_pump_mode select.boiler_dhw_circmode 5 9 1 48 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.circ circulation active boolean True switch.boiler_dhw_circulation_active switch.boiler_dhw_circ 5 9 1 49 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.curtemp current intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_intern_temperature sensor.boiler_dhw_curtemp 5 9 1/10 50 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_extern_temperature sensor.boiler_dhw_curtemp2 5 9 1/10 51 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.curflow current tap water flow uint8 (>=0<=25) l/min False sensor.boiler_dhw_current_tap_water_flow sensor.boiler_dhw_curflow 5 9 1/10 52 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_intern_temperature sensor.boiler_dhw_storagetemp1 5 9 1/10 53 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.storagetemp2 storage extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_extern_temperature sensor.boiler_dhw_storagetemp2 5 9 1/10 54 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.activated activated boolean True switch.boiler_dhw_activated switch.boiler_dhw_activated 5 9 1 55 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.onetime one time charging boolean True switch.boiler_dhw_one_time_charging switch.boiler_dhw_onetime 5 9 1 56 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.disinfecting disinfecting boolean True switch.boiler_dhw_disinfecting switch.boiler_dhw_disinfecting 5 9 1 57 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.charging charging boolean False binary_sensor.boiler_dhw_charging binary_sensor.boiler_dhw_charging 5 9 1 58 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.recharging recharging boolean False binary_sensor.boiler_dhw_recharging binary_sensor.boiler_dhw_recharging 5 9 1 59 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.tempok temperature ok boolean False binary_sensor.boiler_dhw_temperature_ok binary_sensor.boiler_dhw_tempok 5 9 1 60 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.active active boolean False binary_sensor.boiler_dhw_active binary_sensor.boiler_dhw_active 5 9 1 61 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.3wayvalve 3-way valve active boolean False binary_sensor.boiler_dhw_3-way_valve_active binary_sensor.boiler_dhw_3wayvalve 5 9 1 62 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.mixertemp mixer temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_mixer_temperature sensor.boiler_dhw_mixertemp 5 9 1/10 63 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.cylmiddletemp cylinder middle temperature (TS3) uint16 (>=0<=3199) C False sensor.boiler_dhw_cylinder_middle_temperature_(TS3) sensor.boiler_dhw_cylmiddletemp 5 9 1/10 64 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.starts starts uint24 (>=0<=16777214) False sensor.boiler_dhw_starts sensor.boiler_dhw_starts 5 9 1 65 2
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.workm active time time (>=0<=16777214) minutes False sensor.boiler_dhw_active_time sensor.boiler_dhw_workm 5 9 1 67 2
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 nompower nominal Power uint8 (>=0<=254) kW True number.boiler_nominal_Power number.boiler_nompower 5 0 1 270 1
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 nrgtotal total energy uint24 (>=0<=167772) kWh False sensor.boiler_total_energy sensor.boiler_nrgtotal 5 0 1/100 83 2
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 nrgheat energy heating uint24 (>=0<=10000000) kWh True number.boiler_energy_heating number.boiler_nrgheat 5 0 1/100 85 2
GB*72, Trendline, Cerapur, Greenstar Si boiler 123 dhw.nrg energy uint24 (>=0<=10000000) kWh True number.boiler_dhw_energy number.boiler_dhw_nrg 5 9 1/100 0 2
GB212 boiler 131 reset reset cmd [-|maintenance|error|history|message] True sensor.boiler_reset sensor.boiler_reset 5 0 1 0 1
GB212 boiler 131 heatingoff force heating off boolean True switch.boiler_force_heating_off switch.boiler_heatingoff 5 0 1 1 1
GB212 boiler 131 heatingactive heating active boolean False binary_sensor.boiler_heating_active binary_sensor.boiler_heatingactive 5 0 1 2 1
GB212 boiler 131 tapwateractive tapwater active boolean False binary_sensor.boiler_tapwater_active binary_sensor.boiler_tapwateractive 5 0 1 3 1
GB212 boiler 131 selflowtemp selected flow temperature uint8 (>=0<=90) C True number.boiler_selected_flow_temperature number.boiler_selflowtemp 5 0 1 4 1
GB212 boiler 131 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.boiler_heating_pump_modulation sensor.boiler_heatingpumpmod 5 0 1 5 1
GB212 boiler 131 outdoortemp outside temperature int16 (>=-3199<=3199) C False sensor.boiler_outside_temperature sensor.boiler_outdoortemp 5 0 1/10 6 1
GB212 boiler 131 curflowtemp current flow temperature uint16 (>=0<=3199) C False sensor.boiler_current_flow_temperature sensor.boiler_curflowtemp 5 0 1/10 7 1
GB212 boiler 131 rettemp return temperature uint16 (>=0<=3199) C False sensor.boiler_return_temperature sensor.boiler_rettemp 5 0 1/10 8 1
GB212 boiler 131 switchtemp mixing switch temperature uint16 (>=0<=3199) C False sensor.boiler_mixing_switch_temperature sensor.boiler_switchtemp 5 0 1/10 9 1
GB212 boiler 131 syspress system pressure uint8 (>=0<=25) bar False sensor.boiler_system_pressure sensor.boiler_syspress 5 0 1/10 10 1
GB212 boiler 131 boiltemp actual boiler temperature uint16 (>=0<=3199) C False sensor.boiler_actual_boiler_temperature sensor.boiler_boiltemp 5 0 1/10 11 1
GB212 boiler 131 headertemp low loss header uint16 (>=0<=3199) C False sensor.boiler_low_loss_header sensor.boiler_headertemp 5 0 1/10 12 1
GB212 boiler 131 exhausttemp exhaust temperature uint16 (>=0<=3199) C False sensor.boiler_exhaust_temperature sensor.boiler_exhausttemp 5 0 1/10 244 1
GB212 boiler 131 burngas gas boolean False binary_sensor.boiler_gas binary_sensor.boiler_burngas 5 0 1 245 1
GB212 boiler 131 burngas2 gas stage 2 boolean False binary_sensor.boiler_gas_stage_2 binary_sensor.boiler_burngas2 5 0 1 246 1
GB212 boiler 131 flamecurr flame current uint16 (>=0<=3199) µA False sensor.boiler_flame_current sensor.boiler_flamecurr 5 0 1/10 247 1
GB212 boiler 131 fanwork fan boolean False binary_sensor.boiler_fan binary_sensor.boiler_fanwork 5 0 1 248 1
GB212 boiler 131 ignwork ignition boolean False binary_sensor.boiler_ignition binary_sensor.boiler_ignwork 5 0 1 249 1
GB212 boiler 131 oilpreheat oil preheating boolean False binary_sensor.boiler_oil_preheating binary_sensor.boiler_oilpreheat 5 0 1 250 1
GB212 boiler 131 burnminpower burner min power uint8 (>=0<=100) % True number.boiler_burner_min_power number.boiler_burnminpower 5 0 1 251 1
GB212 boiler 131 burnmaxpower burner max power uint8 (>=0<=254) % True number.boiler_burner_max_power number.boiler_burnmaxpower 5 0 1 252 1
GB212 boiler 131 burnminperiod burner min period uint8 (>=0<=120) minutes True number.boiler_burner_min_period number.boiler_burnminperiod 5 0 1 253 1
GB212 boiler 131 absburnpow burner current power (absolute) uint8 (>=0<=100) % False sensor.boiler_burner_current_power_(absolute) sensor.boiler_absburnpow 5 0 1 254 1
GB212 boiler 131 heatblock heating block uint16 (>=0<=3199) C False sensor.boiler_heating_block sensor.boiler_heatblock 5 0 1/10 255 1
GB212 boiler 131 boilhyston hysteresis on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_on_temperature number.boiler_boilhyston 5 0 1 256 1
GB212 boiler 131 boilhystoff hysteresis off temperature int8 (>=0<=20) C True number.boiler_hysteresis_off_temperature number.boiler_boilhystoff 5 0 1 257 1
GB212 boiler 131 boil2hyston hysteresis stage 2 on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_stage_2_on_temperature number.boiler_boil2hyston 5 0 1 258 1
GB212 boiler 131 boil2hystoff hysteresis stage 2 off temperature int8 (>=0<=20) C True number.boiler_hysteresis_stage_2_off_temperature number.boiler_boil2hystoff 5 0 1 259 1
GB212 boiler 131 curveon heatingcurve on boolean True switch.boiler_heatingcurve_on switch.boiler_curveon 5 0 1 260 1
GB212 boiler 131 curvebase heatingcurve base uint8 (>=20<=90) C True number.boiler_heatingcurve_base number.boiler_curvebase 5 0 1 261 1
GB212 boiler 131 curveend heatingcurve end uint8 (>=20<=90) C True number.boiler_heatingcurve_end number.boiler_curveend 5 0 1 262 1
GB212 boiler 131 summertemp summer temperature uint8 (>=0<=45) C True number.boiler_summer_temperature number.boiler_summertemp 5 0 1 263 1
GB212 boiler 131 nofrostmode nofrost mode boolean True switch.boiler_nofrost_mode switch.boiler_nofrostmode 5 0 1 264 1
GB212 boiler 131 nofrosttemp nofrost temperature uint8 (>=0<=10) C True number.boiler_nofrost_temperature number.boiler_nofrosttemp 5 0 1 265 1
GB212 boiler 131 heatingactivated heating activated boolean True switch.boiler_heating_activated switch.boiler_heatingactivated 5 0 1 13 1
GB212 boiler 131 heatingtemp heating temperature uint8 (>=0<=90) C True number.boiler_heating_temperature number.boiler_heatingtemp 5 0 1 14 1
GB212 boiler 131 heatingpump heating pump boolean False binary_sensor.boiler_heating_pump binary_sensor.boiler_heatingpump 5 0 1 15 1
GB212 boiler 131 pumpmodmax boiler pump max power uint8 (>=0<=100) % True number.boiler_boiler_pump_max_power number.boiler_pumpmodmax 5 0 1 16 1
GB212 boiler 131 pumpmodmin boiler pump min power uint8 (>=0<=100) % True number.boiler_boiler_pump_min_power number.boiler_pumpmodmin 5 0 1 17 1
GB212 boiler 131 pumpmode boiler pump mode enum [proportional|deltaP-1|deltaP-2|deltaP-3|deltaP-4] True select.boiler_boiler_pump_mode select.boiler_pumpmode 5 0 1 18 1
GB212 boiler 131 pumpcharacter boiler pump characteristic enum [proportional|150mbar|200mbar|250mbar|300mbar|350mbar|400mbar] True select.boiler_boiler_pump_characteristic select.boiler_pumpcharacter 5 0 1 19 1
GB212 boiler 131 pumpdelay pump delay uint8 (>=0<=60) minutes True number.boiler_pump_delay number.boiler_pumpdelay 5 0 1 20 1
GB212 boiler 131 pumpontemp pump logic temperature uint8 (>=0<=60) C True number.boiler_pump_logic_temperature number.boiler_pumpontemp 5 0 1 21 1
GB212 boiler 131 selburnpow burner selected max power uint8 (>=0<=254) % True number.boiler_burner_selected_max_power number.boiler_selburnpow 5 0 1 22 1
GB212 boiler 131 curburnpow burner current power uint8 (>=0<=100) % False sensor.boiler_burner_current_power sensor.boiler_curburnpow 5 0 1 23 1
GB212 boiler 131 burnstarts burner starts uint24 (>=0<=16777214) False sensor.boiler_burner_starts sensor.boiler_burnstarts 5 0 1 24 2
GB212 boiler 131 burnworkmin total burner operating time time (>=0<=16777214) minutes False sensor.boiler_total_burner_operating_time sensor.boiler_burnworkmin 5 0 1 26 2
GB212 boiler 131 burn2workmin burner stage 2 operating time time (>=0<=16777214) minutes False sensor.boiler_burner_stage_2_operating_time sensor.boiler_burn2workmin 5 0 1 28 2
GB212 boiler 131 heatworkmin total heat operating time time (>=0<=16777214) minutes False sensor.boiler_total_heat_operating_time sensor.boiler_heatworkmin 5 0 1 30 2
GB212 boiler 131 heatstarts burner starts heating uint24 (>=0<=16777214) False sensor.boiler_burner_starts_heating sensor.boiler_heatstarts 5 0 1 32 2
GB212 boiler 131 ubauptime total UBA operating time time (>=0<=16777214) minutes False sensor.boiler_total_UBA_operating_time sensor.boiler_ubauptime 5 0 1 34 2
GB212 boiler 131 lastcode last error code string False sensor.boiler_last_error_code sensor.boiler_lastcode 5 0 1 36 28
GB212 boiler 131 servicecode service code string False sensor.boiler_service_code sensor.boiler_servicecode 5 0 1 64 2
GB212 boiler 131 servicecodenumber service code number uint16 (>=0<=31999) False sensor.boiler_service_code_number sensor.boiler_servicecodenumber 5 0 1 66 1
GB212 boiler 131 maintenancemessage maintenance message string False sensor.boiler_maintenance_message sensor.boiler_maintenancemessage 5 0 1 67 2
GB212 boiler 131 maintenance maintenance scheduled enum [off|time|date|manual] True select.boiler_maintenance_scheduled select.boiler_maintenance 5 0 1 69 1
GB212 boiler 131 maintenancetime time to next maintenance uint16 (>=0<=31999) hours True number.boiler_time_to_next_maintenance number.boiler_maintenancetime 5 0 1 70 1
GB212 boiler 131 maintenancedate next maintenance date string True sensor.boiler_next_maintenance_date sensor.boiler_maintenancedate 5 0 1 71 6
GB212 boiler 131 emergencyops emergency operation boolean True switch.boiler_emergency_operation switch.boiler_emergencyops 5 0 1 77 1
GB212 boiler 131 emergencytemp emergency temperature uint8 (>=15<=70) C True number.boiler_emergency_temperature number.boiler_emergencytemp 5 0 1 78 1
GB212 boiler 131 pc0flow Flow PC0 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC0 sensor.boiler_pc0flow 5 0 1 79 1
GB212 boiler 131 pc1flow Flow PC1 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC1 sensor.boiler_pc1flow 5 0 1 80 1
GB212 boiler 131 pc1on PC1 boolean False binary_sensor.boiler_PC1 binary_sensor.boiler_pc1on 5 0 1 81 1
GB212 boiler 131 pc1rate PC1 rate uint8 (>=0<=100) % False sensor.boiler_PC1_rate sensor.boiler_pc1rate 5 0 1 82 1
GB212 boiler 131 meterheat meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_meter_heating sensor.boiler_meterheat 5 0 1/10 95 2
GB212 boiler 131 dhw.meter meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_meter sensor.boiler_dhw_meter 5 9 1/10 2 2
GB212 boiler 131 gasmeterheat gas meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_gas_meter_heating sensor.boiler_gasmeterheat 5 0 1/10 266 2
GB212 boiler 131 dhw.gasmeter gas meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_gas_meter sensor.boiler_dhw_gasmeter 5 9 1/10 69 2
GB212 boiler 131 nrgheat2 energy heating 2 uint24 (>=0<=1677721) kWh False sensor.boiler_energy_heating_2 sensor.boiler_nrgheat2 5 0 1/10 268 2
GB212 boiler 131 dhw.nrg2 energy 2 uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_energy_2 sensor.boiler_dhw_nrg2 5 9 1/10 71 2
GB212 boiler 131 dhw.tapactivated turn on/off boolean True switch.boiler_dhw_turn_on/off switch.boiler_dhw_tapactivated 5 9 1 28 1
GB212 boiler 131 dhw.settemp set temperature uint8 (>=0<=254) C False sensor.boiler_dhw_set_temperature sensor.boiler_dhw_settemp 5 9 1 29 1
GB212 boiler 131 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_temperature number.boiler_dhw_seltemp 5 9 1 30 1
GB212 boiler 131 dhw.seltemplow selected lower temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_lower_temperature number.boiler_dhw_seltemplow 5 9 1 31 1
GB212 boiler 131 dhw.tempecoplus selected eco+ temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_eco+_temperature number.boiler_dhw_tempecoplus 5 9 1 32 1
GB212 boiler 131 dhw.seltempoff selected temperature for off uint8 (>=0<=254) C False sensor.boiler_dhw_selected_temperature_for_off sensor.boiler_dhw_seltempoff 5 9 1 33 1
GB212 boiler 131 dhw.seltempsingle single charge temperature uint8 (>=0<=254) C True number.boiler_dhw_single_charge_temperature number.boiler_dhw_seltempsingle 5 9 1 34 1
GB212 boiler 131 dhw.solartemp solar boiler temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_solar_boiler_temperature sensor.boiler_dhw_solartemp 5 9 1/10 35 1
GB212 boiler 131 dhw.type type enum [off|flow|buffered flow|buffer|layered buffer] False sensor.boiler_dhw_type sensor.boiler_dhw_type 5 9 1 36 1
GB212 boiler 131 dhw.comfort comfort enum [hot|eco|intelligent] True select.boiler_dhw_comfort select.boiler_dhw_comfort 5 9 1 37 1
GB212 boiler 131 dhw.comfort1 comfort mode enum [high comfort|eco] True select.boiler_dhw_comfort_mode select.boiler_dhw_comfort1 5 9 1 38 1
GB212 boiler 131 dhw.flowtempoffset flow temperature offset uint8 (>=0<=100) C True number.boiler_dhw_flow_temperature_offset number.boiler_dhw_flowtempoffset 5 9 1 39 1
GB212 boiler 131 dhw.chargeoptimization charge optimization boolean True switch.boiler_dhw_charge_optimization switch.boiler_dhw_chargeoptimization 5 9 1 40 1
GB212 boiler 131 dhw.maxpower max power uint8 (>=0<=254) % True number.boiler_dhw_max_power number.boiler_dhw_maxpower 5 9 1 41 1
GB212 boiler 131 dhw.maxtemp maximum temperature uint8 (>=0<=80) C True number.boiler_dhw_maximum_temperature number.boiler_dhw_maxtemp 5 9 1 42 1
GB212 boiler 131 dhw.circpump circulation pump available boolean True switch.boiler_dhw_circulation_pump_available switch.boiler_dhw_circpump 5 9 1 43 1
GB212 boiler 131 dhw.chargetype charging type enum [chargepump|3-way valve] False sensor.boiler_dhw_charging_type sensor.boiler_dhw_chargetype 5 9 1 44 1
GB212 boiler 131 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_on_temperature number.boiler_dhw_hyston 5 9 1 45 1
GB212 boiler 131 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_off_temperature number.boiler_dhw_hystoff 5 9 1 46 1
GB212 boiler 131 dhw.disinfectiontemp disinfection temperature uint8 (>=60<=80) C True number.boiler_dhw_disinfection_temperature number.boiler_dhw_disinfectiontemp 5 9 1 47 1
GB212 boiler 131 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.boiler_dhw_circulation_pump_mode select.boiler_dhw_circmode 5 9 1 48 1
GB212 boiler 131 dhw.circ circulation active boolean True switch.boiler_dhw_circulation_active switch.boiler_dhw_circ 5 9 1 49 1
GB212 boiler 131 dhw.curtemp current intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_intern_temperature sensor.boiler_dhw_curtemp 5 9 1/10 50 1
GB212 boiler 131 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_extern_temperature sensor.boiler_dhw_curtemp2 5 9 1/10 51 1
GB212 boiler 131 dhw.curflow current tap water flow uint8 (>=0<=25) l/min False sensor.boiler_dhw_current_tap_water_flow sensor.boiler_dhw_curflow 5 9 1/10 52 1
GB212 boiler 131 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_intern_temperature sensor.boiler_dhw_storagetemp1 5 9 1/10 53 1
GB212 boiler 131 dhw.storagetemp2 storage extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_extern_temperature sensor.boiler_dhw_storagetemp2 5 9 1/10 54 1
GB212 boiler 131 dhw.activated activated boolean True switch.boiler_dhw_activated switch.boiler_dhw_activated 5 9 1 55 1
GB212 boiler 131 dhw.onetime one time charging boolean True switch.boiler_dhw_one_time_charging switch.boiler_dhw_onetime 5 9 1 56 1
GB212 boiler 131 dhw.disinfecting disinfecting boolean True switch.boiler_dhw_disinfecting switch.boiler_dhw_disinfecting 5 9 1 57 1
GB212 boiler 131 dhw.charging charging boolean False binary_sensor.boiler_dhw_charging binary_sensor.boiler_dhw_charging 5 9 1 58 1
GB212 boiler 131 dhw.recharging recharging boolean False binary_sensor.boiler_dhw_recharging binary_sensor.boiler_dhw_recharging 5 9 1 59 1
GB212 boiler 131 dhw.tempok temperature ok boolean False binary_sensor.boiler_dhw_temperature_ok binary_sensor.boiler_dhw_tempok 5 9 1 60 1
GB212 boiler 131 dhw.active active boolean False binary_sensor.boiler_dhw_active binary_sensor.boiler_dhw_active 5 9 1 61 1
GB212 boiler 131 dhw.3wayvalve 3-way valve active boolean False binary_sensor.boiler_dhw_3-way_valve_active binary_sensor.boiler_dhw_3wayvalve 5 9 1 62 1
GB212 boiler 131 dhw.mixertemp mixer temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_mixer_temperature sensor.boiler_dhw_mixertemp 5 9 1/10 63 1
GB212 boiler 131 dhw.cylmiddletemp cylinder middle temperature (TS3) uint16 (>=0<=3199) C False sensor.boiler_dhw_cylinder_middle_temperature_(TS3) sensor.boiler_dhw_cylmiddletemp 5 9 1/10 64 1
GB212 boiler 131 dhw.starts starts uint24 (>=0<=16777214) False sensor.boiler_dhw_starts sensor.boiler_dhw_starts 5 9 1 65 2
GB212 boiler 131 dhw.workm active time time (>=0<=16777214) minutes False sensor.boiler_dhw_active_time sensor.boiler_dhw_workm 5 9 1 67 2
GB212 boiler 131 nompower nominal Power uint8 (>=0<=254) kW True number.boiler_nominal_Power number.boiler_nompower 5 0 1 270 1
GB212 boiler 131 nrgtotal total energy uint24 (>=0<=167772) kWh False sensor.boiler_total_energy sensor.boiler_nrgtotal 5 0 1/100 83 2
GB212 boiler 131 nrgheat energy heating uint24 (>=0<=10000000) kWh True number.boiler_energy_heating number.boiler_nrgheat 5 0 1/100 85 2
GB212 boiler 131 dhw.nrg energy uint24 (>=0<=10000000) kWh True number.boiler_dhw_energy number.boiler_dhw_nrg 5 9 1/100 0 2
GC7000F boiler 132 reset reset cmd [-|maintenance|error|history|message] True sensor.boiler_reset sensor.boiler_reset 5 0 1 0 1
GC7000F boiler 132 heatingoff force heating off boolean True switch.boiler_force_heating_off switch.boiler_heatingoff 5 0 1 1 1
GC7000F boiler 132 heatingactive heating active boolean False binary_sensor.boiler_heating_active binary_sensor.boiler_heatingactive 5 0 1 2 1
GC7000F boiler 132 tapwateractive tapwater active boolean False binary_sensor.boiler_tapwater_active binary_sensor.boiler_tapwateractive 5 0 1 3 1
GC7000F boiler 132 selflowtemp selected flow temperature uint8 (>=0<=90) C True number.boiler_selected_flow_temperature number.boiler_selflowtemp 5 0 1 4 1
GC7000F boiler 132 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.boiler_heating_pump_modulation sensor.boiler_heatingpumpmod 5 0 1 5 1
GC7000F boiler 132 outdoortemp outside temperature int16 (>=-3199<=3199) C False sensor.boiler_outside_temperature sensor.boiler_outdoortemp 5 0 1/10 6 1
GC7000F boiler 132 curflowtemp current flow temperature uint16 (>=0<=3199) C False sensor.boiler_current_flow_temperature sensor.boiler_curflowtemp 5 0 1/10 7 1
GC7000F boiler 132 rettemp return temperature uint16 (>=0<=3199) C False sensor.boiler_return_temperature sensor.boiler_rettemp 5 0 1/10 8 1
GC7000F boiler 132 switchtemp mixing switch temperature uint16 (>=0<=3199) C False sensor.boiler_mixing_switch_temperature sensor.boiler_switchtemp 5 0 1/10 9 1
GC7000F boiler 132 syspress system pressure uint8 (>=0<=25) bar False sensor.boiler_system_pressure sensor.boiler_syspress 5 0 1/10 10 1
GC7000F boiler 132 boiltemp actual boiler temperature uint16 (>=0<=3199) C False sensor.boiler_actual_boiler_temperature sensor.boiler_boiltemp 5 0 1/10 11 1
GC7000F boiler 132 headertemp low loss header uint16 (>=0<=3199) C False sensor.boiler_low_loss_header sensor.boiler_headertemp 5 0 1/10 12 1
GC7000F boiler 132 exhausttemp exhaust temperature uint16 (>=0<=3199) C False sensor.boiler_exhaust_temperature sensor.boiler_exhausttemp 5 0 1/10 244 1
GC7000F boiler 132 burngas gas boolean False binary_sensor.boiler_gas binary_sensor.boiler_burngas 5 0 1 245 1
GC7000F boiler 132 burngas2 gas stage 2 boolean False binary_sensor.boiler_gas_stage_2 binary_sensor.boiler_burngas2 5 0 1 246 1
GC7000F boiler 132 flamecurr flame current uint16 (>=0<=3199) µA False sensor.boiler_flame_current sensor.boiler_flamecurr 5 0 1/10 247 1
GC7000F boiler 132 fanwork fan boolean False binary_sensor.boiler_fan binary_sensor.boiler_fanwork 5 0 1 248 1
GC7000F boiler 132 ignwork ignition boolean False binary_sensor.boiler_ignition binary_sensor.boiler_ignwork 5 0 1 249 1
GC7000F boiler 132 oilpreheat oil preheating boolean False binary_sensor.boiler_oil_preheating binary_sensor.boiler_oilpreheat 5 0 1 250 1
GC7000F boiler 132 burnminpower burner min power uint8 (>=0<=100) % True number.boiler_burner_min_power number.boiler_burnminpower 5 0 1 251 1
GC7000F boiler 132 burnmaxpower burner max power uint8 (>=0<=254) % True number.boiler_burner_max_power number.boiler_burnmaxpower 5 0 1 252 1
GC7000F boiler 132 burnminperiod burner min period uint8 (>=0<=120) minutes True number.boiler_burner_min_period number.boiler_burnminperiod 5 0 1 253 1
GC7000F boiler 132 absburnpow burner current power (absolute) uint8 (>=0<=100) % False sensor.boiler_burner_current_power_(absolute) sensor.boiler_absburnpow 5 0 1 254 1
GC7000F boiler 132 heatblock heating block uint16 (>=0<=3199) C False sensor.boiler_heating_block sensor.boiler_heatblock 5 0 1/10 255 1
GC7000F boiler 132 boilhyston hysteresis on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_on_temperature number.boiler_boilhyston 5 0 1 256 1
GC7000F boiler 132 boilhystoff hysteresis off temperature int8 (>=0<=20) C True number.boiler_hysteresis_off_temperature number.boiler_boilhystoff 5 0 1 257 1
GC7000F boiler 132 boil2hyston hysteresis stage 2 on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_stage_2_on_temperature number.boiler_boil2hyston 5 0 1 258 1
GC7000F boiler 132 boil2hystoff hysteresis stage 2 off temperature int8 (>=0<=20) C True number.boiler_hysteresis_stage_2_off_temperature number.boiler_boil2hystoff 5 0 1 259 1
GC7000F boiler 132 curveon heatingcurve on boolean True switch.boiler_heatingcurve_on switch.boiler_curveon 5 0 1 260 1
GC7000F boiler 132 curvebase heatingcurve base uint8 (>=20<=90) C True number.boiler_heatingcurve_base number.boiler_curvebase 5 0 1 261 1
GC7000F boiler 132 curveend heatingcurve end uint8 (>=20<=90) C True number.boiler_heatingcurve_end number.boiler_curveend 5 0 1 262 1
GC7000F boiler 132 summertemp summer temperature uint8 (>=0<=45) C True number.boiler_summer_temperature number.boiler_summertemp 5 0 1 263 1
GC7000F boiler 132 nofrostmode nofrost mode boolean True switch.boiler_nofrost_mode switch.boiler_nofrostmode 5 0 1 264 1
GC7000F boiler 132 nofrosttemp nofrost temperature uint8 (>=0<=10) C True number.boiler_nofrost_temperature number.boiler_nofrosttemp 5 0 1 265 1
GC7000F boiler 132 heatingactivated heating activated boolean True switch.boiler_heating_activated switch.boiler_heatingactivated 5 0 1 13 1
GC7000F boiler 132 heatingtemp heating temperature uint8 (>=0<=90) C True number.boiler_heating_temperature number.boiler_heatingtemp 5 0 1 14 1
GC7000F boiler 132 heatingpump heating pump boolean False binary_sensor.boiler_heating_pump binary_sensor.boiler_heatingpump 5 0 1 15 1
GC7000F boiler 132 pumpmodmax boiler pump max power uint8 (>=0<=100) % True number.boiler_boiler_pump_max_power number.boiler_pumpmodmax 5 0 1 16 1
GC7000F boiler 132 pumpmodmin boiler pump min power uint8 (>=0<=100) % True number.boiler_boiler_pump_min_power number.boiler_pumpmodmin 5 0 1 17 1
GC7000F boiler 132 pumpmode boiler pump mode enum [proportional|deltaP-1|deltaP-2|deltaP-3|deltaP-4] True select.boiler_boiler_pump_mode select.boiler_pumpmode 5 0 1 18 1
GC7000F boiler 132 pumpcharacter boiler pump characteristic enum [proportional|150mbar|200mbar|250mbar|300mbar|350mbar|400mbar] True select.boiler_boiler_pump_characteristic select.boiler_pumpcharacter 5 0 1 19 1
GC7000F boiler 132 pumpdelay pump delay uint8 (>=0<=60) minutes True number.boiler_pump_delay number.boiler_pumpdelay 5 0 1 20 1
GC7000F boiler 132 pumpontemp pump logic temperature uint8 (>=0<=60) C True number.boiler_pump_logic_temperature number.boiler_pumpontemp 5 0 1 21 1
GC7000F boiler 132 selburnpow burner selected max power uint8 (>=0<=254) % True number.boiler_burner_selected_max_power number.boiler_selburnpow 5 0 1 22 1
GC7000F boiler 132 curburnpow burner current power uint8 (>=0<=100) % False sensor.boiler_burner_current_power sensor.boiler_curburnpow 5 0 1 23 1
GC7000F boiler 132 burnstarts burner starts uint24 (>=0<=16777214) False sensor.boiler_burner_starts sensor.boiler_burnstarts 5 0 1 24 2
GC7000F boiler 132 burnworkmin total burner operating time time (>=0<=16777214) minutes False sensor.boiler_total_burner_operating_time sensor.boiler_burnworkmin 5 0 1 26 2
GC7000F boiler 132 burn2workmin burner stage 2 operating time time (>=0<=16777214) minutes False sensor.boiler_burner_stage_2_operating_time sensor.boiler_burn2workmin 5 0 1 28 2
GC7000F boiler 132 heatworkmin total heat operating time time (>=0<=16777214) minutes False sensor.boiler_total_heat_operating_time sensor.boiler_heatworkmin 5 0 1 30 2
GC7000F boiler 132 heatstarts burner starts heating uint24 (>=0<=16777214) False sensor.boiler_burner_starts_heating sensor.boiler_heatstarts 5 0 1 32 2
GC7000F boiler 132 ubauptime total UBA operating time time (>=0<=16777214) minutes False sensor.boiler_total_UBA_operating_time sensor.boiler_ubauptime 5 0 1 34 2
GC7000F boiler 132 lastcode last error code string False sensor.boiler_last_error_code sensor.boiler_lastcode 5 0 1 36 28
GC7000F boiler 132 servicecode service code string False sensor.boiler_service_code sensor.boiler_servicecode 5 0 1 64 2
GC7000F boiler 132 servicecodenumber service code number uint16 (>=0<=31999) False sensor.boiler_service_code_number sensor.boiler_servicecodenumber 5 0 1 66 1
GC7000F boiler 132 maintenancemessage maintenance message string False sensor.boiler_maintenance_message sensor.boiler_maintenancemessage 5 0 1 67 2
GC7000F boiler 132 maintenance maintenance scheduled enum [off|time|date|manual] True select.boiler_maintenance_scheduled select.boiler_maintenance 5 0 1 69 1
GC7000F boiler 132 maintenancetime time to next maintenance uint16 (>=0<=31999) hours True number.boiler_time_to_next_maintenance number.boiler_maintenancetime 5 0 1 70 1
GC7000F boiler 132 maintenancedate next maintenance date string True sensor.boiler_next_maintenance_date sensor.boiler_maintenancedate 5 0 1 71 6
GC7000F boiler 132 emergencyops emergency operation boolean True switch.boiler_emergency_operation switch.boiler_emergencyops 5 0 1 77 1
GC7000F boiler 132 emergencytemp emergency temperature uint8 (>=15<=70) C True number.boiler_emergency_temperature number.boiler_emergencytemp 5 0 1 78 1
GC7000F boiler 132 pc0flow Flow PC0 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC0 sensor.boiler_pc0flow 5 0 1 79 1
GC7000F boiler 132 pc1flow Flow PC1 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC1 sensor.boiler_pc1flow 5 0 1 80 1
GC7000F boiler 132 pc1on PC1 boolean False binary_sensor.boiler_PC1 binary_sensor.boiler_pc1on 5 0 1 81 1
GC7000F boiler 132 pc1rate PC1 rate uint8 (>=0<=100) % False sensor.boiler_PC1_rate sensor.boiler_pc1rate 5 0 1 82 1
GC7000F boiler 132 meterheat meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_meter_heating sensor.boiler_meterheat 5 0 1/10 95 2
GC7000F boiler 132 dhw.meter meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_meter sensor.boiler_dhw_meter 5 9 1/10 2 2
GC7000F boiler 132 gasmeterheat gas meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_gas_meter_heating sensor.boiler_gasmeterheat 5 0 1/10 266 2
GC7000F boiler 132 dhw.gasmeter gas meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_gas_meter sensor.boiler_dhw_gasmeter 5 9 1/10 69 2
GC7000F boiler 132 nrgheat2 energy heating 2 uint24 (>=0<=1677721) kWh False sensor.boiler_energy_heating_2 sensor.boiler_nrgheat2 5 0 1/10 268 2
GC7000F boiler 132 dhw.nrg2 energy 2 uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_energy_2 sensor.boiler_dhw_nrg2 5 9 1/10 71 2
GC7000F boiler 132 dhw.tapactivated turn on/off boolean True switch.boiler_dhw_turn_on/off switch.boiler_dhw_tapactivated 5 9 1 28 1
GC7000F boiler 132 dhw.settemp set temperature uint8 (>=0<=254) C False sensor.boiler_dhw_set_temperature sensor.boiler_dhw_settemp 5 9 1 29 1
GC7000F boiler 132 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_temperature number.boiler_dhw_seltemp 5 9 1 30 1
GC7000F boiler 132 dhw.seltemplow selected lower temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_lower_temperature number.boiler_dhw_seltemplow 5 9 1 31 1
GC7000F boiler 132 dhw.tempecoplus selected eco+ temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_eco+_temperature number.boiler_dhw_tempecoplus 5 9 1 32 1
GC7000F boiler 132 dhw.seltempoff selected temperature for off uint8 (>=0<=254) C False sensor.boiler_dhw_selected_temperature_for_off sensor.boiler_dhw_seltempoff 5 9 1 33 1
GC7000F boiler 132 dhw.seltempsingle single charge temperature uint8 (>=0<=254) C True number.boiler_dhw_single_charge_temperature number.boiler_dhw_seltempsingle 5 9 1 34 1
GC7000F boiler 132 dhw.solartemp solar boiler temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_solar_boiler_temperature sensor.boiler_dhw_solartemp 5 9 1/10 35 1
GC7000F boiler 132 dhw.type type enum [off|flow|buffered flow|buffer|layered buffer] False sensor.boiler_dhw_type sensor.boiler_dhw_type 5 9 1 36 1
GC7000F boiler 132 dhw.comfort comfort enum [hot|eco|intelligent] True select.boiler_dhw_comfort select.boiler_dhw_comfort 5 9 1 37 1
GC7000F boiler 132 dhw.comfort1 comfort mode enum [high comfort|eco] True select.boiler_dhw_comfort_mode select.boiler_dhw_comfort1 5 9 1 38 1
GC7000F boiler 132 dhw.flowtempoffset flow temperature offset uint8 (>=0<=100) C True number.boiler_dhw_flow_temperature_offset number.boiler_dhw_flowtempoffset 5 9 1 39 1
GC7000F boiler 132 dhw.chargeoptimization charge optimization boolean True switch.boiler_dhw_charge_optimization switch.boiler_dhw_chargeoptimization 5 9 1 40 1
GC7000F boiler 132 dhw.maxpower max power uint8 (>=0<=254) % True number.boiler_dhw_max_power number.boiler_dhw_maxpower 5 9 1 41 1
GC7000F boiler 132 dhw.maxtemp maximum temperature uint8 (>=0<=80) C True number.boiler_dhw_maximum_temperature number.boiler_dhw_maxtemp 5 9 1 42 1
GC7000F boiler 132 dhw.circpump circulation pump available boolean True switch.boiler_dhw_circulation_pump_available switch.boiler_dhw_circpump 5 9 1 43 1
GC7000F boiler 132 dhw.chargetype charging type enum [chargepump|3-way valve] False sensor.boiler_dhw_charging_type sensor.boiler_dhw_chargetype 5 9 1 44 1
GC7000F boiler 132 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_on_temperature number.boiler_dhw_hyston 5 9 1 45 1
GC7000F boiler 132 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_off_temperature number.boiler_dhw_hystoff 5 9 1 46 1
GC7000F boiler 132 dhw.disinfectiontemp disinfection temperature uint8 (>=60<=80) C True number.boiler_dhw_disinfection_temperature number.boiler_dhw_disinfectiontemp 5 9 1 47 1
GC7000F boiler 132 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.boiler_dhw_circulation_pump_mode select.boiler_dhw_circmode 5 9 1 48 1
GC7000F boiler 132 dhw.circ circulation active boolean True switch.boiler_dhw_circulation_active switch.boiler_dhw_circ 5 9 1 49 1
GC7000F boiler 132 dhw.curtemp current intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_intern_temperature sensor.boiler_dhw_curtemp 5 9 1/10 50 1
GC7000F boiler 132 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_extern_temperature sensor.boiler_dhw_curtemp2 5 9 1/10 51 1
GC7000F boiler 132 dhw.curflow current tap water flow uint8 (>=0<=25) l/min False sensor.boiler_dhw_current_tap_water_flow sensor.boiler_dhw_curflow 5 9 1/10 52 1
GC7000F boiler 132 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_intern_temperature sensor.boiler_dhw_storagetemp1 5 9 1/10 53 1
GC7000F boiler 132 dhw.storagetemp2 storage extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_extern_temperature sensor.boiler_dhw_storagetemp2 5 9 1/10 54 1
GC7000F boiler 132 dhw.activated activated boolean True switch.boiler_dhw_activated switch.boiler_dhw_activated 5 9 1 55 1
GC7000F boiler 132 dhw.onetime one time charging boolean True switch.boiler_dhw_one_time_charging switch.boiler_dhw_onetime 5 9 1 56 1
GC7000F boiler 132 dhw.disinfecting disinfecting boolean True switch.boiler_dhw_disinfecting switch.boiler_dhw_disinfecting 5 9 1 57 1
GC7000F boiler 132 dhw.charging charging boolean False binary_sensor.boiler_dhw_charging binary_sensor.boiler_dhw_charging 5 9 1 58 1
GC7000F boiler 132 dhw.recharging recharging boolean False binary_sensor.boiler_dhw_recharging binary_sensor.boiler_dhw_recharging 5 9 1 59 1
GC7000F boiler 132 dhw.tempok temperature ok boolean False binary_sensor.boiler_dhw_temperature_ok binary_sensor.boiler_dhw_tempok 5 9 1 60 1
GC7000F boiler 132 dhw.active active boolean False binary_sensor.boiler_dhw_active binary_sensor.boiler_dhw_active 5 9 1 61 1
GC7000F boiler 132 dhw.3wayvalve 3-way valve active boolean False binary_sensor.boiler_dhw_3-way_valve_active binary_sensor.boiler_dhw_3wayvalve 5 9 1 62 1
GC7000F boiler 132 dhw.mixertemp mixer temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_mixer_temperature sensor.boiler_dhw_mixertemp 5 9 1/10 63 1
GC7000F boiler 132 dhw.cylmiddletemp cylinder middle temperature (TS3) uint16 (>=0<=3199) C False sensor.boiler_dhw_cylinder_middle_temperature_(TS3) sensor.boiler_dhw_cylmiddletemp 5 9 1/10 64 1
GC7000F boiler 132 dhw.starts starts uint24 (>=0<=16777214) False sensor.boiler_dhw_starts sensor.boiler_dhw_starts 5 9 1 65 2
GC7000F boiler 132 dhw.workm active time time (>=0<=16777214) minutes False sensor.boiler_dhw_active_time sensor.boiler_dhw_workm 5 9 1 67 2
GC7000F boiler 132 nompower nominal Power uint8 (>=0<=254) kW True number.boiler_nominal_Power number.boiler_nompower 5 0 1 270 1
GC7000F boiler 132 nrgtotal total energy uint24 (>=0<=167772) kWh False sensor.boiler_total_energy sensor.boiler_nrgtotal 5 0 1/100 83 2
GC7000F boiler 132 nrgheat energy heating uint24 (>=0<=10000000) kWh True number.boiler_energy_heating number.boiler_nrgheat 5 0 1/100 85 2
GC7000F boiler 132 dhw.nrg energy uint24 (>=0<=10000000) kWh True number.boiler_dhw_energy number.boiler_dhw_nrg 5 9 1/100 0 2
Logano GB125/KB195i, Logamatic MC110 boiler 133 reset reset cmd [-|maintenance|error|history|message] True sensor.boiler_reset sensor.boiler_reset 5 0 1 0 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 heatingoff force heating off boolean True switch.boiler_force_heating_off switch.boiler_heatingoff 5 0 1 1 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 heatingactive heating active boolean False binary_sensor.boiler_heating_active binary_sensor.boiler_heatingactive 5 0 1 2 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 tapwateractive tapwater active boolean False binary_sensor.boiler_tapwater_active binary_sensor.boiler_tapwateractive 5 0 1 3 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 selflowtemp selected flow temperature uint8 (>=0<=90) C True number.boiler_selected_flow_temperature number.boiler_selflowtemp 5 0 1 4 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.boiler_heating_pump_modulation sensor.boiler_heatingpumpmod 5 0 1 5 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 outdoortemp outside temperature int16 (>=-3199<=3199) C False sensor.boiler_outside_temperature sensor.boiler_outdoortemp 5 0 1/10 6 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 curflowtemp current flow temperature uint16 (>=0<=3199) C False sensor.boiler_current_flow_temperature sensor.boiler_curflowtemp 5 0 1/10 7 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 rettemp return temperature uint16 (>=0<=3199) C False sensor.boiler_return_temperature sensor.boiler_rettemp 5 0 1/10 8 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 switchtemp mixing switch temperature uint16 (>=0<=3199) C False sensor.boiler_mixing_switch_temperature sensor.boiler_switchtemp 5 0 1/10 9 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 syspress system pressure uint8 (>=0<=25) bar False sensor.boiler_system_pressure sensor.boiler_syspress 5 0 1/10 10 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 boiltemp actual boiler temperature uint16 (>=0<=3199) C False sensor.boiler_actual_boiler_temperature sensor.boiler_boiltemp 5 0 1/10 11 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 headertemp low loss header uint16 (>=0<=3199) C False sensor.boiler_low_loss_header sensor.boiler_headertemp 5 0 1/10 12 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 exhausttemp exhaust temperature uint16 (>=0<=3199) C False sensor.boiler_exhaust_temperature sensor.boiler_exhausttemp 5 0 1/10 244 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 burngas gas boolean False binary_sensor.boiler_gas binary_sensor.boiler_burngas 5 0 1 245 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 burngas2 gas stage 2 boolean False binary_sensor.boiler_gas_stage_2 binary_sensor.boiler_burngas2 5 0 1 246 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 flamecurr flame current uint16 (>=0<=3199) µA False sensor.boiler_flame_current sensor.boiler_flamecurr 5 0 1/10 247 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 fanwork fan boolean False binary_sensor.boiler_fan binary_sensor.boiler_fanwork 5 0 1 248 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 ignwork ignition boolean False binary_sensor.boiler_ignition binary_sensor.boiler_ignwork 5 0 1 249 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 oilpreheat oil preheating boolean False binary_sensor.boiler_oil_preheating binary_sensor.boiler_oilpreheat 5 0 1 250 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 burnminpower burner min power uint8 (>=0<=100) % True number.boiler_burner_min_power number.boiler_burnminpower 5 0 1 251 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 burnmaxpower burner max power uint8 (>=0<=254) % True number.boiler_burner_max_power number.boiler_burnmaxpower 5 0 1 252 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 burnminperiod burner min period uint8 (>=0<=120) minutes True number.boiler_burner_min_period number.boiler_burnminperiod 5 0 1 253 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 absburnpow burner current power (absolute) uint8 (>=0<=100) % False sensor.boiler_burner_current_power_(absolute) sensor.boiler_absburnpow 5 0 1 254 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 heatblock heating block uint16 (>=0<=3199) C False sensor.boiler_heating_block sensor.boiler_heatblock 5 0 1/10 255 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 boilhyston hysteresis on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_on_temperature number.boiler_boilhyston 5 0 1 256 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 boilhystoff hysteresis off temperature int8 (>=0<=20) C True number.boiler_hysteresis_off_temperature number.boiler_boilhystoff 5 0 1 257 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 boil2hyston hysteresis stage 2 on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_stage_2_on_temperature number.boiler_boil2hyston 5 0 1 258 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 boil2hystoff hysteresis stage 2 off temperature int8 (>=0<=20) C True number.boiler_hysteresis_stage_2_off_temperature number.boiler_boil2hystoff 5 0 1 259 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 curveon heatingcurve on boolean True switch.boiler_heatingcurve_on switch.boiler_curveon 5 0 1 260 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 curvebase heatingcurve base uint8 (>=20<=90) C True number.boiler_heatingcurve_base number.boiler_curvebase 5 0 1 261 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 curveend heatingcurve end uint8 (>=20<=90) C True number.boiler_heatingcurve_end number.boiler_curveend 5 0 1 262 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 summertemp summer temperature uint8 (>=0<=45) C True number.boiler_summer_temperature number.boiler_summertemp 5 0 1 263 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 nofrostmode nofrost mode boolean True switch.boiler_nofrost_mode switch.boiler_nofrostmode 5 0 1 264 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 nofrosttemp nofrost temperature uint8 (>=0<=10) C True number.boiler_nofrost_temperature number.boiler_nofrosttemp 5 0 1 265 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 heatingactivated heating activated boolean True switch.boiler_heating_activated switch.boiler_heatingactivated 5 0 1 13 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 heatingtemp heating temperature uint8 (>=0<=90) C True number.boiler_heating_temperature number.boiler_heatingtemp 5 0 1 14 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 heatingpump heating pump boolean False binary_sensor.boiler_heating_pump binary_sensor.boiler_heatingpump 5 0 1 15 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 pumpmodmax boiler pump max power uint8 (>=0<=100) % True number.boiler_boiler_pump_max_power number.boiler_pumpmodmax 5 0 1 16 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 pumpmodmin boiler pump min power uint8 (>=0<=100) % True number.boiler_boiler_pump_min_power number.boiler_pumpmodmin 5 0 1 17 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 pumpmode boiler pump mode enum [proportional|deltaP-1|deltaP-2|deltaP-3|deltaP-4] True select.boiler_boiler_pump_mode select.boiler_pumpmode 5 0 1 18 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 pumpcharacter boiler pump characteristic enum [proportional|150mbar|200mbar|250mbar|300mbar|350mbar|400mbar] True select.boiler_boiler_pump_characteristic select.boiler_pumpcharacter 5 0 1 19 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 pumpdelay pump delay uint8 (>=0<=60) minutes True number.boiler_pump_delay number.boiler_pumpdelay 5 0 1 20 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 pumpontemp pump logic temperature uint8 (>=0<=60) C True number.boiler_pump_logic_temperature number.boiler_pumpontemp 5 0 1 21 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 selburnpow burner selected max power uint8 (>=0<=254) % True number.boiler_burner_selected_max_power number.boiler_selburnpow 5 0 1 22 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 curburnpow burner current power uint8 (>=0<=100) % False sensor.boiler_burner_current_power sensor.boiler_curburnpow 5 0 1 23 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 burnstarts burner starts uint24 (>=0<=16777214) False sensor.boiler_burner_starts sensor.boiler_burnstarts 5 0 1 24 2
Logano GB125/KB195i, Logamatic MC110 boiler 133 burnworkmin total burner operating time time (>=0<=16777214) minutes False sensor.boiler_total_burner_operating_time sensor.boiler_burnworkmin 5 0 1 26 2
Logano GB125/KB195i, Logamatic MC110 boiler 133 burn2workmin burner stage 2 operating time time (>=0<=16777214) minutes False sensor.boiler_burner_stage_2_operating_time sensor.boiler_burn2workmin 5 0 1 28 2
Logano GB125/KB195i, Logamatic MC110 boiler 133 heatworkmin total heat operating time time (>=0<=16777214) minutes False sensor.boiler_total_heat_operating_time sensor.boiler_heatworkmin 5 0 1 30 2
Logano GB125/KB195i, Logamatic MC110 boiler 133 heatstarts burner starts heating uint24 (>=0<=16777214) False sensor.boiler_burner_starts_heating sensor.boiler_heatstarts 5 0 1 32 2
Logano GB125/KB195i, Logamatic MC110 boiler 133 ubauptime total UBA operating time time (>=0<=16777214) minutes False sensor.boiler_total_UBA_operating_time sensor.boiler_ubauptime 5 0 1 34 2
Logano GB125/KB195i, Logamatic MC110 boiler 133 lastcode last error code string False sensor.boiler_last_error_code sensor.boiler_lastcode 5 0 1 36 28
Logano GB125/KB195i, Logamatic MC110 boiler 133 servicecode service code string False sensor.boiler_service_code sensor.boiler_servicecode 5 0 1 64 2
Logano GB125/KB195i, Logamatic MC110 boiler 133 servicecodenumber service code number uint16 (>=0<=31999) False sensor.boiler_service_code_number sensor.boiler_servicecodenumber 5 0 1 66 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 maintenancemessage maintenance message string False sensor.boiler_maintenance_message sensor.boiler_maintenancemessage 5 0 1 67 2
Logano GB125/KB195i, Logamatic MC110 boiler 133 maintenance maintenance scheduled enum [off|time|date|manual] True select.boiler_maintenance_scheduled select.boiler_maintenance 5 0 1 69 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 maintenancetime time to next maintenance uint16 (>=0<=31999) hours True number.boiler_time_to_next_maintenance number.boiler_maintenancetime 5 0 1 70 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 maintenancedate next maintenance date string True sensor.boiler_next_maintenance_date sensor.boiler_maintenancedate 5 0 1 71 6
Logano GB125/KB195i, Logamatic MC110 boiler 133 emergencyops emergency operation boolean True switch.boiler_emergency_operation switch.boiler_emergencyops 5 0 1 77 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 emergencytemp emergency temperature uint8 (>=15<=70) C True number.boiler_emergency_temperature number.boiler_emergencytemp 5 0 1 78 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 pc0flow Flow PC0 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC0 sensor.boiler_pc0flow 5 0 1 79 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 pc1flow Flow PC1 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC1 sensor.boiler_pc1flow 5 0 1 80 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 pc1on PC1 boolean False binary_sensor.boiler_PC1 binary_sensor.boiler_pc1on 5 0 1 81 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 pc1rate PC1 rate uint8 (>=0<=100) % False sensor.boiler_PC1_rate sensor.boiler_pc1rate 5 0 1 82 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 meterheat meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_meter_heating sensor.boiler_meterheat 5 0 1/10 95 2
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.meter meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_meter sensor.boiler_dhw_meter 5 9 1/10 2 2
Logano GB125/KB195i, Logamatic MC110 boiler 133 gasmeterheat gas meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_gas_meter_heating sensor.boiler_gasmeterheat 5 0 1/10 266 2
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.gasmeter gas meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_gas_meter sensor.boiler_dhw_gasmeter 5 9 1/10 69 2
Logano GB125/KB195i, Logamatic MC110 boiler 133 nrgheat2 energy heating 2 uint24 (>=0<=1677721) kWh False sensor.boiler_energy_heating_2 sensor.boiler_nrgheat2 5 0 1/10 268 2
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.nrg2 energy 2 uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_energy_2 sensor.boiler_dhw_nrg2 5 9 1/10 71 2
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.tapactivated turn on/off boolean True switch.boiler_dhw_turn_on/off switch.boiler_dhw_tapactivated 5 9 1 28 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.settemp set temperature uint8 (>=0<=254) C False sensor.boiler_dhw_set_temperature sensor.boiler_dhw_settemp 5 9 1 29 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_temperature number.boiler_dhw_seltemp 5 9 1 30 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.seltemplow selected lower temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_lower_temperature number.boiler_dhw_seltemplow 5 9 1 31 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.tempecoplus selected eco+ temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_eco+_temperature number.boiler_dhw_tempecoplus 5 9 1 32 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.seltempoff selected temperature for off uint8 (>=0<=254) C False sensor.boiler_dhw_selected_temperature_for_off sensor.boiler_dhw_seltempoff 5 9 1 33 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.seltempsingle single charge temperature uint8 (>=0<=254) C True number.boiler_dhw_single_charge_temperature number.boiler_dhw_seltempsingle 5 9 1 34 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.solartemp solar boiler temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_solar_boiler_temperature sensor.boiler_dhw_solartemp 5 9 1/10 35 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.type type enum [off|flow|buffered flow|buffer|layered buffer] False sensor.boiler_dhw_type sensor.boiler_dhw_type 5 9 1 36 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.comfort comfort enum [hot|eco|intelligent] True select.boiler_dhw_comfort select.boiler_dhw_comfort 5 9 1 37 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.comfort1 comfort mode enum [high comfort|eco] True select.boiler_dhw_comfort_mode select.boiler_dhw_comfort1 5 9 1 38 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.flowtempoffset flow temperature offset uint8 (>=0<=100) C True number.boiler_dhw_flow_temperature_offset number.boiler_dhw_flowtempoffset 5 9 1 39 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.chargeoptimization charge optimization boolean True switch.boiler_dhw_charge_optimization switch.boiler_dhw_chargeoptimization 5 9 1 40 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.maxpower max power uint8 (>=0<=254) % True number.boiler_dhw_max_power number.boiler_dhw_maxpower 5 9 1 41 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.maxtemp maximum temperature uint8 (>=0<=80) C True number.boiler_dhw_maximum_temperature number.boiler_dhw_maxtemp 5 9 1 42 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.circpump circulation pump available boolean True switch.boiler_dhw_circulation_pump_available switch.boiler_dhw_circpump 5 9 1 43 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.chargetype charging type enum [chargepump|3-way valve] False sensor.boiler_dhw_charging_type sensor.boiler_dhw_chargetype 5 9 1 44 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_on_temperature number.boiler_dhw_hyston 5 9 1 45 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_off_temperature number.boiler_dhw_hystoff 5 9 1 46 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.disinfectiontemp disinfection temperature uint8 (>=60<=80) C True number.boiler_dhw_disinfection_temperature number.boiler_dhw_disinfectiontemp 5 9 1 47 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.boiler_dhw_circulation_pump_mode select.boiler_dhw_circmode 5 9 1 48 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.circ circulation active boolean True switch.boiler_dhw_circulation_active switch.boiler_dhw_circ 5 9 1 49 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.curtemp current intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_intern_temperature sensor.boiler_dhw_curtemp 5 9 1/10 50 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_extern_temperature sensor.boiler_dhw_curtemp2 5 9 1/10 51 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.curflow current tap water flow uint8 (>=0<=25) l/min False sensor.boiler_dhw_current_tap_water_flow sensor.boiler_dhw_curflow 5 9 1/10 52 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_intern_temperature sensor.boiler_dhw_storagetemp1 5 9 1/10 53 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.storagetemp2 storage extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_extern_temperature sensor.boiler_dhw_storagetemp2 5 9 1/10 54 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.activated activated boolean True switch.boiler_dhw_activated switch.boiler_dhw_activated 5 9 1 55 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.onetime one time charging boolean True switch.boiler_dhw_one_time_charging switch.boiler_dhw_onetime 5 9 1 56 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.disinfecting disinfecting boolean True switch.boiler_dhw_disinfecting switch.boiler_dhw_disinfecting 5 9 1 57 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.charging charging boolean False binary_sensor.boiler_dhw_charging binary_sensor.boiler_dhw_charging 5 9 1 58 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.recharging recharging boolean False binary_sensor.boiler_dhw_recharging binary_sensor.boiler_dhw_recharging 5 9 1 59 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.tempok temperature ok boolean False binary_sensor.boiler_dhw_temperature_ok binary_sensor.boiler_dhw_tempok 5 9 1 60 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.active active boolean False binary_sensor.boiler_dhw_active binary_sensor.boiler_dhw_active 5 9 1 61 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.3wayvalve 3-way valve active boolean False binary_sensor.boiler_dhw_3-way_valve_active binary_sensor.boiler_dhw_3wayvalve 5 9 1 62 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.mixertemp mixer temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_mixer_temperature sensor.boiler_dhw_mixertemp 5 9 1/10 63 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.cylmiddletemp cylinder middle temperature (TS3) uint16 (>=0<=3199) C False sensor.boiler_dhw_cylinder_middle_temperature_(TS3) sensor.boiler_dhw_cylmiddletemp 5 9 1/10 64 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.starts starts uint24 (>=0<=16777214) False sensor.boiler_dhw_starts sensor.boiler_dhw_starts 5 9 1 65 2
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.workm active time time (>=0<=16777214) minutes False sensor.boiler_dhw_active_time sensor.boiler_dhw_workm 5 9 1 67 2
Logano GB125/KB195i, Logamatic MC110 boiler 133 nompower nominal Power uint8 (>=0<=254) kW True number.boiler_nominal_Power number.boiler_nompower 5 0 1 270 1
Logano GB125/KB195i, Logamatic MC110 boiler 133 nrgtotal total energy uint24 (>=0<=167772) kWh False sensor.boiler_total_energy sensor.boiler_nrgtotal 5 0 1/100 83 2
Logano GB125/KB195i, Logamatic MC110 boiler 133 nrgheat energy heating uint24 (>=0<=10000000) kWh True number.boiler_energy_heating number.boiler_nrgheat 5 0 1/100 85 2
Logano GB125/KB195i, Logamatic MC110 boiler 133 dhw.nrg energy uint24 (>=0<=10000000) kWh True number.boiler_dhw_energy number.boiler_dhw_nrg 5 9 1/100 0 2
Greenstar 30Ri Compact boiler 154 reset reset cmd [-|maintenance|error|history|message] True sensor.boiler_reset sensor.boiler_reset 5 0 1 0 1
Greenstar 30Ri Compact boiler 154 heatingoff force heating off boolean True switch.boiler_force_heating_off switch.boiler_heatingoff 5 0 1 1 1
Greenstar 30Ri Compact boiler 154 heatingactive heating active boolean False binary_sensor.boiler_heating_active binary_sensor.boiler_heatingactive 5 0 1 2 1
Greenstar 30Ri Compact boiler 154 tapwateractive tapwater active boolean False binary_sensor.boiler_tapwater_active binary_sensor.boiler_tapwateractive 5 0 1 3 1
Greenstar 30Ri Compact boiler 154 selflowtemp selected flow temperature uint8 (>=0<=90) C True number.boiler_selected_flow_temperature number.boiler_selflowtemp 5 0 1 4 1
Greenstar 30Ri Compact boiler 154 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.boiler_heating_pump_modulation sensor.boiler_heatingpumpmod 5 0 1 5 1
Greenstar 30Ri Compact boiler 154 outdoortemp outside temperature int16 (>=-3199<=3199) C False sensor.boiler_outside_temperature sensor.boiler_outdoortemp 5 0 1/10 6 1
Greenstar 30Ri Compact boiler 154 curflowtemp current flow temperature uint16 (>=0<=3199) C False sensor.boiler_current_flow_temperature sensor.boiler_curflowtemp 5 0 1/10 7 1
Greenstar 30Ri Compact boiler 154 rettemp return temperature uint16 (>=0<=3199) C False sensor.boiler_return_temperature sensor.boiler_rettemp 5 0 1/10 8 1
Greenstar 30Ri Compact boiler 154 switchtemp mixing switch temperature uint16 (>=0<=3199) C False sensor.boiler_mixing_switch_temperature sensor.boiler_switchtemp 5 0 1/10 9 1
Greenstar 30Ri Compact boiler 154 syspress system pressure uint8 (>=0<=25) bar False sensor.boiler_system_pressure sensor.boiler_syspress 5 0 1/10 10 1
Greenstar 30Ri Compact boiler 154 boiltemp actual boiler temperature uint16 (>=0<=3199) C False sensor.boiler_actual_boiler_temperature sensor.boiler_boiltemp 5 0 1/10 11 1
Greenstar 30Ri Compact boiler 154 headertemp low loss header uint16 (>=0<=3199) C False sensor.boiler_low_loss_header sensor.boiler_headertemp 5 0 1/10 12 1
Greenstar 30Ri Compact boiler 154 exhausttemp exhaust temperature uint16 (>=0<=3199) C False sensor.boiler_exhaust_temperature sensor.boiler_exhausttemp 5 0 1/10 244 1
Greenstar 30Ri Compact boiler 154 burngas gas boolean False binary_sensor.boiler_gas binary_sensor.boiler_burngas 5 0 1 245 1
Greenstar 30Ri Compact boiler 154 burngas2 gas stage 2 boolean False binary_sensor.boiler_gas_stage_2 binary_sensor.boiler_burngas2 5 0 1 246 1
Greenstar 30Ri Compact boiler 154 flamecurr flame current uint16 (>=0<=3199) µA False sensor.boiler_flame_current sensor.boiler_flamecurr 5 0 1/10 247 1
Greenstar 30Ri Compact boiler 154 fanwork fan boolean False binary_sensor.boiler_fan binary_sensor.boiler_fanwork 5 0 1 248 1
Greenstar 30Ri Compact boiler 154 ignwork ignition boolean False binary_sensor.boiler_ignition binary_sensor.boiler_ignwork 5 0 1 249 1
Greenstar 30Ri Compact boiler 154 oilpreheat oil preheating boolean False binary_sensor.boiler_oil_preheating binary_sensor.boiler_oilpreheat 5 0 1 250 1
Greenstar 30Ri Compact boiler 154 burnminpower burner min power uint8 (>=0<=100) % True number.boiler_burner_min_power number.boiler_burnminpower 5 0 1 251 1
Greenstar 30Ri Compact boiler 154 burnmaxpower burner max power uint8 (>=0<=254) % True number.boiler_burner_max_power number.boiler_burnmaxpower 5 0 1 252 1
Greenstar 30Ri Compact boiler 154 burnminperiod burner min period uint8 (>=0<=120) minutes True number.boiler_burner_min_period number.boiler_burnminperiod 5 0 1 253 1
Greenstar 30Ri Compact boiler 154 absburnpow burner current power (absolute) uint8 (>=0<=100) % False sensor.boiler_burner_current_power_(absolute) sensor.boiler_absburnpow 5 0 1 254 1
Greenstar 30Ri Compact boiler 154 heatblock heating block uint16 (>=0<=3199) C False sensor.boiler_heating_block sensor.boiler_heatblock 5 0 1/10 255 1
Greenstar 30Ri Compact boiler 154 boilhyston hysteresis on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_on_temperature number.boiler_boilhyston 5 0 1 256 1
Greenstar 30Ri Compact boiler 154 boilhystoff hysteresis off temperature int8 (>=0<=20) C True number.boiler_hysteresis_off_temperature number.boiler_boilhystoff 5 0 1 257 1
Greenstar 30Ri Compact boiler 154 boil2hyston hysteresis stage 2 on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_stage_2_on_temperature number.boiler_boil2hyston 5 0 1 258 1
Greenstar 30Ri Compact boiler 154 boil2hystoff hysteresis stage 2 off temperature int8 (>=0<=20) C True number.boiler_hysteresis_stage_2_off_temperature number.boiler_boil2hystoff 5 0 1 259 1
Greenstar 30Ri Compact boiler 154 curveon heatingcurve on boolean True switch.boiler_heatingcurve_on switch.boiler_curveon 5 0 1 260 1
Greenstar 30Ri Compact boiler 154 curvebase heatingcurve base uint8 (>=20<=90) C True number.boiler_heatingcurve_base number.boiler_curvebase 5 0 1 261 1
Greenstar 30Ri Compact boiler 154 curveend heatingcurve end uint8 (>=20<=90) C True number.boiler_heatingcurve_end number.boiler_curveend 5 0 1 262 1
Greenstar 30Ri Compact boiler 154 summertemp summer temperature uint8 (>=0<=45) C True number.boiler_summer_temperature number.boiler_summertemp 5 0 1 263 1
Greenstar 30Ri Compact boiler 154 nofrostmode nofrost mode boolean True switch.boiler_nofrost_mode switch.boiler_nofrostmode 5 0 1 264 1
Greenstar 30Ri Compact boiler 154 nofrosttemp nofrost temperature uint8 (>=0<=10) C True number.boiler_nofrost_temperature number.boiler_nofrosttemp 5 0 1 265 1
Greenstar 30Ri Compact boiler 154 heatingactivated heating activated boolean True switch.boiler_heating_activated switch.boiler_heatingactivated 5 0 1 13 1
Greenstar 30Ri Compact boiler 154 heatingtemp heating temperature uint8 (>=0<=90) C True number.boiler_heating_temperature number.boiler_heatingtemp 5 0 1 14 1
Greenstar 30Ri Compact boiler 154 heatingpump heating pump boolean False binary_sensor.boiler_heating_pump binary_sensor.boiler_heatingpump 5 0 1 15 1
Greenstar 30Ri Compact boiler 154 pumpmodmax boiler pump max power uint8 (>=0<=100) % True number.boiler_boiler_pump_max_power number.boiler_pumpmodmax 5 0 1 16 1
Greenstar 30Ri Compact boiler 154 pumpmodmin boiler pump min power uint8 (>=0<=100) % True number.boiler_boiler_pump_min_power number.boiler_pumpmodmin 5 0 1 17 1
Greenstar 30Ri Compact boiler 154 pumpmode boiler pump mode enum [proportional|deltaP-1|deltaP-2|deltaP-3|deltaP-4] True select.boiler_boiler_pump_mode select.boiler_pumpmode 5 0 1 18 1
Greenstar 30Ri Compact boiler 154 pumpcharacter boiler pump characteristic enum [proportional|150mbar|200mbar|250mbar|300mbar|350mbar|400mbar] True select.boiler_boiler_pump_characteristic select.boiler_pumpcharacter 5 0 1 19 1
Greenstar 30Ri Compact boiler 154 pumpdelay pump delay uint8 (>=0<=60) minutes True number.boiler_pump_delay number.boiler_pumpdelay 5 0 1 20 1
Greenstar 30Ri Compact boiler 154 pumpontemp pump logic temperature uint8 (>=0<=60) C True number.boiler_pump_logic_temperature number.boiler_pumpontemp 5 0 1 21 1
Greenstar 30Ri Compact boiler 154 selburnpow burner selected max power uint8 (>=0<=254) % True number.boiler_burner_selected_max_power number.boiler_selburnpow 5 0 1 22 1
Greenstar 30Ri Compact boiler 154 curburnpow burner current power uint8 (>=0<=100) % False sensor.boiler_burner_current_power sensor.boiler_curburnpow 5 0 1 23 1
Greenstar 30Ri Compact boiler 154 burnstarts burner starts uint24 (>=0<=16777214) False sensor.boiler_burner_starts sensor.boiler_burnstarts 5 0 1 24 2
Greenstar 30Ri Compact boiler 154 burnworkmin total burner operating time time (>=0<=16777214) minutes False sensor.boiler_total_burner_operating_time sensor.boiler_burnworkmin 5 0 1 26 2
Greenstar 30Ri Compact boiler 154 burn2workmin burner stage 2 operating time time (>=0<=16777214) minutes False sensor.boiler_burner_stage_2_operating_time sensor.boiler_burn2workmin 5 0 1 28 2
Greenstar 30Ri Compact boiler 154 heatworkmin total heat operating time time (>=0<=16777214) minutes False sensor.boiler_total_heat_operating_time sensor.boiler_heatworkmin 5 0 1 30 2
Greenstar 30Ri Compact boiler 154 heatstarts burner starts heating uint24 (>=0<=16777214) False sensor.boiler_burner_starts_heating sensor.boiler_heatstarts 5 0 1 32 2
Greenstar 30Ri Compact boiler 154 ubauptime total UBA operating time time (>=0<=16777214) minutes False sensor.boiler_total_UBA_operating_time sensor.boiler_ubauptime 5 0 1 34 2
Greenstar 30Ri Compact boiler 154 lastcode last error code string False sensor.boiler_last_error_code sensor.boiler_lastcode 5 0 1 36 28
Greenstar 30Ri Compact boiler 154 servicecode service code string False sensor.boiler_service_code sensor.boiler_servicecode 5 0 1 64 2
Greenstar 30Ri Compact boiler 154 servicecodenumber service code number uint16 (>=0<=31999) False sensor.boiler_service_code_number sensor.boiler_servicecodenumber 5 0 1 66 1
Greenstar 30Ri Compact boiler 154 maintenancemessage maintenance message string False sensor.boiler_maintenance_message sensor.boiler_maintenancemessage 5 0 1 67 2
Greenstar 30Ri Compact boiler 154 maintenance maintenance scheduled enum [off|time|date|manual] True select.boiler_maintenance_scheduled select.boiler_maintenance 5 0 1 69 1
Greenstar 30Ri Compact boiler 154 maintenancetime time to next maintenance uint16 (>=0<=31999) hours True number.boiler_time_to_next_maintenance number.boiler_maintenancetime 5 0 1 70 1
Greenstar 30Ri Compact boiler 154 maintenancedate next maintenance date string True sensor.boiler_next_maintenance_date sensor.boiler_maintenancedate 5 0 1 71 6
Greenstar 30Ri Compact boiler 154 emergencyops emergency operation boolean True switch.boiler_emergency_operation switch.boiler_emergencyops 5 0 1 77 1
Greenstar 30Ri Compact boiler 154 emergencytemp emergency temperature uint8 (>=15<=70) C True number.boiler_emergency_temperature number.boiler_emergencytemp 5 0 1 78 1
Greenstar 30Ri Compact boiler 154 pc0flow Flow PC0 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC0 sensor.boiler_pc0flow 5 0 1 79 1
Greenstar 30Ri Compact boiler 154 pc1flow Flow PC1 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC1 sensor.boiler_pc1flow 5 0 1 80 1
Greenstar 30Ri Compact boiler 154 pc1on PC1 boolean False binary_sensor.boiler_PC1 binary_sensor.boiler_pc1on 5 0 1 81 1
Greenstar 30Ri Compact boiler 154 pc1rate PC1 rate uint8 (>=0<=100) % False sensor.boiler_PC1_rate sensor.boiler_pc1rate 5 0 1 82 1
Greenstar 30Ri Compact boiler 154 meterheat meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_meter_heating sensor.boiler_meterheat 5 0 1/10 95 2
Greenstar 30Ri Compact boiler 154 dhw.meter meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_meter sensor.boiler_dhw_meter 5 9 1/10 2 2
Greenstar 30Ri Compact boiler 154 gasmeterheat gas meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_gas_meter_heating sensor.boiler_gasmeterheat 5 0 1/10 266 2
Greenstar 30Ri Compact boiler 154 dhw.gasmeter gas meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_gas_meter sensor.boiler_dhw_gasmeter 5 9 1/10 69 2
Greenstar 30Ri Compact boiler 154 nrgheat2 energy heating 2 uint24 (>=0<=1677721) kWh False sensor.boiler_energy_heating_2 sensor.boiler_nrgheat2 5 0 1/10 268 2
Greenstar 30Ri Compact boiler 154 dhw.nrg2 energy 2 uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_energy_2 sensor.boiler_dhw_nrg2 5 9 1/10 71 2
Greenstar 30Ri Compact boiler 154 dhw.tapactivated turn on/off boolean True switch.boiler_dhw_turn_on/off switch.boiler_dhw_tapactivated 5 9 1 28 1
Greenstar 30Ri Compact boiler 154 dhw.settemp set temperature uint8 (>=0<=254) C False sensor.boiler_dhw_set_temperature sensor.boiler_dhw_settemp 5 9 1 29 1
Greenstar 30Ri Compact boiler 154 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_temperature number.boiler_dhw_seltemp 5 9 1 30 1
Greenstar 30Ri Compact boiler 154 dhw.seltemplow selected lower temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_lower_temperature number.boiler_dhw_seltemplow 5 9 1 31 1
Greenstar 30Ri Compact boiler 154 dhw.tempecoplus selected eco+ temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_eco+_temperature number.boiler_dhw_tempecoplus 5 9 1 32 1
Greenstar 30Ri Compact boiler 154 dhw.seltempoff selected temperature for off uint8 (>=0<=254) C False sensor.boiler_dhw_selected_temperature_for_off sensor.boiler_dhw_seltempoff 5 9 1 33 1
Greenstar 30Ri Compact boiler 154 dhw.seltempsingle single charge temperature uint8 (>=0<=254) C True number.boiler_dhw_single_charge_temperature number.boiler_dhw_seltempsingle 5 9 1 34 1
Greenstar 30Ri Compact boiler 154 dhw.solartemp solar boiler temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_solar_boiler_temperature sensor.boiler_dhw_solartemp 5 9 1/10 35 1
Greenstar 30Ri Compact boiler 154 dhw.type type enum [off|flow|buffered flow|buffer|layered buffer] False sensor.boiler_dhw_type sensor.boiler_dhw_type 5 9 1 36 1
Greenstar 30Ri Compact boiler 154 dhw.comfort comfort enum [hot|eco|intelligent] True select.boiler_dhw_comfort select.boiler_dhw_comfort 5 9 1 37 1
Greenstar 30Ri Compact boiler 154 dhw.comfort1 comfort mode enum [high comfort|eco] True select.boiler_dhw_comfort_mode select.boiler_dhw_comfort1 5 9 1 38 1
Greenstar 30Ri Compact boiler 154 dhw.flowtempoffset flow temperature offset uint8 (>=0<=100) C True number.boiler_dhw_flow_temperature_offset number.boiler_dhw_flowtempoffset 5 9 1 39 1
Greenstar 30Ri Compact boiler 154 dhw.chargeoptimization charge optimization boolean True switch.boiler_dhw_charge_optimization switch.boiler_dhw_chargeoptimization 5 9 1 40 1
Greenstar 30Ri Compact boiler 154 dhw.maxpower max power uint8 (>=0<=254) % True number.boiler_dhw_max_power number.boiler_dhw_maxpower 5 9 1 41 1
Greenstar 30Ri Compact boiler 154 dhw.maxtemp maximum temperature uint8 (>=0<=80) C True number.boiler_dhw_maximum_temperature number.boiler_dhw_maxtemp 5 9 1 42 1
Greenstar 30Ri Compact boiler 154 dhw.circpump circulation pump available boolean True switch.boiler_dhw_circulation_pump_available switch.boiler_dhw_circpump 5 9 1 43 1
Greenstar 30Ri Compact boiler 154 dhw.chargetype charging type enum [chargepump|3-way valve] False sensor.boiler_dhw_charging_type sensor.boiler_dhw_chargetype 5 9 1 44 1
Greenstar 30Ri Compact boiler 154 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_on_temperature number.boiler_dhw_hyston 5 9 1 45 1
Greenstar 30Ri Compact boiler 154 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_off_temperature number.boiler_dhw_hystoff 5 9 1 46 1
Greenstar 30Ri Compact boiler 154 dhw.disinfectiontemp disinfection temperature uint8 (>=60<=80) C True number.boiler_dhw_disinfection_temperature number.boiler_dhw_disinfectiontemp 5 9 1 47 1
Greenstar 30Ri Compact boiler 154 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.boiler_dhw_circulation_pump_mode select.boiler_dhw_circmode 5 9 1 48 1
Greenstar 30Ri Compact boiler 154 dhw.circ circulation active boolean True switch.boiler_dhw_circulation_active switch.boiler_dhw_circ 5 9 1 49 1
Greenstar 30Ri Compact boiler 154 dhw.curtemp current intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_intern_temperature sensor.boiler_dhw_curtemp 5 9 1/10 50 1
Greenstar 30Ri Compact boiler 154 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_extern_temperature sensor.boiler_dhw_curtemp2 5 9 1/10 51 1
Greenstar 30Ri Compact boiler 154 dhw.curflow current tap water flow uint8 (>=0<=25) l/min False sensor.boiler_dhw_current_tap_water_flow sensor.boiler_dhw_curflow 5 9 1/10 52 1
Greenstar 30Ri Compact boiler 154 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_intern_temperature sensor.boiler_dhw_storagetemp1 5 9 1/10 53 1
Greenstar 30Ri Compact boiler 154 dhw.storagetemp2 storage extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_extern_temperature sensor.boiler_dhw_storagetemp2 5 9 1/10 54 1
Greenstar 30Ri Compact boiler 154 dhw.activated activated boolean True switch.boiler_dhw_activated switch.boiler_dhw_activated 5 9 1 55 1
Greenstar 30Ri Compact boiler 154 dhw.onetime one time charging boolean True switch.boiler_dhw_one_time_charging switch.boiler_dhw_onetime 5 9 1 56 1
Greenstar 30Ri Compact boiler 154 dhw.disinfecting disinfecting boolean True switch.boiler_dhw_disinfecting switch.boiler_dhw_disinfecting 5 9 1 57 1
Greenstar 30Ri Compact boiler 154 dhw.charging charging boolean False binary_sensor.boiler_dhw_charging binary_sensor.boiler_dhw_charging 5 9 1 58 1
Greenstar 30Ri Compact boiler 154 dhw.recharging recharging boolean False binary_sensor.boiler_dhw_recharging binary_sensor.boiler_dhw_recharging 5 9 1 59 1
Greenstar 30Ri Compact boiler 154 dhw.tempok temperature ok boolean False binary_sensor.boiler_dhw_temperature_ok binary_sensor.boiler_dhw_tempok 5 9 1 60 1
Greenstar 30Ri Compact boiler 154 dhw.active active boolean False binary_sensor.boiler_dhw_active binary_sensor.boiler_dhw_active 5 9 1 61 1
Greenstar 30Ri Compact boiler 154 dhw.3wayvalve 3-way valve active boolean False binary_sensor.boiler_dhw_3-way_valve_active binary_sensor.boiler_dhw_3wayvalve 5 9 1 62 1
Greenstar 30Ri Compact boiler 154 dhw.mixertemp mixer temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_mixer_temperature sensor.boiler_dhw_mixertemp 5 9 1/10 63 1
Greenstar 30Ri Compact boiler 154 dhw.cylmiddletemp cylinder middle temperature (TS3) uint16 (>=0<=3199) C False sensor.boiler_dhw_cylinder_middle_temperature_(TS3) sensor.boiler_dhw_cylmiddletemp 5 9 1/10 64 1
Greenstar 30Ri Compact boiler 154 dhw.starts starts uint24 (>=0<=16777214) False sensor.boiler_dhw_starts sensor.boiler_dhw_starts 5 9 1 65 2
Greenstar 30Ri Compact boiler 154 dhw.workm active time time (>=0<=16777214) minutes False sensor.boiler_dhw_active_time sensor.boiler_dhw_workm 5 9 1 67 2
Greenstar 30Ri Compact boiler 154 nompower nominal Power uint8 (>=0<=254) kW True number.boiler_nominal_Power number.boiler_nompower 5 0 1 270 1
Greenstar 30Ri Compact boiler 154 nrgtotal total energy uint24 (>=0<=167772) kWh False sensor.boiler_total_energy sensor.boiler_nrgtotal 5 0 1/100 83 2
Greenstar 30Ri Compact boiler 154 nrgheat energy heating uint24 (>=0<=10000000) kWh True number.boiler_energy_heating number.boiler_nrgheat 5 0 1/100 85 2
Greenstar 30Ri Compact boiler 154 dhw.nrg energy uint24 (>=0<=10000000) kWh True number.boiler_dhw_energy number.boiler_dhw_nrg 5 9 1/100 0 2
Suprapur-o boiler 155 reset reset cmd [-|maintenance|error|history|message] True sensor.boiler_reset sensor.boiler_reset 5 0 1 0 1
Suprapur-o boiler 155 heatingoff force heating off boolean True switch.boiler_force_heating_off switch.boiler_heatingoff 5 0 1 1 1
Suprapur-o boiler 155 heatingactive heating active boolean False binary_sensor.boiler_heating_active binary_sensor.boiler_heatingactive 5 0 1 2 1
Suprapur-o boiler 155 tapwateractive tapwater active boolean False binary_sensor.boiler_tapwater_active binary_sensor.boiler_tapwateractive 5 0 1 3 1
Suprapur-o boiler 155 selflowtemp selected flow temperature uint8 (>=0<=90) C True number.boiler_selected_flow_temperature number.boiler_selflowtemp 5 0 1 4 1
Suprapur-o boiler 155 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.boiler_heating_pump_modulation sensor.boiler_heatingpumpmod 5 0 1 5 1
Suprapur-o boiler 155 outdoortemp outside temperature int16 (>=-3199<=3199) C False sensor.boiler_outside_temperature sensor.boiler_outdoortemp 5 0 1/10 6 1
Suprapur-o boiler 155 curflowtemp current flow temperature uint16 (>=0<=3199) C False sensor.boiler_current_flow_temperature sensor.boiler_curflowtemp 5 0 1/10 7 1
Suprapur-o boiler 155 rettemp return temperature uint16 (>=0<=3199) C False sensor.boiler_return_temperature sensor.boiler_rettemp 5 0 1/10 8 1
Suprapur-o boiler 155 switchtemp mixing switch temperature uint16 (>=0<=3199) C False sensor.boiler_mixing_switch_temperature sensor.boiler_switchtemp 5 0 1/10 9 1
Suprapur-o boiler 155 syspress system pressure uint8 (>=0<=25) bar False sensor.boiler_system_pressure sensor.boiler_syspress 5 0 1/10 10 1
Suprapur-o boiler 155 boiltemp actual boiler temperature uint16 (>=0<=3199) C False sensor.boiler_actual_boiler_temperature sensor.boiler_boiltemp 5 0 1/10 11 1
Suprapur-o boiler 155 headertemp low loss header uint16 (>=0<=3199) C False sensor.boiler_low_loss_header sensor.boiler_headertemp 5 0 1/10 12 1
Suprapur-o boiler 155 exhausttemp exhaust temperature uint16 (>=0<=3199) C False sensor.boiler_exhaust_temperature sensor.boiler_exhausttemp 5 0 1/10 244 1
Suprapur-o boiler 155 burngas gas boolean False binary_sensor.boiler_gas binary_sensor.boiler_burngas 5 0 1 245 1
Suprapur-o boiler 155 burngas2 gas stage 2 boolean False binary_sensor.boiler_gas_stage_2 binary_sensor.boiler_burngas2 5 0 1 246 1
Suprapur-o boiler 155 flamecurr flame current uint16 (>=0<=3199) µA False sensor.boiler_flame_current sensor.boiler_flamecurr 5 0 1/10 247 1
Suprapur-o boiler 155 fanwork fan boolean False binary_sensor.boiler_fan binary_sensor.boiler_fanwork 5 0 1 248 1
Suprapur-o boiler 155 ignwork ignition boolean False binary_sensor.boiler_ignition binary_sensor.boiler_ignwork 5 0 1 249 1
Suprapur-o boiler 155 oilpreheat oil preheating boolean False binary_sensor.boiler_oil_preheating binary_sensor.boiler_oilpreheat 5 0 1 250 1
Suprapur-o boiler 155 burnminpower burner min power uint8 (>=0<=100) % True number.boiler_burner_min_power number.boiler_burnminpower 5 0 1 251 1
Suprapur-o boiler 155 burnmaxpower burner max power uint8 (>=0<=254) % True number.boiler_burner_max_power number.boiler_burnmaxpower 5 0 1 252 1
Suprapur-o boiler 155 burnminperiod burner min period uint8 (>=0<=120) minutes True number.boiler_burner_min_period number.boiler_burnminperiod 5 0 1 253 1
Suprapur-o boiler 155 absburnpow burner current power (absolute) uint8 (>=0<=100) % False sensor.boiler_burner_current_power_(absolute) sensor.boiler_absburnpow 5 0 1 254 1
Suprapur-o boiler 155 heatblock heating block uint16 (>=0<=3199) C False sensor.boiler_heating_block sensor.boiler_heatblock 5 0 1/10 255 1
Suprapur-o boiler 155 boilhyston hysteresis on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_on_temperature number.boiler_boilhyston 5 0 1 256 1
Suprapur-o boiler 155 boilhystoff hysteresis off temperature int8 (>=0<=20) C True number.boiler_hysteresis_off_temperature number.boiler_boilhystoff 5 0 1 257 1
Suprapur-o boiler 155 boil2hyston hysteresis stage 2 on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_stage_2_on_temperature number.boiler_boil2hyston 5 0 1 258 1
Suprapur-o boiler 155 boil2hystoff hysteresis stage 2 off temperature int8 (>=0<=20) C True number.boiler_hysteresis_stage_2_off_temperature number.boiler_boil2hystoff 5 0 1 259 1
Suprapur-o boiler 155 curveon heatingcurve on boolean True switch.boiler_heatingcurve_on switch.boiler_curveon 5 0 1 260 1
Suprapur-o boiler 155 curvebase heatingcurve base uint8 (>=20<=90) C True number.boiler_heatingcurve_base number.boiler_curvebase 5 0 1 261 1
Suprapur-o boiler 155 curveend heatingcurve end uint8 (>=20<=90) C True number.boiler_heatingcurve_end number.boiler_curveend 5 0 1 262 1
Suprapur-o boiler 155 summertemp summer temperature uint8 (>=0<=45) C True number.boiler_summer_temperature number.boiler_summertemp 5 0 1 263 1
Suprapur-o boiler 155 nofrostmode nofrost mode boolean True switch.boiler_nofrost_mode switch.boiler_nofrostmode 5 0 1 264 1
Suprapur-o boiler 155 nofrosttemp nofrost temperature uint8 (>=0<=10) C True number.boiler_nofrost_temperature number.boiler_nofrosttemp 5 0 1 265 1
Suprapur-o boiler 155 heatingactivated heating activated boolean True switch.boiler_heating_activated switch.boiler_heatingactivated 5 0 1 13 1
Suprapur-o boiler 155 heatingtemp heating temperature uint8 (>=0<=90) C True number.boiler_heating_temperature number.boiler_heatingtemp 5 0 1 14 1
Suprapur-o boiler 155 heatingpump heating pump boolean False binary_sensor.boiler_heating_pump binary_sensor.boiler_heatingpump 5 0 1 15 1
Suprapur-o boiler 155 pumpmodmax boiler pump max power uint8 (>=0<=100) % True number.boiler_boiler_pump_max_power number.boiler_pumpmodmax 5 0 1 16 1
Suprapur-o boiler 155 pumpmodmin boiler pump min power uint8 (>=0<=100) % True number.boiler_boiler_pump_min_power number.boiler_pumpmodmin 5 0 1 17 1
Suprapur-o boiler 155 pumpmode boiler pump mode enum [proportional|deltaP-1|deltaP-2|deltaP-3|deltaP-4] True select.boiler_boiler_pump_mode select.boiler_pumpmode 5 0 1 18 1
Suprapur-o boiler 155 pumpcharacter boiler pump characteristic enum [proportional|150mbar|200mbar|250mbar|300mbar|350mbar|400mbar] True select.boiler_boiler_pump_characteristic select.boiler_pumpcharacter 5 0 1 19 1
Suprapur-o boiler 155 pumpdelay pump delay uint8 (>=0<=60) minutes True number.boiler_pump_delay number.boiler_pumpdelay 5 0 1 20 1
Suprapur-o boiler 155 pumpontemp pump logic temperature uint8 (>=0<=60) C True number.boiler_pump_logic_temperature number.boiler_pumpontemp 5 0 1 21 1
Suprapur-o boiler 155 selburnpow burner selected max power uint8 (>=0<=254) % True number.boiler_burner_selected_max_power number.boiler_selburnpow 5 0 1 22 1
Suprapur-o boiler 155 curburnpow burner current power uint8 (>=0<=100) % False sensor.boiler_burner_current_power sensor.boiler_curburnpow 5 0 1 23 1
Suprapur-o boiler 155 burnstarts burner starts uint24 (>=0<=16777214) False sensor.boiler_burner_starts sensor.boiler_burnstarts 5 0 1 24 2
Suprapur-o boiler 155 burnworkmin total burner operating time time (>=0<=16777214) minutes False sensor.boiler_total_burner_operating_time sensor.boiler_burnworkmin 5 0 1 26 2
Suprapur-o boiler 155 burn2workmin burner stage 2 operating time time (>=0<=16777214) minutes False sensor.boiler_burner_stage_2_operating_time sensor.boiler_burn2workmin 5 0 1 28 2
Suprapur-o boiler 155 heatworkmin total heat operating time time (>=0<=16777214) minutes False sensor.boiler_total_heat_operating_time sensor.boiler_heatworkmin 5 0 1 30 2
Suprapur-o boiler 155 heatstarts burner starts heating uint24 (>=0<=16777214) False sensor.boiler_burner_starts_heating sensor.boiler_heatstarts 5 0 1 32 2
Suprapur-o boiler 155 ubauptime total UBA operating time time (>=0<=16777214) minutes False sensor.boiler_total_UBA_operating_time sensor.boiler_ubauptime 5 0 1 34 2
Suprapur-o boiler 155 lastcode last error code string False sensor.boiler_last_error_code sensor.boiler_lastcode 5 0 1 36 28
Suprapur-o boiler 155 servicecode service code string False sensor.boiler_service_code sensor.boiler_servicecode 5 0 1 64 2
Suprapur-o boiler 155 servicecodenumber service code number uint16 (>=0<=31999) False sensor.boiler_service_code_number sensor.boiler_servicecodenumber 5 0 1 66 1
Suprapur-o boiler 155 maintenancemessage maintenance message string False sensor.boiler_maintenance_message sensor.boiler_maintenancemessage 5 0 1 67 2
Suprapur-o boiler 155 maintenance maintenance scheduled enum [off|time|date|manual] True select.boiler_maintenance_scheduled select.boiler_maintenance 5 0 1 69 1
Suprapur-o boiler 155 maintenancetime time to next maintenance uint16 (>=0<=31999) hours True number.boiler_time_to_next_maintenance number.boiler_maintenancetime 5 0 1 70 1
Suprapur-o boiler 155 maintenancedate next maintenance date string True sensor.boiler_next_maintenance_date sensor.boiler_maintenancedate 5 0 1 71 6
Suprapur-o boiler 155 emergencyops emergency operation boolean True switch.boiler_emergency_operation switch.boiler_emergencyops 5 0 1 77 1
Suprapur-o boiler 155 emergencytemp emergency temperature uint8 (>=15<=70) C True number.boiler_emergency_temperature number.boiler_emergencytemp 5 0 1 78 1
Suprapur-o boiler 155 pc0flow Flow PC0 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC0 sensor.boiler_pc0flow 5 0 1 79 1
Suprapur-o boiler 155 pc1flow Flow PC1 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC1 sensor.boiler_pc1flow 5 0 1 80 1
Suprapur-o boiler 155 pc1on PC1 boolean False binary_sensor.boiler_PC1 binary_sensor.boiler_pc1on 5 0 1 81 1
Suprapur-o boiler 155 pc1rate PC1 rate uint8 (>=0<=100) % False sensor.boiler_PC1_rate sensor.boiler_pc1rate 5 0 1 82 1
Suprapur-o boiler 155 meterheat meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_meter_heating sensor.boiler_meterheat 5 0 1/10 95 2
Suprapur-o boiler 155 dhw.meter meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_meter sensor.boiler_dhw_meter 5 9 1/10 2 2
Suprapur-o boiler 155 gasmeterheat gas meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_gas_meter_heating sensor.boiler_gasmeterheat 5 0 1/10 266 2
Suprapur-o boiler 155 dhw.gasmeter gas meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_gas_meter sensor.boiler_dhw_gasmeter 5 9 1/10 69 2
Suprapur-o boiler 155 nrgheat2 energy heating 2 uint24 (>=0<=1677721) kWh False sensor.boiler_energy_heating_2 sensor.boiler_nrgheat2 5 0 1/10 268 2
Suprapur-o boiler 155 dhw.nrg2 energy 2 uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_energy_2 sensor.boiler_dhw_nrg2 5 9 1/10 71 2
Suprapur-o boiler 155 dhw.tapactivated turn on/off boolean True switch.boiler_dhw_turn_on/off switch.boiler_dhw_tapactivated 5 9 1 28 1
Suprapur-o boiler 155 dhw.settemp set temperature uint8 (>=0<=254) C False sensor.boiler_dhw_set_temperature sensor.boiler_dhw_settemp 5 9 1 29 1
Suprapur-o boiler 155 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_temperature number.boiler_dhw_seltemp 5 9 1 30 1
Suprapur-o boiler 155 dhw.seltemplow selected lower temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_lower_temperature number.boiler_dhw_seltemplow 5 9 1 31 1
Suprapur-o boiler 155 dhw.tempecoplus selected eco+ temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_eco+_temperature number.boiler_dhw_tempecoplus 5 9 1 32 1
Suprapur-o boiler 155 dhw.seltempoff selected temperature for off uint8 (>=0<=254) C False sensor.boiler_dhw_selected_temperature_for_off sensor.boiler_dhw_seltempoff 5 9 1 33 1
Suprapur-o boiler 155 dhw.seltempsingle single charge temperature uint8 (>=0<=254) C True number.boiler_dhw_single_charge_temperature number.boiler_dhw_seltempsingle 5 9 1 34 1
Suprapur-o boiler 155 dhw.solartemp solar boiler temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_solar_boiler_temperature sensor.boiler_dhw_solartemp 5 9 1/10 35 1
Suprapur-o boiler 155 dhw.type type enum [off|flow|buffered flow|buffer|layered buffer] False sensor.boiler_dhw_type sensor.boiler_dhw_type 5 9 1 36 1
Suprapur-o boiler 155 dhw.comfort comfort enum [hot|eco|intelligent] True select.boiler_dhw_comfort select.boiler_dhw_comfort 5 9 1 37 1
Suprapur-o boiler 155 dhw.comfort1 comfort mode enum [high comfort|eco] True select.boiler_dhw_comfort_mode select.boiler_dhw_comfort1 5 9 1 38 1
Suprapur-o boiler 155 dhw.flowtempoffset flow temperature offset uint8 (>=0<=100) C True number.boiler_dhw_flow_temperature_offset number.boiler_dhw_flowtempoffset 5 9 1 39 1
Suprapur-o boiler 155 dhw.chargeoptimization charge optimization boolean True switch.boiler_dhw_charge_optimization switch.boiler_dhw_chargeoptimization 5 9 1 40 1
Suprapur-o boiler 155 dhw.maxpower max power uint8 (>=0<=254) % True number.boiler_dhw_max_power number.boiler_dhw_maxpower 5 9 1 41 1
Suprapur-o boiler 155 dhw.maxtemp maximum temperature uint8 (>=0<=80) C True number.boiler_dhw_maximum_temperature number.boiler_dhw_maxtemp 5 9 1 42 1
Suprapur-o boiler 155 dhw.circpump circulation pump available boolean True switch.boiler_dhw_circulation_pump_available switch.boiler_dhw_circpump 5 9 1 43 1
Suprapur-o boiler 155 dhw.chargetype charging type enum [chargepump|3-way valve] False sensor.boiler_dhw_charging_type sensor.boiler_dhw_chargetype 5 9 1 44 1
Suprapur-o boiler 155 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_on_temperature number.boiler_dhw_hyston 5 9 1 45 1
Suprapur-o boiler 155 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_off_temperature number.boiler_dhw_hystoff 5 9 1 46 1
Suprapur-o boiler 155 dhw.disinfectiontemp disinfection temperature uint8 (>=60<=80) C True number.boiler_dhw_disinfection_temperature number.boiler_dhw_disinfectiontemp 5 9 1 47 1
Suprapur-o boiler 155 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.boiler_dhw_circulation_pump_mode select.boiler_dhw_circmode 5 9 1 48 1
Suprapur-o boiler 155 dhw.circ circulation active boolean True switch.boiler_dhw_circulation_active switch.boiler_dhw_circ 5 9 1 49 1
Suprapur-o boiler 155 dhw.curtemp current intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_intern_temperature sensor.boiler_dhw_curtemp 5 9 1/10 50 1
Suprapur-o boiler 155 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_extern_temperature sensor.boiler_dhw_curtemp2 5 9 1/10 51 1
Suprapur-o boiler 155 dhw.curflow current tap water flow uint8 (>=0<=25) l/min False sensor.boiler_dhw_current_tap_water_flow sensor.boiler_dhw_curflow 5 9 1/10 52 1
Suprapur-o boiler 155 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_intern_temperature sensor.boiler_dhw_storagetemp1 5 9 1/10 53 1
Suprapur-o boiler 155 dhw.storagetemp2 storage extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_extern_temperature sensor.boiler_dhw_storagetemp2 5 9 1/10 54 1
Suprapur-o boiler 155 dhw.activated activated boolean True switch.boiler_dhw_activated switch.boiler_dhw_activated 5 9 1 55 1
Suprapur-o boiler 155 dhw.onetime one time charging boolean True switch.boiler_dhw_one_time_charging switch.boiler_dhw_onetime 5 9 1 56 1
Suprapur-o boiler 155 dhw.disinfecting disinfecting boolean True switch.boiler_dhw_disinfecting switch.boiler_dhw_disinfecting 5 9 1 57 1
Suprapur-o boiler 155 dhw.charging charging boolean False binary_sensor.boiler_dhw_charging binary_sensor.boiler_dhw_charging 5 9 1 58 1
Suprapur-o boiler 155 dhw.recharging recharging boolean False binary_sensor.boiler_dhw_recharging binary_sensor.boiler_dhw_recharging 5 9 1 59 1
Suprapur-o boiler 155 dhw.tempok temperature ok boolean False binary_sensor.boiler_dhw_temperature_ok binary_sensor.boiler_dhw_tempok 5 9 1 60 1
Suprapur-o boiler 155 dhw.active active boolean False binary_sensor.boiler_dhw_active binary_sensor.boiler_dhw_active 5 9 1 61 1
Suprapur-o boiler 155 dhw.3wayvalve 3-way valve active boolean False binary_sensor.boiler_dhw_3-way_valve_active binary_sensor.boiler_dhw_3wayvalve 5 9 1 62 1
Suprapur-o boiler 155 dhw.mixertemp mixer temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_mixer_temperature sensor.boiler_dhw_mixertemp 5 9 1/10 63 1
Suprapur-o boiler 155 dhw.cylmiddletemp cylinder middle temperature (TS3) uint16 (>=0<=3199) C False sensor.boiler_dhw_cylinder_middle_temperature_(TS3) sensor.boiler_dhw_cylmiddletemp 5 9 1/10 64 1
Suprapur-o boiler 155 dhw.starts starts uint24 (>=0<=16777214) False sensor.boiler_dhw_starts sensor.boiler_dhw_starts 5 9 1 65 2
Suprapur-o boiler 155 dhw.workm active time time (>=0<=16777214) minutes False sensor.boiler_dhw_active_time sensor.boiler_dhw_workm 5 9 1 67 2
Suprapur-o boiler 155 nompower nominal Power uint8 (>=0<=254) kW True number.boiler_nominal_Power number.boiler_nompower 5 0 1 270 1
Suprapur-o boiler 155 nrgtotal total energy uint24 (>=0<=167772) kWh False sensor.boiler_total_energy sensor.boiler_nrgtotal 5 0 1/100 83 2
Suprapur-o boiler 155 nrgheat energy heating uint24 (>=0<=10000000) kWh True number.boiler_energy_heating number.boiler_nrgheat 5 0 1/100 85 2
Suprapur-o boiler 155 dhw.nrg energy uint24 (>=0<=10000000) kWh True number.boiler_dhw_energy number.boiler_dhw_nrg 5 9 1/100 0 2
Cerapur Aero boiler 167 reset reset cmd [-|maintenance|error|history|message] True sensor.boiler_reset sensor.boiler_reset 5 0 1 0 1
Cerapur Aero boiler 167 heatingoff force heating off boolean True switch.boiler_force_heating_off switch.boiler_heatingoff 5 0 1 1 1
Cerapur Aero boiler 167 heatingactive heating active boolean False binary_sensor.boiler_heating_active binary_sensor.boiler_heatingactive 5 0 1 2 1
Cerapur Aero boiler 167 tapwateractive tapwater active boolean False binary_sensor.boiler_tapwater_active binary_sensor.boiler_tapwateractive 5 0 1 3 1
Cerapur Aero boiler 167 selflowtemp selected flow temperature uint8 (>=0<=90) C True number.boiler_selected_flow_temperature number.boiler_selflowtemp 5 0 1 4 1
Cerapur Aero boiler 167 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.boiler_heating_pump_modulation sensor.boiler_heatingpumpmod 5 0 1 5 1
Cerapur Aero boiler 167 outdoortemp outside temperature int16 (>=-3199<=3199) C False sensor.boiler_outside_temperature sensor.boiler_outdoortemp 5 0 1/10 6 1
Cerapur Aero boiler 167 curflowtemp current flow temperature uint16 (>=0<=3199) C False sensor.boiler_current_flow_temperature sensor.boiler_curflowtemp 5 0 1/10 7 1
Cerapur Aero boiler 167 rettemp return temperature uint16 (>=0<=3199) C False sensor.boiler_return_temperature sensor.boiler_rettemp 5 0 1/10 8 1
Cerapur Aero boiler 167 switchtemp mixing switch temperature uint16 (>=0<=3199) C False sensor.boiler_mixing_switch_temperature sensor.boiler_switchtemp 5 0 1/10 9 1
Cerapur Aero boiler 167 syspress system pressure uint8 (>=0<=25) bar False sensor.boiler_system_pressure sensor.boiler_syspress 5 0 1/10 10 1
Cerapur Aero boiler 167 boiltemp actual boiler temperature uint16 (>=0<=3199) C False sensor.boiler_actual_boiler_temperature sensor.boiler_boiltemp 5 0 1/10 11 1
Cerapur Aero boiler 167 headertemp low loss header uint16 (>=0<=3199) C False sensor.boiler_low_loss_header sensor.boiler_headertemp 5 0 1/10 12 1
Cerapur Aero boiler 167 exhausttemp exhaust temperature uint16 (>=0<=3199) C False sensor.boiler_exhaust_temperature sensor.boiler_exhausttemp 5 0 1/10 244 1
Cerapur Aero boiler 167 burngas gas boolean False binary_sensor.boiler_gas binary_sensor.boiler_burngas 5 0 1 245 1
Cerapur Aero boiler 167 burngas2 gas stage 2 boolean False binary_sensor.boiler_gas_stage_2 binary_sensor.boiler_burngas2 5 0 1 246 1
Cerapur Aero boiler 167 flamecurr flame current uint16 (>=0<=3199) µA False sensor.boiler_flame_current sensor.boiler_flamecurr 5 0 1/10 247 1
Cerapur Aero boiler 167 fanwork fan boolean False binary_sensor.boiler_fan binary_sensor.boiler_fanwork 5 0 1 248 1
Cerapur Aero boiler 167 ignwork ignition boolean False binary_sensor.boiler_ignition binary_sensor.boiler_ignwork 5 0 1 249 1
Cerapur Aero boiler 167 oilpreheat oil preheating boolean False binary_sensor.boiler_oil_preheating binary_sensor.boiler_oilpreheat 5 0 1 250 1
Cerapur Aero boiler 167 burnminpower burner min power uint8 (>=0<=100) % True number.boiler_burner_min_power number.boiler_burnminpower 5 0 1 251 1
Cerapur Aero boiler 167 burnmaxpower burner max power uint8 (>=0<=254) % True number.boiler_burner_max_power number.boiler_burnmaxpower 5 0 1 252 1
Cerapur Aero boiler 167 burnminperiod burner min period uint8 (>=0<=120) minutes True number.boiler_burner_min_period number.boiler_burnminperiod 5 0 1 253 1
Cerapur Aero boiler 167 absburnpow burner current power (absolute) uint8 (>=0<=100) % False sensor.boiler_burner_current_power_(absolute) sensor.boiler_absburnpow 5 0 1 254 1
Cerapur Aero boiler 167 heatblock heating block uint16 (>=0<=3199) C False sensor.boiler_heating_block sensor.boiler_heatblock 5 0 1/10 255 1
Cerapur Aero boiler 167 boilhyston hysteresis on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_on_temperature number.boiler_boilhyston 5 0 1 256 1
Cerapur Aero boiler 167 boilhystoff hysteresis off temperature int8 (>=0<=20) C True number.boiler_hysteresis_off_temperature number.boiler_boilhystoff 5 0 1 257 1
Cerapur Aero boiler 167 boil2hyston hysteresis stage 2 on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_stage_2_on_temperature number.boiler_boil2hyston 5 0 1 258 1
Cerapur Aero boiler 167 boil2hystoff hysteresis stage 2 off temperature int8 (>=0<=20) C True number.boiler_hysteresis_stage_2_off_temperature number.boiler_boil2hystoff 5 0 1 259 1
Cerapur Aero boiler 167 curveon heatingcurve on boolean True switch.boiler_heatingcurve_on switch.boiler_curveon 5 0 1 260 1
Cerapur Aero boiler 167 curvebase heatingcurve base uint8 (>=20<=90) C True number.boiler_heatingcurve_base number.boiler_curvebase 5 0 1 261 1
Cerapur Aero boiler 167 curveend heatingcurve end uint8 (>=20<=90) C True number.boiler_heatingcurve_end number.boiler_curveend 5 0 1 262 1
Cerapur Aero boiler 167 summertemp summer temperature uint8 (>=0<=45) C True number.boiler_summer_temperature number.boiler_summertemp 5 0 1 263 1
Cerapur Aero boiler 167 nofrostmode nofrost mode boolean True switch.boiler_nofrost_mode switch.boiler_nofrostmode 5 0 1 264 1
Cerapur Aero boiler 167 nofrosttemp nofrost temperature uint8 (>=0<=10) C True number.boiler_nofrost_temperature number.boiler_nofrosttemp 5 0 1 265 1
Cerapur Aero boiler 167 heatingactivated heating activated boolean True switch.boiler_heating_activated switch.boiler_heatingactivated 5 0 1 13 1
Cerapur Aero boiler 167 heatingtemp heating temperature uint8 (>=0<=90) C True number.boiler_heating_temperature number.boiler_heatingtemp 5 0 1 14 1
Cerapur Aero boiler 167 heatingpump heating pump boolean False binary_sensor.boiler_heating_pump binary_sensor.boiler_heatingpump 5 0 1 15 1
Cerapur Aero boiler 167 pumpmodmax boiler pump max power uint8 (>=0<=100) % True number.boiler_boiler_pump_max_power number.boiler_pumpmodmax 5 0 1 16 1
Cerapur Aero boiler 167 pumpmodmin boiler pump min power uint8 (>=0<=100) % True number.boiler_boiler_pump_min_power number.boiler_pumpmodmin 5 0 1 17 1
Cerapur Aero boiler 167 pumpmode boiler pump mode enum [proportional|deltaP-1|deltaP-2|deltaP-3|deltaP-4] True select.boiler_boiler_pump_mode select.boiler_pumpmode 5 0 1 18 1
Cerapur Aero boiler 167 pumpcharacter boiler pump characteristic enum [proportional|150mbar|200mbar|250mbar|300mbar|350mbar|400mbar] True select.boiler_boiler_pump_characteristic select.boiler_pumpcharacter 5 0 1 19 1
Cerapur Aero boiler 167 pumpdelay pump delay uint8 (>=0<=60) minutes True number.boiler_pump_delay number.boiler_pumpdelay 5 0 1 20 1
Cerapur Aero boiler 167 pumpontemp pump logic temperature uint8 (>=0<=60) C True number.boiler_pump_logic_temperature number.boiler_pumpontemp 5 0 1 21 1
Cerapur Aero boiler 167 selburnpow burner selected max power uint8 (>=0<=254) % True number.boiler_burner_selected_max_power number.boiler_selburnpow 5 0 1 22 1
Cerapur Aero boiler 167 curburnpow burner current power uint8 (>=0<=100) % False sensor.boiler_burner_current_power sensor.boiler_curburnpow 5 0 1 23 1
Cerapur Aero boiler 167 burnstarts burner starts uint24 (>=0<=16777214) False sensor.boiler_burner_starts sensor.boiler_burnstarts 5 0 1 24 2
Cerapur Aero boiler 167 burnworkmin total burner operating time time (>=0<=16777214) minutes False sensor.boiler_total_burner_operating_time sensor.boiler_burnworkmin 5 0 1 26 2
Cerapur Aero boiler 167 burn2workmin burner stage 2 operating time time (>=0<=16777214) minutes False sensor.boiler_burner_stage_2_operating_time sensor.boiler_burn2workmin 5 0 1 28 2
Cerapur Aero boiler 167 heatworkmin total heat operating time time (>=0<=16777214) minutes False sensor.boiler_total_heat_operating_time sensor.boiler_heatworkmin 5 0 1 30 2
Cerapur Aero boiler 167 heatstarts burner starts heating uint24 (>=0<=16777214) False sensor.boiler_burner_starts_heating sensor.boiler_heatstarts 5 0 1 32 2
Cerapur Aero boiler 167 ubauptime total UBA operating time time (>=0<=16777214) minutes False sensor.boiler_total_UBA_operating_time sensor.boiler_ubauptime 5 0 1 34 2
Cerapur Aero boiler 167 lastcode last error code string False sensor.boiler_last_error_code sensor.boiler_lastcode 5 0 1 36 28
Cerapur Aero boiler 167 servicecode service code string False sensor.boiler_service_code sensor.boiler_servicecode 5 0 1 64 2
Cerapur Aero boiler 167 servicecodenumber service code number uint16 (>=0<=31999) False sensor.boiler_service_code_number sensor.boiler_servicecodenumber 5 0 1 66 1
Cerapur Aero boiler 167 maintenancemessage maintenance message string False sensor.boiler_maintenance_message sensor.boiler_maintenancemessage 5 0 1 67 2
Cerapur Aero boiler 167 maintenance maintenance scheduled enum [off|time|date|manual] True select.boiler_maintenance_scheduled select.boiler_maintenance 5 0 1 69 1
Cerapur Aero boiler 167 maintenancetime time to next maintenance uint16 (>=0<=31999) hours True number.boiler_time_to_next_maintenance number.boiler_maintenancetime 5 0 1 70 1
Cerapur Aero boiler 167 maintenancedate next maintenance date string True sensor.boiler_next_maintenance_date sensor.boiler_maintenancedate 5 0 1 71 6
Cerapur Aero boiler 167 emergencyops emergency operation boolean True switch.boiler_emergency_operation switch.boiler_emergencyops 5 0 1 77 1
Cerapur Aero boiler 167 emergencytemp emergency temperature uint8 (>=15<=70) C True number.boiler_emergency_temperature number.boiler_emergencytemp 5 0 1 78 1
Cerapur Aero boiler 167 pc0flow Flow PC0 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC0 sensor.boiler_pc0flow 5 0 1 79 1
Cerapur Aero boiler 167 pc1flow Flow PC1 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC1 sensor.boiler_pc1flow 5 0 1 80 1
Cerapur Aero boiler 167 pc1on PC1 boolean False binary_sensor.boiler_PC1 binary_sensor.boiler_pc1on 5 0 1 81 1
Cerapur Aero boiler 167 pc1rate PC1 rate uint8 (>=0<=100) % False sensor.boiler_PC1_rate sensor.boiler_pc1rate 5 0 1 82 1
Cerapur Aero boiler 167 meterheat meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_meter_heating sensor.boiler_meterheat 5 0 1/10 95 2
Cerapur Aero boiler 167 dhw.meter meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_meter sensor.boiler_dhw_meter 5 9 1/10 2 2
Cerapur Aero boiler 167 gasmeterheat gas meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_gas_meter_heating sensor.boiler_gasmeterheat 5 0 1/10 266 2
Cerapur Aero boiler 167 dhw.gasmeter gas meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_gas_meter sensor.boiler_dhw_gasmeter 5 9 1/10 69 2
Cerapur Aero boiler 167 nrgheat2 energy heating 2 uint24 (>=0<=1677721) kWh False sensor.boiler_energy_heating_2 sensor.boiler_nrgheat2 5 0 1/10 268 2
Cerapur Aero boiler 167 dhw.nrg2 energy 2 uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_energy_2 sensor.boiler_dhw_nrg2 5 9 1/10 71 2
Cerapur Aero boiler 167 dhw.tapactivated turn on/off boolean True switch.boiler_dhw_turn_on/off switch.boiler_dhw_tapactivated 5 9 1 28 1
Cerapur Aero boiler 167 dhw.settemp set temperature uint8 (>=0<=254) C False sensor.boiler_dhw_set_temperature sensor.boiler_dhw_settemp 5 9 1 29 1
Cerapur Aero boiler 167 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_temperature number.boiler_dhw_seltemp 5 9 1 30 1
Cerapur Aero boiler 167 dhw.seltemplow selected lower temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_lower_temperature number.boiler_dhw_seltemplow 5 9 1 31 1
Cerapur Aero boiler 167 dhw.tempecoplus selected eco+ temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_eco+_temperature number.boiler_dhw_tempecoplus 5 9 1 32 1
Cerapur Aero boiler 167 dhw.seltempoff selected temperature for off uint8 (>=0<=254) C False sensor.boiler_dhw_selected_temperature_for_off sensor.boiler_dhw_seltempoff 5 9 1 33 1
Cerapur Aero boiler 167 dhw.seltempsingle single charge temperature uint8 (>=0<=254) C True number.boiler_dhw_single_charge_temperature number.boiler_dhw_seltempsingle 5 9 1 34 1
Cerapur Aero boiler 167 dhw.solartemp solar boiler temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_solar_boiler_temperature sensor.boiler_dhw_solartemp 5 9 1/10 35 1
Cerapur Aero boiler 167 dhw.type type enum [off|flow|buffered flow|buffer|layered buffer] False sensor.boiler_dhw_type sensor.boiler_dhw_type 5 9 1 36 1
Cerapur Aero boiler 167 dhw.comfort comfort enum [hot|eco|intelligent] True select.boiler_dhw_comfort select.boiler_dhw_comfort 5 9 1 37 1
Cerapur Aero boiler 167 dhw.comfort1 comfort mode enum [high comfort|eco] True select.boiler_dhw_comfort_mode select.boiler_dhw_comfort1 5 9 1 38 1
Cerapur Aero boiler 167 dhw.flowtempoffset flow temperature offset uint8 (>=0<=100) C True number.boiler_dhw_flow_temperature_offset number.boiler_dhw_flowtempoffset 5 9 1 39 1
Cerapur Aero boiler 167 dhw.chargeoptimization charge optimization boolean True switch.boiler_dhw_charge_optimization switch.boiler_dhw_chargeoptimization 5 9 1 40 1
Cerapur Aero boiler 167 dhw.maxpower max power uint8 (>=0<=254) % True number.boiler_dhw_max_power number.boiler_dhw_maxpower 5 9 1 41 1
Cerapur Aero boiler 167 dhw.maxtemp maximum temperature uint8 (>=0<=80) C True number.boiler_dhw_maximum_temperature number.boiler_dhw_maxtemp 5 9 1 42 1
Cerapur Aero boiler 167 dhw.circpump circulation pump available boolean True switch.boiler_dhw_circulation_pump_available switch.boiler_dhw_circpump 5 9 1 43 1
Cerapur Aero boiler 167 dhw.chargetype charging type enum [chargepump|3-way valve] False sensor.boiler_dhw_charging_type sensor.boiler_dhw_chargetype 5 9 1 44 1
Cerapur Aero boiler 167 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_on_temperature number.boiler_dhw_hyston 5 9 1 45 1
Cerapur Aero boiler 167 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_off_temperature number.boiler_dhw_hystoff 5 9 1 46 1
Cerapur Aero boiler 167 dhw.disinfectiontemp disinfection temperature uint8 (>=60<=80) C True number.boiler_dhw_disinfection_temperature number.boiler_dhw_disinfectiontemp 5 9 1 47 1
Cerapur Aero boiler 167 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.boiler_dhw_circulation_pump_mode select.boiler_dhw_circmode 5 9 1 48 1
Cerapur Aero boiler 167 dhw.circ circulation active boolean True switch.boiler_dhw_circulation_active switch.boiler_dhw_circ 5 9 1 49 1
Cerapur Aero boiler 167 dhw.curtemp current intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_intern_temperature sensor.boiler_dhw_curtemp 5 9 1/10 50 1
Cerapur Aero boiler 167 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_extern_temperature sensor.boiler_dhw_curtemp2 5 9 1/10 51 1
Cerapur Aero boiler 167 dhw.curflow current tap water flow uint8 (>=0<=25) l/min False sensor.boiler_dhw_current_tap_water_flow sensor.boiler_dhw_curflow 5 9 1/10 52 1
Cerapur Aero boiler 167 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_intern_temperature sensor.boiler_dhw_storagetemp1 5 9 1/10 53 1
Cerapur Aero boiler 167 dhw.storagetemp2 storage extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_extern_temperature sensor.boiler_dhw_storagetemp2 5 9 1/10 54 1
Cerapur Aero boiler 167 dhw.activated activated boolean True switch.boiler_dhw_activated switch.boiler_dhw_activated 5 9 1 55 1
Cerapur Aero boiler 167 dhw.onetime one time charging boolean True switch.boiler_dhw_one_time_charging switch.boiler_dhw_onetime 5 9 1 56 1
Cerapur Aero boiler 167 dhw.disinfecting disinfecting boolean True switch.boiler_dhw_disinfecting switch.boiler_dhw_disinfecting 5 9 1 57 1
Cerapur Aero boiler 167 dhw.charging charging boolean False binary_sensor.boiler_dhw_charging binary_sensor.boiler_dhw_charging 5 9 1 58 1
Cerapur Aero boiler 167 dhw.recharging recharging boolean False binary_sensor.boiler_dhw_recharging binary_sensor.boiler_dhw_recharging 5 9 1 59 1
Cerapur Aero boiler 167 dhw.tempok temperature ok boolean False binary_sensor.boiler_dhw_temperature_ok binary_sensor.boiler_dhw_tempok 5 9 1 60 1
Cerapur Aero boiler 167 dhw.active active boolean False binary_sensor.boiler_dhw_active binary_sensor.boiler_dhw_active 5 9 1 61 1
Cerapur Aero boiler 167 dhw.3wayvalve 3-way valve active boolean False binary_sensor.boiler_dhw_3-way_valve_active binary_sensor.boiler_dhw_3wayvalve 5 9 1 62 1
Cerapur Aero boiler 167 dhw.mixertemp mixer temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_mixer_temperature sensor.boiler_dhw_mixertemp 5 9 1/10 63 1
Cerapur Aero boiler 167 dhw.cylmiddletemp cylinder middle temperature (TS3) uint16 (>=0<=3199) C False sensor.boiler_dhw_cylinder_middle_temperature_(TS3) sensor.boiler_dhw_cylmiddletemp 5 9 1/10 64 1
Cerapur Aero boiler 167 dhw.starts starts uint24 (>=0<=16777214) False sensor.boiler_dhw_starts sensor.boiler_dhw_starts 5 9 1 65 2
Cerapur Aero boiler 167 dhw.workm active time time (>=0<=16777214) minutes False sensor.boiler_dhw_active_time sensor.boiler_dhw_workm 5 9 1 67 2
Cerapur Aero boiler 167 nompower nominal Power uint8 (>=0<=254) kW True number.boiler_nominal_Power number.boiler_nompower 5 0 1 270 1
Cerapur Aero boiler 167 nrgtotal total energy uint24 (>=0<=167772) kWh False sensor.boiler_total_energy sensor.boiler_nrgtotal 5 0 1/100 83 2
Cerapur Aero boiler 167 nrgheat energy heating uint24 (>=0<=10000000) kWh True number.boiler_energy_heating number.boiler_nrgheat 5 0 1/100 85 2
Cerapur Aero boiler 167 dhw.nrg energy uint24 (>=0<=10000000) kWh True number.boiler_dhw_energy number.boiler_dhw_nrg 5 9 1/100 0 2
Hybrid Heatpump boiler 168 reset reset cmd [-|maintenance|error|history|message] True sensor.boiler_reset sensor.boiler_reset 5 0 1 0 1
Hybrid Heatpump boiler 168 heatingoff force heating off boolean True switch.boiler_force_heating_off switch.boiler_heatingoff 5 0 1 1 1
Hybrid Heatpump boiler 168 heatingactive heating active boolean False binary_sensor.boiler_heating_active binary_sensor.boiler_heatingactive 5 0 1 2 1
Hybrid Heatpump boiler 168 tapwateractive tapwater active boolean False binary_sensor.boiler_tapwater_active binary_sensor.boiler_tapwateractive 5 0 1 3 1
Hybrid Heatpump boiler 168 selflowtemp selected flow temperature uint8 (>=0<=90) C True number.boiler_selected_flow_temperature number.boiler_selflowtemp 5 0 1 4 1
Hybrid Heatpump boiler 168 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.boiler_heating_pump_modulation sensor.boiler_heatingpumpmod 5 0 1 5 1
Hybrid Heatpump boiler 168 outdoortemp outside temperature int16 (>=-3199<=3199) C False sensor.boiler_outside_temperature sensor.boiler_outdoortemp 5 0 1/10 6 1
Hybrid Heatpump boiler 168 curflowtemp current flow temperature uint16 (>=0<=3199) C False sensor.boiler_current_flow_temperature sensor.boiler_curflowtemp 5 0 1/10 7 1
Hybrid Heatpump boiler 168 rettemp return temperature uint16 (>=0<=3199) C False sensor.boiler_return_temperature sensor.boiler_rettemp 5 0 1/10 8 1
Hybrid Heatpump boiler 168 switchtemp mixing switch temperature uint16 (>=0<=3199) C False sensor.boiler_mixing_switch_temperature sensor.boiler_switchtemp 5 0 1/10 9 1
Hybrid Heatpump boiler 168 syspress system pressure uint8 (>=0<=25) bar False sensor.boiler_system_pressure sensor.boiler_syspress 5 0 1/10 10 1
Hybrid Heatpump boiler 168 boiltemp actual boiler temperature uint16 (>=0<=3199) C False sensor.boiler_actual_boiler_temperature sensor.boiler_boiltemp 5 0 1/10 11 1
Hybrid Heatpump boiler 168 headertemp low loss header uint16 (>=0<=3199) C False sensor.boiler_low_loss_header sensor.boiler_headertemp 5 0 1/10 12 1
Hybrid Heatpump boiler 168 exhausttemp exhaust temperature uint16 (>=0<=3199) C False sensor.boiler_exhaust_temperature sensor.boiler_exhausttemp 5 0 1/10 244 1
Hybrid Heatpump boiler 168 burngas gas boolean False binary_sensor.boiler_gas binary_sensor.boiler_burngas 5 0 1 245 1
Hybrid Heatpump boiler 168 burngas2 gas stage 2 boolean False binary_sensor.boiler_gas_stage_2 binary_sensor.boiler_burngas2 5 0 1 246 1
Hybrid Heatpump boiler 168 flamecurr flame current uint16 (>=0<=3199) µA False sensor.boiler_flame_current sensor.boiler_flamecurr 5 0 1/10 247 1
Hybrid Heatpump boiler 168 fanwork fan boolean False binary_sensor.boiler_fan binary_sensor.boiler_fanwork 5 0 1 248 1
Hybrid Heatpump boiler 168 ignwork ignition boolean False binary_sensor.boiler_ignition binary_sensor.boiler_ignwork 5 0 1 249 1
Hybrid Heatpump boiler 168 oilpreheat oil preheating boolean False binary_sensor.boiler_oil_preheating binary_sensor.boiler_oilpreheat 5 0 1 250 1
Hybrid Heatpump boiler 168 burnminpower burner min power uint8 (>=0<=100) % True number.boiler_burner_min_power number.boiler_burnminpower 5 0 1 251 1
Hybrid Heatpump boiler 168 burnmaxpower burner max power uint8 (>=0<=254) % True number.boiler_burner_max_power number.boiler_burnmaxpower 5 0 1 252 1
Hybrid Heatpump boiler 168 burnminperiod burner min period uint8 (>=0<=120) minutes True number.boiler_burner_min_period number.boiler_burnminperiod 5 0 1 253 1
Hybrid Heatpump boiler 168 absburnpow burner current power (absolute) uint8 (>=0<=100) % False sensor.boiler_burner_current_power_(absolute) sensor.boiler_absburnpow 5 0 1 254 1
Hybrid Heatpump boiler 168 heatblock heating block uint16 (>=0<=3199) C False sensor.boiler_heating_block sensor.boiler_heatblock 5 0 1/10 255 1
Hybrid Heatpump boiler 168 boilhyston hysteresis on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_on_temperature number.boiler_boilhyston 5 0 1 256 1
Hybrid Heatpump boiler 168 boilhystoff hysteresis off temperature int8 (>=0<=20) C True number.boiler_hysteresis_off_temperature number.boiler_boilhystoff 5 0 1 257 1
Hybrid Heatpump boiler 168 boil2hyston hysteresis stage 2 on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_stage_2_on_temperature number.boiler_boil2hyston 5 0 1 258 1
Hybrid Heatpump boiler 168 boil2hystoff hysteresis stage 2 off temperature int8 (>=0<=20) C True number.boiler_hysteresis_stage_2_off_temperature number.boiler_boil2hystoff 5 0 1 259 1
Hybrid Heatpump boiler 168 curveon heatingcurve on boolean True switch.boiler_heatingcurve_on switch.boiler_curveon 5 0 1 260 1
Hybrid Heatpump boiler 168 curvebase heatingcurve base uint8 (>=20<=90) C True number.boiler_heatingcurve_base number.boiler_curvebase 5 0 1 261 1
Hybrid Heatpump boiler 168 curveend heatingcurve end uint8 (>=20<=90) C True number.boiler_heatingcurve_end number.boiler_curveend 5 0 1 262 1
Hybrid Heatpump boiler 168 summertemp summer temperature uint8 (>=0<=45) C True number.boiler_summer_temperature number.boiler_summertemp 5 0 1 263 1
Hybrid Heatpump boiler 168 nofrostmode nofrost mode boolean True switch.boiler_nofrost_mode switch.boiler_nofrostmode 5 0 1 264 1
Hybrid Heatpump boiler 168 nofrosttemp nofrost temperature uint8 (>=0<=10) C True number.boiler_nofrost_temperature number.boiler_nofrosttemp 5 0 1 265 1
Hybrid Heatpump boiler 168 heatingactivated heating activated boolean True switch.boiler_heating_activated switch.boiler_heatingactivated 5 0 1 13 1
Hybrid Heatpump boiler 168 heatingtemp heating temperature uint8 (>=0<=90) C True number.boiler_heating_temperature number.boiler_heatingtemp 5 0 1 14 1
Hybrid Heatpump boiler 168 heatingpump heating pump boolean False binary_sensor.boiler_heating_pump binary_sensor.boiler_heatingpump 5 0 1 15 1
Hybrid Heatpump boiler 168 pumpmodmax boiler pump max power uint8 (>=0<=100) % True number.boiler_boiler_pump_max_power number.boiler_pumpmodmax 5 0 1 16 1
Hybrid Heatpump boiler 168 pumpmodmin boiler pump min power uint8 (>=0<=100) % True number.boiler_boiler_pump_min_power number.boiler_pumpmodmin 5 0 1 17 1
Hybrid Heatpump boiler 168 pumpmode boiler pump mode enum [proportional|deltaP-1|deltaP-2|deltaP-3|deltaP-4] True select.boiler_boiler_pump_mode select.boiler_pumpmode 5 0 1 18 1
Hybrid Heatpump boiler 168 pumpcharacter boiler pump characteristic enum [proportional|150mbar|200mbar|250mbar|300mbar|350mbar|400mbar] True select.boiler_boiler_pump_characteristic select.boiler_pumpcharacter 5 0 1 19 1
Hybrid Heatpump boiler 168 pumpdelay pump delay uint8 (>=0<=60) minutes True number.boiler_pump_delay number.boiler_pumpdelay 5 0 1 20 1
Hybrid Heatpump boiler 168 pumpontemp pump logic temperature uint8 (>=0<=60) C True number.boiler_pump_logic_temperature number.boiler_pumpontemp 5 0 1 21 1
Hybrid Heatpump boiler 168 selburnpow burner selected max power uint8 (>=0<=254) % True number.boiler_burner_selected_max_power number.boiler_selburnpow 5 0 1 22 1
Hybrid Heatpump boiler 168 curburnpow burner current power uint8 (>=0<=100) % False sensor.boiler_burner_current_power sensor.boiler_curburnpow 5 0 1 23 1
Hybrid Heatpump boiler 168 burnstarts burner starts uint24 (>=0<=16777214) False sensor.boiler_burner_starts sensor.boiler_burnstarts 5 0 1 24 2
Hybrid Heatpump boiler 168 burnworkmin total burner operating time time (>=0<=16777214) minutes False sensor.boiler_total_burner_operating_time sensor.boiler_burnworkmin 5 0 1 26 2
Hybrid Heatpump boiler 168 burn2workmin burner stage 2 operating time time (>=0<=16777214) minutes False sensor.boiler_burner_stage_2_operating_time sensor.boiler_burn2workmin 5 0 1 28 2
Hybrid Heatpump boiler 168 heatworkmin total heat operating time time (>=0<=16777214) minutes False sensor.boiler_total_heat_operating_time sensor.boiler_heatworkmin 5 0 1 30 2
Hybrid Heatpump boiler 168 heatstarts burner starts heating uint24 (>=0<=16777214) False sensor.boiler_burner_starts_heating sensor.boiler_heatstarts 5 0 1 32 2
Hybrid Heatpump boiler 168 ubauptime total UBA operating time time (>=0<=16777214) minutes False sensor.boiler_total_UBA_operating_time sensor.boiler_ubauptime 5 0 1 34 2
Hybrid Heatpump boiler 168 lastcode last error code string False sensor.boiler_last_error_code sensor.boiler_lastcode 5 0 1 36 28
Hybrid Heatpump boiler 168 servicecode service code string False sensor.boiler_service_code sensor.boiler_servicecode 5 0 1 64 2
Hybrid Heatpump boiler 168 servicecodenumber service code number uint16 (>=0<=31999) False sensor.boiler_service_code_number sensor.boiler_servicecodenumber 5 0 1 66 1
Hybrid Heatpump boiler 168 maintenancemessage maintenance message string False sensor.boiler_maintenance_message sensor.boiler_maintenancemessage 5 0 1 67 2
Hybrid Heatpump boiler 168 maintenance maintenance scheduled enum [off|time|date|manual] True select.boiler_maintenance_scheduled select.boiler_maintenance 5 0 1 69 1
Hybrid Heatpump boiler 168 maintenancetime time to next maintenance uint16 (>=0<=31999) hours True number.boiler_time_to_next_maintenance number.boiler_maintenancetime 5 0 1 70 1
Hybrid Heatpump boiler 168 maintenancedate next maintenance date string True sensor.boiler_next_maintenance_date sensor.boiler_maintenancedate 5 0 1 71 6
Hybrid Heatpump boiler 168 emergencyops emergency operation boolean True switch.boiler_emergency_operation switch.boiler_emergencyops 5 0 1 77 1
Hybrid Heatpump boiler 168 emergencytemp emergency temperature uint8 (>=15<=70) C True number.boiler_emergency_temperature number.boiler_emergencytemp 5 0 1 78 1
Hybrid Heatpump boiler 168 pc0flow Flow PC0 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC0 sensor.boiler_pc0flow 5 0 1 79 1
Hybrid Heatpump boiler 168 pc1flow Flow PC1 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC1 sensor.boiler_pc1flow 5 0 1 80 1
Hybrid Heatpump boiler 168 pc1on PC1 boolean False binary_sensor.boiler_PC1 binary_sensor.boiler_pc1on 5 0 1 81 1
Hybrid Heatpump boiler 168 pc1rate PC1 rate uint8 (>=0<=100) % False sensor.boiler_PC1_rate sensor.boiler_pc1rate 5 0 1 82 1
Hybrid Heatpump boiler 168 meterheat meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_meter_heating sensor.boiler_meterheat 5 0 1/10 95 2
Hybrid Heatpump boiler 168 dhw.meter meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_meter sensor.boiler_dhw_meter 5 9 1/10 2 2
Hybrid Heatpump boiler 168 gasmeterheat gas meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_gas_meter_heating sensor.boiler_gasmeterheat 5 0 1/10 266 2
Hybrid Heatpump boiler 168 dhw.gasmeter gas meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_gas_meter sensor.boiler_dhw_gasmeter 5 9 1/10 69 2
Hybrid Heatpump boiler 168 nrgheat2 energy heating 2 uint24 (>=0<=1677721) kWh False sensor.boiler_energy_heating_2 sensor.boiler_nrgheat2 5 0 1/10 268 2
Hybrid Heatpump boiler 168 dhw.nrg2 energy 2 uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_energy_2 sensor.boiler_dhw_nrg2 5 9 1/10 71 2
Hybrid Heatpump boiler 168 dhw.tapactivated turn on/off boolean True switch.boiler_dhw_turn_on/off switch.boiler_dhw_tapactivated 5 9 1 28 1
Hybrid Heatpump boiler 168 dhw.settemp set temperature uint8 (>=0<=254) C False sensor.boiler_dhw_set_temperature sensor.boiler_dhw_settemp 5 9 1 29 1
Hybrid Heatpump boiler 168 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_temperature number.boiler_dhw_seltemp 5 9 1 30 1
Hybrid Heatpump boiler 168 dhw.seltemplow selected lower temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_lower_temperature number.boiler_dhw_seltemplow 5 9 1 31 1
Hybrid Heatpump boiler 168 dhw.tempecoplus selected eco+ temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_eco+_temperature number.boiler_dhw_tempecoplus 5 9 1 32 1
Hybrid Heatpump boiler 168 dhw.seltempoff selected temperature for off uint8 (>=0<=254) C False sensor.boiler_dhw_selected_temperature_for_off sensor.boiler_dhw_seltempoff 5 9 1 33 1
Hybrid Heatpump boiler 168 dhw.seltempsingle single charge temperature uint8 (>=0<=254) C True number.boiler_dhw_single_charge_temperature number.boiler_dhw_seltempsingle 5 9 1 34 1
Hybrid Heatpump boiler 168 dhw.solartemp solar boiler temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_solar_boiler_temperature sensor.boiler_dhw_solartemp 5 9 1/10 35 1
Hybrid Heatpump boiler 168 dhw.type type enum [off|flow|buffered flow|buffer|layered buffer] False sensor.boiler_dhw_type sensor.boiler_dhw_type 5 9 1 36 1
Hybrid Heatpump boiler 168 dhw.comfort comfort enum [hot|eco|intelligent] True select.boiler_dhw_comfort select.boiler_dhw_comfort 5 9 1 37 1
Hybrid Heatpump boiler 168 dhw.comfort1 comfort mode enum [high comfort|eco] True select.boiler_dhw_comfort_mode select.boiler_dhw_comfort1 5 9 1 38 1
Hybrid Heatpump boiler 168 dhw.flowtempoffset flow temperature offset uint8 (>=0<=100) C True number.boiler_dhw_flow_temperature_offset number.boiler_dhw_flowtempoffset 5 9 1 39 1
Hybrid Heatpump boiler 168 dhw.chargeoptimization charge optimization boolean True switch.boiler_dhw_charge_optimization switch.boiler_dhw_chargeoptimization 5 9 1 40 1
Hybrid Heatpump boiler 168 dhw.maxpower max power uint8 (>=0<=254) % True number.boiler_dhw_max_power number.boiler_dhw_maxpower 5 9 1 41 1
Hybrid Heatpump boiler 168 dhw.maxtemp maximum temperature uint8 (>=0<=80) C True number.boiler_dhw_maximum_temperature number.boiler_dhw_maxtemp 5 9 1 42 1
Hybrid Heatpump boiler 168 dhw.circpump circulation pump available boolean True switch.boiler_dhw_circulation_pump_available switch.boiler_dhw_circpump 5 9 1 43 1
Hybrid Heatpump boiler 168 dhw.chargetype charging type enum [chargepump|3-way valve] False sensor.boiler_dhw_charging_type sensor.boiler_dhw_chargetype 5 9 1 44 1
Hybrid Heatpump boiler 168 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_on_temperature number.boiler_dhw_hyston 5 9 1 45 1
Hybrid Heatpump boiler 168 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_off_temperature number.boiler_dhw_hystoff 5 9 1 46 1
Hybrid Heatpump boiler 168 dhw.disinfectiontemp disinfection temperature uint8 (>=60<=80) C True number.boiler_dhw_disinfection_temperature number.boiler_dhw_disinfectiontemp 5 9 1 47 1
Hybrid Heatpump boiler 168 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.boiler_dhw_circulation_pump_mode select.boiler_dhw_circmode 5 9 1 48 1
Hybrid Heatpump boiler 168 dhw.circ circulation active boolean True switch.boiler_dhw_circulation_active switch.boiler_dhw_circ 5 9 1 49 1
Hybrid Heatpump boiler 168 dhw.curtemp current intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_intern_temperature sensor.boiler_dhw_curtemp 5 9 1/10 50 1
Hybrid Heatpump boiler 168 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_extern_temperature sensor.boiler_dhw_curtemp2 5 9 1/10 51 1
Hybrid Heatpump boiler 168 dhw.curflow current tap water flow uint8 (>=0<=25) l/min False sensor.boiler_dhw_current_tap_water_flow sensor.boiler_dhw_curflow 5 9 1/10 52 1
Hybrid Heatpump boiler 168 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_intern_temperature sensor.boiler_dhw_storagetemp1 5 9 1/10 53 1
Hybrid Heatpump boiler 168 dhw.storagetemp2 storage extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_extern_temperature sensor.boiler_dhw_storagetemp2 5 9 1/10 54 1
Hybrid Heatpump boiler 168 dhw.activated activated boolean True switch.boiler_dhw_activated switch.boiler_dhw_activated 5 9 1 55 1
Hybrid Heatpump boiler 168 dhw.onetime one time charging boolean True switch.boiler_dhw_one_time_charging switch.boiler_dhw_onetime 5 9 1 56 1
Hybrid Heatpump boiler 168 dhw.disinfecting disinfecting boolean True switch.boiler_dhw_disinfecting switch.boiler_dhw_disinfecting 5 9 1 57 1
Hybrid Heatpump boiler 168 dhw.charging charging boolean False binary_sensor.boiler_dhw_charging binary_sensor.boiler_dhw_charging 5 9 1 58 1
Hybrid Heatpump boiler 168 dhw.recharging recharging boolean False binary_sensor.boiler_dhw_recharging binary_sensor.boiler_dhw_recharging 5 9 1 59 1
Hybrid Heatpump boiler 168 dhw.tempok temperature ok boolean False binary_sensor.boiler_dhw_temperature_ok binary_sensor.boiler_dhw_tempok 5 9 1 60 1
Hybrid Heatpump boiler 168 dhw.active active boolean False binary_sensor.boiler_dhw_active binary_sensor.boiler_dhw_active 5 9 1 61 1
Hybrid Heatpump boiler 168 dhw.3wayvalve 3-way valve active boolean False binary_sensor.boiler_dhw_3-way_valve_active binary_sensor.boiler_dhw_3wayvalve 5 9 1 62 1
Hybrid Heatpump boiler 168 dhw.mixertemp mixer temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_mixer_temperature sensor.boiler_dhw_mixertemp 5 9 1/10 63 1
Hybrid Heatpump boiler 168 dhw.cylmiddletemp cylinder middle temperature (TS3) uint16 (>=0<=3199) C False sensor.boiler_dhw_cylinder_middle_temperature_(TS3) sensor.boiler_dhw_cylmiddletemp 5 9 1/10 64 1
Hybrid Heatpump boiler 168 dhw.starts starts uint24 (>=0<=16777214) False sensor.boiler_dhw_starts sensor.boiler_dhw_starts 5 9 1 65 2
Hybrid Heatpump boiler 168 dhw.workm active time time (>=0<=16777214) minutes False sensor.boiler_dhw_active_time sensor.boiler_dhw_workm 5 9 1 67 2
Hybrid Heatpump boiler 168 nompower nominal Power uint8 (>=0<=254) kW True number.boiler_nominal_Power number.boiler_nompower 5 0 1 270 1
Hybrid Heatpump boiler 168 nrgtotal total energy uint24 (>=0<=167772) kWh False sensor.boiler_total_energy sensor.boiler_nrgtotal 5 0 1/100 83 2
Hybrid Heatpump boiler 168 nrgheat energy heating uint24 (>=0<=10000000) kWh True number.boiler_energy_heating number.boiler_nrgheat 5 0 1/100 85 2
Hybrid Heatpump boiler 168 dhw.nrg energy uint24 (>=0<=10000000) kWh True number.boiler_dhw_energy number.boiler_dhw_nrg 5 9 1/100 0 2
Logano GB212 boiler 170 reset reset cmd [-|maintenance|error|history|message] True sensor.boiler_reset sensor.boiler_reset 5 0 1 0 1
Logano GB212 boiler 170 heatingoff force heating off boolean True switch.boiler_force_heating_off switch.boiler_heatingoff 5 0 1 1 1
Logano GB212 boiler 170 heatingactive heating active boolean False binary_sensor.boiler_heating_active binary_sensor.boiler_heatingactive 5 0 1 2 1
Logano GB212 boiler 170 tapwateractive tapwater active boolean False binary_sensor.boiler_tapwater_active binary_sensor.boiler_tapwateractive 5 0 1 3 1
Logano GB212 boiler 170 selflowtemp selected flow temperature uint8 (>=0<=90) C True number.boiler_selected_flow_temperature number.boiler_selflowtemp 5 0 1 4 1
Logano GB212 boiler 170 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.boiler_heating_pump_modulation sensor.boiler_heatingpumpmod 5 0 1 5 1
Logano GB212 boiler 170 outdoortemp outside temperature int16 (>=-3199<=3199) C False sensor.boiler_outside_temperature sensor.boiler_outdoortemp 5 0 1/10 6 1
Logano GB212 boiler 170 curflowtemp current flow temperature uint16 (>=0<=3199) C False sensor.boiler_current_flow_temperature sensor.boiler_curflowtemp 5 0 1/10 7 1
Logano GB212 boiler 170 rettemp return temperature uint16 (>=0<=3199) C False sensor.boiler_return_temperature sensor.boiler_rettemp 5 0 1/10 8 1
Logano GB212 boiler 170 switchtemp mixing switch temperature uint16 (>=0<=3199) C False sensor.boiler_mixing_switch_temperature sensor.boiler_switchtemp 5 0 1/10 9 1
Logano GB212 boiler 170 syspress system pressure uint8 (>=0<=25) bar False sensor.boiler_system_pressure sensor.boiler_syspress 5 0 1/10 10 1
Logano GB212 boiler 170 boiltemp actual boiler temperature uint16 (>=0<=3199) C False sensor.boiler_actual_boiler_temperature sensor.boiler_boiltemp 5 0 1/10 11 1
Logano GB212 boiler 170 headertemp low loss header uint16 (>=0<=3199) C False sensor.boiler_low_loss_header sensor.boiler_headertemp 5 0 1/10 12 1
Logano GB212 boiler 170 exhausttemp exhaust temperature uint16 (>=0<=3199) C False sensor.boiler_exhaust_temperature sensor.boiler_exhausttemp 5 0 1/10 244 1
Logano GB212 boiler 170 burngas gas boolean False binary_sensor.boiler_gas binary_sensor.boiler_burngas 5 0 1 245 1
Logano GB212 boiler 170 burngas2 gas stage 2 boolean False binary_sensor.boiler_gas_stage_2 binary_sensor.boiler_burngas2 5 0 1 246 1
Logano GB212 boiler 170 flamecurr flame current uint16 (>=0<=3199) µA False sensor.boiler_flame_current sensor.boiler_flamecurr 5 0 1/10 247 1
Logano GB212 boiler 170 fanwork fan boolean False binary_sensor.boiler_fan binary_sensor.boiler_fanwork 5 0 1 248 1
Logano GB212 boiler 170 ignwork ignition boolean False binary_sensor.boiler_ignition binary_sensor.boiler_ignwork 5 0 1 249 1
Logano GB212 boiler 170 oilpreheat oil preheating boolean False binary_sensor.boiler_oil_preheating binary_sensor.boiler_oilpreheat 5 0 1 250 1
Logano GB212 boiler 170 burnminpower burner min power uint8 (>=0<=100) % True number.boiler_burner_min_power number.boiler_burnminpower 5 0 1 251 1
Logano GB212 boiler 170 burnmaxpower burner max power uint8 (>=0<=254) % True number.boiler_burner_max_power number.boiler_burnmaxpower 5 0 1 252 1
Logano GB212 boiler 170 burnminperiod burner min period uint8 (>=0<=120) minutes True number.boiler_burner_min_period number.boiler_burnminperiod 5 0 1 253 1
Logano GB212 boiler 170 absburnpow burner current power (absolute) uint8 (>=0<=100) % False sensor.boiler_burner_current_power_(absolute) sensor.boiler_absburnpow 5 0 1 254 1
Logano GB212 boiler 170 heatblock heating block uint16 (>=0<=3199) C False sensor.boiler_heating_block sensor.boiler_heatblock 5 0 1/10 255 1
Logano GB212 boiler 170 boilhyston hysteresis on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_on_temperature number.boiler_boilhyston 5 0 1 256 1
Logano GB212 boiler 170 boilhystoff hysteresis off temperature int8 (>=0<=20) C True number.boiler_hysteresis_off_temperature number.boiler_boilhystoff 5 0 1 257 1
Logano GB212 boiler 170 boil2hyston hysteresis stage 2 on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_stage_2_on_temperature number.boiler_boil2hyston 5 0 1 258 1
Logano GB212 boiler 170 boil2hystoff hysteresis stage 2 off temperature int8 (>=0<=20) C True number.boiler_hysteresis_stage_2_off_temperature number.boiler_boil2hystoff 5 0 1 259 1
Logano GB212 boiler 170 curveon heatingcurve on boolean True switch.boiler_heatingcurve_on switch.boiler_curveon 5 0 1 260 1
Logano GB212 boiler 170 curvebase heatingcurve base uint8 (>=20<=90) C True number.boiler_heatingcurve_base number.boiler_curvebase 5 0 1 261 1
Logano GB212 boiler 170 curveend heatingcurve end uint8 (>=20<=90) C True number.boiler_heatingcurve_end number.boiler_curveend 5 0 1 262 1
Logano GB212 boiler 170 summertemp summer temperature uint8 (>=0<=45) C True number.boiler_summer_temperature number.boiler_summertemp 5 0 1 263 1
Logano GB212 boiler 170 nofrostmode nofrost mode boolean True switch.boiler_nofrost_mode switch.boiler_nofrostmode 5 0 1 264 1
Logano GB212 boiler 170 nofrosttemp nofrost temperature uint8 (>=0<=10) C True number.boiler_nofrost_temperature number.boiler_nofrosttemp 5 0 1 265 1
Logano GB212 boiler 170 heatingactivated heating activated boolean True switch.boiler_heating_activated switch.boiler_heatingactivated 5 0 1 13 1
Logano GB212 boiler 170 heatingtemp heating temperature uint8 (>=0<=90) C True number.boiler_heating_temperature number.boiler_heatingtemp 5 0 1 14 1
Logano GB212 boiler 170 heatingpump heating pump boolean False binary_sensor.boiler_heating_pump binary_sensor.boiler_heatingpump 5 0 1 15 1
Logano GB212 boiler 170 pumpmodmax boiler pump max power uint8 (>=0<=100) % True number.boiler_boiler_pump_max_power number.boiler_pumpmodmax 5 0 1 16 1
Logano GB212 boiler 170 pumpmodmin boiler pump min power uint8 (>=0<=100) % True number.boiler_boiler_pump_min_power number.boiler_pumpmodmin 5 0 1 17 1
Logano GB212 boiler 170 pumpmode boiler pump mode enum [proportional|deltaP-1|deltaP-2|deltaP-3|deltaP-4] True select.boiler_boiler_pump_mode select.boiler_pumpmode 5 0 1 18 1
Logano GB212 boiler 170 pumpcharacter boiler pump characteristic enum [proportional|150mbar|200mbar|250mbar|300mbar|350mbar|400mbar] True select.boiler_boiler_pump_characteristic select.boiler_pumpcharacter 5 0 1 19 1
Logano GB212 boiler 170 pumpdelay pump delay uint8 (>=0<=60) minutes True number.boiler_pump_delay number.boiler_pumpdelay 5 0 1 20 1
Logano GB212 boiler 170 pumpontemp pump logic temperature uint8 (>=0<=60) C True number.boiler_pump_logic_temperature number.boiler_pumpontemp 5 0 1 21 1
Logano GB212 boiler 170 selburnpow burner selected max power uint8 (>=0<=254) % True number.boiler_burner_selected_max_power number.boiler_selburnpow 5 0 1 22 1
Logano GB212 boiler 170 curburnpow burner current power uint8 (>=0<=100) % False sensor.boiler_burner_current_power sensor.boiler_curburnpow 5 0 1 23 1
Logano GB212 boiler 170 burnstarts burner starts uint24 (>=0<=16777214) False sensor.boiler_burner_starts sensor.boiler_burnstarts 5 0 1 24 2
Logano GB212 boiler 170 burnworkmin total burner operating time time (>=0<=16777214) minutes False sensor.boiler_total_burner_operating_time sensor.boiler_burnworkmin 5 0 1 26 2
Logano GB212 boiler 170 burn2workmin burner stage 2 operating time time (>=0<=16777214) minutes False sensor.boiler_burner_stage_2_operating_time sensor.boiler_burn2workmin 5 0 1 28 2
Logano GB212 boiler 170 heatworkmin total heat operating time time (>=0<=16777214) minutes False sensor.boiler_total_heat_operating_time sensor.boiler_heatworkmin 5 0 1 30 2
Logano GB212 boiler 170 heatstarts burner starts heating uint24 (>=0<=16777214) False sensor.boiler_burner_starts_heating sensor.boiler_heatstarts 5 0 1 32 2
Logano GB212 boiler 170 ubauptime total UBA operating time time (>=0<=16777214) minutes False sensor.boiler_total_UBA_operating_time sensor.boiler_ubauptime 5 0 1 34 2
Logano GB212 boiler 170 lastcode last error code string False sensor.boiler_last_error_code sensor.boiler_lastcode 5 0 1 36 28
Logano GB212 boiler 170 servicecode service code string False sensor.boiler_service_code sensor.boiler_servicecode 5 0 1 64 2
Logano GB212 boiler 170 servicecodenumber service code number uint16 (>=0<=31999) False sensor.boiler_service_code_number sensor.boiler_servicecodenumber 5 0 1 66 1
Logano GB212 boiler 170 maintenancemessage maintenance message string False sensor.boiler_maintenance_message sensor.boiler_maintenancemessage 5 0 1 67 2
Logano GB212 boiler 170 maintenance maintenance scheduled enum [off|time|date|manual] True select.boiler_maintenance_scheduled select.boiler_maintenance 5 0 1 69 1
Logano GB212 boiler 170 maintenancetime time to next maintenance uint16 (>=0<=31999) hours True number.boiler_time_to_next_maintenance number.boiler_maintenancetime 5 0 1 70 1
Logano GB212 boiler 170 maintenancedate next maintenance date string True sensor.boiler_next_maintenance_date sensor.boiler_maintenancedate 5 0 1 71 6
Logano GB212 boiler 170 emergencyops emergency operation boolean True switch.boiler_emergency_operation switch.boiler_emergencyops 5 0 1 77 1
Logano GB212 boiler 170 emergencytemp emergency temperature uint8 (>=15<=70) C True number.boiler_emergency_temperature number.boiler_emergencytemp 5 0 1 78 1
Logano GB212 boiler 170 pc0flow Flow PC0 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC0 sensor.boiler_pc0flow 5 0 1 79 1
Logano GB212 boiler 170 pc1flow Flow PC1 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC1 sensor.boiler_pc1flow 5 0 1 80 1
Logano GB212 boiler 170 pc1on PC1 boolean False binary_sensor.boiler_PC1 binary_sensor.boiler_pc1on 5 0 1 81 1
Logano GB212 boiler 170 pc1rate PC1 rate uint8 (>=0<=100) % False sensor.boiler_PC1_rate sensor.boiler_pc1rate 5 0 1 82 1
Logano GB212 boiler 170 meterheat meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_meter_heating sensor.boiler_meterheat 5 0 1/10 95 2
Logano GB212 boiler 170 dhw.meter meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_meter sensor.boiler_dhw_meter 5 9 1/10 2 2
Logano GB212 boiler 170 gasmeterheat gas meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_gas_meter_heating sensor.boiler_gasmeterheat 5 0 1/10 266 2
Logano GB212 boiler 170 dhw.gasmeter gas meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_gas_meter sensor.boiler_dhw_gasmeter 5 9 1/10 69 2
Logano GB212 boiler 170 nrgheat2 energy heating 2 uint24 (>=0<=1677721) kWh False sensor.boiler_energy_heating_2 sensor.boiler_nrgheat2 5 0 1/10 268 2
Logano GB212 boiler 170 dhw.nrg2 energy 2 uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_energy_2 sensor.boiler_dhw_nrg2 5 9 1/10 71 2
Logano GB212 boiler 170 dhw.tapactivated turn on/off boolean True switch.boiler_dhw_turn_on/off switch.boiler_dhw_tapactivated 5 9 1 28 1
Logano GB212 boiler 170 dhw.settemp set temperature uint8 (>=0<=254) C False sensor.boiler_dhw_set_temperature sensor.boiler_dhw_settemp 5 9 1 29 1
Logano GB212 boiler 170 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_temperature number.boiler_dhw_seltemp 5 9 1 30 1
Logano GB212 boiler 170 dhw.seltemplow selected lower temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_lower_temperature number.boiler_dhw_seltemplow 5 9 1 31 1
Logano GB212 boiler 170 dhw.tempecoplus selected eco+ temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_eco+_temperature number.boiler_dhw_tempecoplus 5 9 1 32 1
Logano GB212 boiler 170 dhw.seltempoff selected temperature for off uint8 (>=0<=254) C False sensor.boiler_dhw_selected_temperature_for_off sensor.boiler_dhw_seltempoff 5 9 1 33 1
Logano GB212 boiler 170 dhw.seltempsingle single charge temperature uint8 (>=0<=254) C True number.boiler_dhw_single_charge_temperature number.boiler_dhw_seltempsingle 5 9 1 34 1
Logano GB212 boiler 170 dhw.solartemp solar boiler temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_solar_boiler_temperature sensor.boiler_dhw_solartemp 5 9 1/10 35 1
Logano GB212 boiler 170 dhw.type type enum [off|flow|buffered flow|buffer|layered buffer] False sensor.boiler_dhw_type sensor.boiler_dhw_type 5 9 1 36 1
Logano GB212 boiler 170 dhw.comfort comfort enum [hot|eco|intelligent] True select.boiler_dhw_comfort select.boiler_dhw_comfort 5 9 1 37 1
Logano GB212 boiler 170 dhw.comfort1 comfort mode enum [high comfort|eco] True select.boiler_dhw_comfort_mode select.boiler_dhw_comfort1 5 9 1 38 1
Logano GB212 boiler 170 dhw.flowtempoffset flow temperature offset uint8 (>=0<=100) C True number.boiler_dhw_flow_temperature_offset number.boiler_dhw_flowtempoffset 5 9 1 39 1
Logano GB212 boiler 170 dhw.chargeoptimization charge optimization boolean True switch.boiler_dhw_charge_optimization switch.boiler_dhw_chargeoptimization 5 9 1 40 1
Logano GB212 boiler 170 dhw.maxpower max power uint8 (>=0<=254) % True number.boiler_dhw_max_power number.boiler_dhw_maxpower 5 9 1 41 1
Logano GB212 boiler 170 dhw.maxtemp maximum temperature uint8 (>=0<=80) C True number.boiler_dhw_maximum_temperature number.boiler_dhw_maxtemp 5 9 1 42 1
Logano GB212 boiler 170 dhw.circpump circulation pump available boolean True switch.boiler_dhw_circulation_pump_available switch.boiler_dhw_circpump 5 9 1 43 1
Logano GB212 boiler 170 dhw.chargetype charging type enum [chargepump|3-way valve] False sensor.boiler_dhw_charging_type sensor.boiler_dhw_chargetype 5 9 1 44 1
Logano GB212 boiler 170 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_on_temperature number.boiler_dhw_hyston 5 9 1 45 1
Logano GB212 boiler 170 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_off_temperature number.boiler_dhw_hystoff 5 9 1 46 1
Logano GB212 boiler 170 dhw.disinfectiontemp disinfection temperature uint8 (>=60<=80) C True number.boiler_dhw_disinfection_temperature number.boiler_dhw_disinfectiontemp 5 9 1 47 1
Logano GB212 boiler 170 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.boiler_dhw_circulation_pump_mode select.boiler_dhw_circmode 5 9 1 48 1
Logano GB212 boiler 170 dhw.circ circulation active boolean True switch.boiler_dhw_circulation_active switch.boiler_dhw_circ 5 9 1 49 1
Logano GB212 boiler 170 dhw.curtemp current intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_intern_temperature sensor.boiler_dhw_curtemp 5 9 1/10 50 1
Logano GB212 boiler 170 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_extern_temperature sensor.boiler_dhw_curtemp2 5 9 1/10 51 1
Logano GB212 boiler 170 dhw.curflow current tap water flow uint8 (>=0<=25) l/min False sensor.boiler_dhw_current_tap_water_flow sensor.boiler_dhw_curflow 5 9 1/10 52 1
Logano GB212 boiler 170 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_intern_temperature sensor.boiler_dhw_storagetemp1 5 9 1/10 53 1
Logano GB212 boiler 170 dhw.storagetemp2 storage extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_extern_temperature sensor.boiler_dhw_storagetemp2 5 9 1/10 54 1
Logano GB212 boiler 170 dhw.activated activated boolean True switch.boiler_dhw_activated switch.boiler_dhw_activated 5 9 1 55 1
Logano GB212 boiler 170 dhw.onetime one time charging boolean True switch.boiler_dhw_one_time_charging switch.boiler_dhw_onetime 5 9 1 56 1
Logano GB212 boiler 170 dhw.disinfecting disinfecting boolean True switch.boiler_dhw_disinfecting switch.boiler_dhw_disinfecting 5 9 1 57 1
Logano GB212 boiler 170 dhw.charging charging boolean False binary_sensor.boiler_dhw_charging binary_sensor.boiler_dhw_charging 5 9 1 58 1
Logano GB212 boiler 170 dhw.recharging recharging boolean False binary_sensor.boiler_dhw_recharging binary_sensor.boiler_dhw_recharging 5 9 1 59 1
Logano GB212 boiler 170 dhw.tempok temperature ok boolean False binary_sensor.boiler_dhw_temperature_ok binary_sensor.boiler_dhw_tempok 5 9 1 60 1
Logano GB212 boiler 170 dhw.active active boolean False binary_sensor.boiler_dhw_active binary_sensor.boiler_dhw_active 5 9 1 61 1
Logano GB212 boiler 170 dhw.3wayvalve 3-way valve active boolean False binary_sensor.boiler_dhw_3-way_valve_active binary_sensor.boiler_dhw_3wayvalve 5 9 1 62 1
Logano GB212 boiler 170 dhw.mixertemp mixer temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_mixer_temperature sensor.boiler_dhw_mixertemp 5 9 1/10 63 1
Logano GB212 boiler 170 dhw.cylmiddletemp cylinder middle temperature (TS3) uint16 (>=0<=3199) C False sensor.boiler_dhw_cylinder_middle_temperature_(TS3) sensor.boiler_dhw_cylmiddletemp 5 9 1/10 64 1
Logano GB212 boiler 170 dhw.starts starts uint24 (>=0<=16777214) False sensor.boiler_dhw_starts sensor.boiler_dhw_starts 5 9 1 65 2
Logano GB212 boiler 170 dhw.workm active time time (>=0<=16777214) minutes False sensor.boiler_dhw_active_time sensor.boiler_dhw_workm 5 9 1 67 2
Logano GB212 boiler 170 nompower nominal Power uint8 (>=0<=254) kW True number.boiler_nominal_Power number.boiler_nompower 5 0 1 270 1
Logano GB212 boiler 170 nrgtotal total energy uint24 (>=0<=167772) kWh False sensor.boiler_total_energy sensor.boiler_nrgtotal 5 0 1/100 83 2
Logano GB212 boiler 170 nrgheat energy heating uint24 (>=0<=10000000) kWh True number.boiler_energy_heating number.boiler_nrgheat 5 0 1/100 85 2
Logano GB212 boiler 170 dhw.nrg energy uint24 (>=0<=10000000) kWh True number.boiler_dhw_energy number.boiler_dhw_nrg 5 9 1/100 0 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 reset reset cmd [-|maintenance|error|history|message] True sensor.boiler_reset sensor.boiler_reset 5 0 1 0 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 heatingoff force heating off boolean True switch.boiler_force_heating_off switch.boiler_heatingoff 5 0 1 1 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 heatingactive heating active boolean False binary_sensor.boiler_heating_active binary_sensor.boiler_heatingactive 5 0 1 2 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 tapwateractive tapwater active boolean False binary_sensor.boiler_tapwater_active binary_sensor.boiler_tapwateractive 5 0 1 3 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 selflowtemp selected flow temperature uint8 (>=0<=90) C True number.boiler_selected_flow_temperature number.boiler_selflowtemp 5 0 1 4 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.boiler_heating_pump_modulation sensor.boiler_heatingpumpmod 5 0 1 5 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 outdoortemp outside temperature int16 (>=-3199<=3199) C False sensor.boiler_outside_temperature sensor.boiler_outdoortemp 5 0 1/10 6 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 curflowtemp current flow temperature uint16 (>=0<=3199) C False sensor.boiler_current_flow_temperature sensor.boiler_curflowtemp 5 0 1/10 7 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 rettemp return temperature uint16 (>=0<=3199) C False sensor.boiler_return_temperature sensor.boiler_rettemp 5 0 1/10 8 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 switchtemp mixing switch temperature uint16 (>=0<=3199) C False sensor.boiler_mixing_switch_temperature sensor.boiler_switchtemp 5 0 1/10 9 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 syspress system pressure uint8 (>=0<=25) bar False sensor.boiler_system_pressure sensor.boiler_syspress 5 0 1/10 10 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 boiltemp actual boiler temperature uint16 (>=0<=3199) C False sensor.boiler_actual_boiler_temperature sensor.boiler_boiltemp 5 0 1/10 11 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 headertemp low loss header uint16 (>=0<=3199) C False sensor.boiler_low_loss_header sensor.boiler_headertemp 5 0 1/10 12 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 heatingactivated heating activated boolean True switch.boiler_heating_activated switch.boiler_heatingactivated 5 0 1 13 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 heatingtemp heating temperature uint8 (>=0<=90) C True number.boiler_heating_temperature number.boiler_heatingtemp 5 0 1 14 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 heatingpump heating pump boolean False binary_sensor.boiler_heating_pump binary_sensor.boiler_heatingpump 5 0 1 15 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 pumpmodmax boiler pump max power uint8 (>=0<=100) % True number.boiler_boiler_pump_max_power number.boiler_pumpmodmax 5 0 1 16 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 pumpmodmin boiler pump min power uint8 (>=0<=100) % True number.boiler_boiler_pump_min_power number.boiler_pumpmodmin 5 0 1 17 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 pumpmode boiler pump mode enum [proportional|deltaP-1|deltaP-2|deltaP-3|deltaP-4] True select.boiler_boiler_pump_mode select.boiler_pumpmode 5 0 1 18 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 pumpcharacter boiler pump characteristic enum [proportional|150mbar|200mbar|250mbar|300mbar|350mbar|400mbar] True select.boiler_boiler_pump_characteristic select.boiler_pumpcharacter 5 0 1 19 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 pumpdelay pump delay uint8 (>=0<=60) minutes True number.boiler_pump_delay number.boiler_pumpdelay 5 0 1 20 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 pumpontemp pump logic temperature uint8 (>=0<=60) C True number.boiler_pump_logic_temperature number.boiler_pumpontemp 5 0 1 21 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 selburnpow burner selected max power uint8 (>=0<=254) % True number.boiler_burner_selected_max_power number.boiler_selburnpow 5 0 1 22 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 curburnpow burner current power uint8 (>=0<=100) % False sensor.boiler_burner_current_power sensor.boiler_curburnpow 5 0 1 23 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 burnstarts burner starts uint24 (>=0<=16777214) False sensor.boiler_burner_starts sensor.boiler_burnstarts 5 0 1 24 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 burnworkmin total burner operating time time (>=0<=16777214) minutes False sensor.boiler_total_burner_operating_time sensor.boiler_burnworkmin 5 0 1 26 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 burn2workmin burner stage 2 operating time time (>=0<=16777214) minutes False sensor.boiler_burner_stage_2_operating_time sensor.boiler_burn2workmin 5 0 1 28 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 heatworkmin total heat operating time time (>=0<=16777214) minutes False sensor.boiler_total_heat_operating_time sensor.boiler_heatworkmin 5 0 1 30 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 heatstarts burner starts heating uint24 (>=0<=16777214) False sensor.boiler_burner_starts_heating sensor.boiler_heatstarts 5 0 1 32 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 ubauptime total UBA operating time time (>=0<=16777214) minutes False sensor.boiler_total_UBA_operating_time sensor.boiler_ubauptime 5 0 1 34 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 lastcode last error code string False sensor.boiler_last_error_code sensor.boiler_lastcode 5 0 1 36 28
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 servicecode service code string False sensor.boiler_service_code sensor.boiler_servicecode 5 0 1 64 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 servicecodenumber service code number uint16 (>=0<=31999) False sensor.boiler_service_code_number sensor.boiler_servicecodenumber 5 0 1 66 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 maintenancemessage maintenance message string False sensor.boiler_maintenance_message sensor.boiler_maintenancemessage 5 0 1 67 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 maintenance maintenance scheduled enum [off|time|date|manual] True select.boiler_maintenance_scheduled select.boiler_maintenance 5 0 1 69 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 maintenancetime time to next maintenance uint16 (>=0<=31999) hours True number.boiler_time_to_next_maintenance number.boiler_maintenancetime 5 0 1 70 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 maintenancedate next maintenance date string True sensor.boiler_next_maintenance_date sensor.boiler_maintenancedate 5 0 1 71 6
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 emergencyops emergency operation boolean True switch.boiler_emergency_operation switch.boiler_emergencyops 5 0 1 77 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 emergencytemp emergency temperature uint8 (>=15<=70) C True number.boiler_emergency_temperature number.boiler_emergencytemp 5 0 1 78 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 pc0flow Flow PC0 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC0 sensor.boiler_pc0flow 5 0 1 79 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 pc1flow Flow PC1 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC1 sensor.boiler_pc1flow 5 0 1 80 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 pc1on PC1 boolean False binary_sensor.boiler_PC1 binary_sensor.boiler_pc1on 5 0 1 81 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 pc1rate PC1 rate uint8 (>=0<=100) % False sensor.boiler_PC1_rate sensor.boiler_pc1rate 5 0 1 82 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 nrgtotal total energy uint24 (>=0<=167772) kWh False sensor.boiler_total_energy sensor.boiler_nrgtotal 5 0 1/100 83 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.nrg energy uint24 (>=0<=167772) kWh False sensor.boiler_dhw_energy sensor.boiler_dhw_nrg 5 9 1/100 0 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 nrgheat energy heating uint24 (>=0<=167772) kWh False sensor.boiler_energy_heating sensor.boiler_nrgheat 5 0 1/100 85 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 nrgcool energy cooling uint24 (>=0<=167772) kWh False sensor.boiler_energy_cooling sensor.boiler_nrgcool 5 0 1/100 87 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 metertotal meter total uint24 (>=0<=167772) kWh False sensor.boiler_meter_total sensor.boiler_metertotal 5 0 1/100 89 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 metercomp meter compressor uint24 (>=0<=167772) kWh False sensor.boiler_meter_compressor sensor.boiler_metercomp 5 0 1/100 91 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 metereheat meter e-heater uint24 (>=0<=167772) kWh False sensor.boiler_meter_e-heater sensor.boiler_metereheat 5 0 1/100 93 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 meterheat meter heating uint24 (>=0<=167772) kWh False sensor.boiler_meter_heating sensor.boiler_meterheat 5 0 1/100 95 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 metercool meter cooling uint24 (>=0<=167772) kWh False sensor.boiler_meter_cooling sensor.boiler_metercool 5 0 1/100 97 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.meter meter uint24 (>=0<=167772) kWh False sensor.boiler_dhw_meter sensor.boiler_dhw_meter 5 9 1/100 2 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 uptimetotal heatpump total uptime time (>=0<=279620) minutes False sensor.boiler_heatpump_total_uptime sensor.boiler_uptimetotal 5 0 1/60 99 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 uptimecontrol total operating time heat time (>=0<=279620) minutes False sensor.boiler_total_operating_time_heat sensor.boiler_uptimecontrol 5 0 1/60 101 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 uptimecompheating operating time compressor heating time (>=0<=279620) minutes False sensor.boiler_operating_time_compressor_heating sensor.boiler_uptimecompheating 5 0 1/60 103 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 uptimecompcooling operating time compressor cooling time (>=0<=279620) minutes False sensor.boiler_operating_time_compressor_cooling sensor.boiler_uptimecompcooling 5 0 1/60 105 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.uptimecomp operating time compressor time (>=0<=279620) minutes False sensor.boiler_dhw_operating_time_compressor sensor.boiler_dhw_uptimecomp 5 9 1/60 4 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 uptimecomppool operating time compressor pool time (>=0<=279620) minutes False sensor.boiler_operating_time_compressor_pool sensor.boiler_uptimecomppool 5 0 1/60 107 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 totalcompstarts total compressor control starts uint24 (>=0<=16777214) False sensor.boiler_total_compressor_control_starts sensor.boiler_totalcompstarts 5 0 1 109 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 heatingstarts heating control starts uint24 (>=0<=16777214) False sensor.boiler_heating_control_starts sensor.boiler_heatingstarts 5 0 1 111 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 coolingstarts cooling control starts uint24 (>=0<=16777214) False sensor.boiler_cooling_control_starts sensor.boiler_coolingstarts 5 0 1 113 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.startshp starts hp uint24 (>=0<=16777214) False sensor.boiler_dhw_starts_hp sensor.boiler_dhw_startshp 5 9 1 6 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 poolstarts pool control starts uint24 (>=0<=16777214) False sensor.boiler_pool_control_starts sensor.boiler_poolstarts 5 0 1 115 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 nrgconstotal total energy consumption uint24 (>=0<=16777214) kWh False sensor.boiler_total_energy_consumption sensor.boiler_nrgconstotal 5 0 1 117 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 nrgconscomptotal total energy consumption compressor uint24 (>=0<=16777214) kWh False sensor.boiler_total_energy_consumption_compressor sensor.boiler_nrgconscomptotal 5 0 1 119 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 nrgconscompheating energy consumption compressor heating uint24 (>=0<=16777214) kWh False sensor.boiler_energy_consumption_compressor_heating sensor.boiler_nrgconscompheating 5 0 1 121 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.nrgconscomp energy consumption compressor uint24 (>=0<=16777214) kWh False sensor.boiler_dhw_energy_consumption_compressor sensor.boiler_dhw_nrgconscomp 5 9 1 8 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 nrgconscompcooling energy consumption compressor cooling uint24 (>=0<=16777214) kWh False sensor.boiler_energy_consumption_compressor_cooling sensor.boiler_nrgconscompcooling 5 0 1 123 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 nrgconscomppool energy consumption compressor pool uint24 (>=0<=16777214) kWh False sensor.boiler_energy_consumption_compressor_pool sensor.boiler_nrgconscomppool 5 0 1 125 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 auxelecheatnrgconstotal total aux elec. heater energy consumption uint24 (>=0<=16777214) kWh False sensor.boiler_total_aux_elec._heater_energy_consumption sensor.boiler_auxelecheatnrgconstotal 5 0 1 127 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 auxelecheatnrgconsheating aux elec. heater energy consumption heating uint24 (>=0<=16777214) kWh False sensor.boiler_aux_elec._heater_energy_consumption_heating sensor.boiler_auxelecheatnrgconsheating 5 0 1 129 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.auxelecheatnrgcons aux elec. heater energy consumption uint24 (>=0<=16777214) kWh False sensor.boiler_dhw_aux_elec._heater_energy_consumption sensor.boiler_dhw_auxelecheatnrgcons 5 9 1 10 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 auxelecheatnrgconspool aux elec. heater energy consumption pool uint24 (>=0<=16777214) kWh False sensor.boiler_aux_elec._heater_energy_consumption_pool sensor.boiler_auxelecheatnrgconspool 5 0 1 131 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 nrgsupptotal total energy supplied uint24 (>=0<=16777214) kWh False sensor.boiler_total_energy_supplied sensor.boiler_nrgsupptotal 5 0 1 133 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 nrgsuppheating total energy supplied heating uint24 (>=0<=16777214) kWh False sensor.boiler_total_energy_supplied_heating sensor.boiler_nrgsuppheating 5 0 1 135 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.nrgsupp total energy warm supplied uint24 (>=0<=16777214) kWh False sensor.boiler_dhw_total_energy_warm_supplied sensor.boiler_dhw_nrgsupp 5 9 1 12 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 nrgsuppcooling total energy supplied cooling uint24 (>=0<=16777214) kWh False sensor.boiler_total_energy_supplied_cooling sensor.boiler_nrgsuppcooling 5 0 1 137 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 nrgsupppool total energy supplied pool uint24 (>=0<=16777214) kWh False sensor.boiler_total_energy_supplied_pool sensor.boiler_nrgsupppool 5 0 1 139 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hppower compressor power output uint16 (>=0<=3199) kW False sensor.boiler_compressor_power_output sensor.boiler_hppower 5 0 1/10 141 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hpmaxpower compressor max power uint8 (>=0<=100) % True number.boiler_compressor_max_power number.boiler_hpmaxpower 5 0 1 142 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 pvmaxcomp pv compressor max power uint8 (>=0<=25) kW True number.boiler_pv_compressor_max_power number.boiler_pvmaxcomp 5 0 1/10 143 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 powerreduction power reduction uint8 (>=30<=60) % True number.boiler_power_reduction number.boiler_powerreduction 5 0 10 144 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hpsetdiffpress set differential pressure uint8 (>=150<=750) mbar True number.boiler_set_differential_pressure number.boiler_hpsetdiffpress 5 0 50 145 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hpcompon hp compressor boolean False binary_sensor.boiler_hp_compressor binary_sensor.boiler_hpcompon 5 0 1 146 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hpactivity compressor activity enum [off|heating|cooling|hot water|pool|pool heating|defrost|compressor alarm] False sensor.boiler_compressor_activity sensor.boiler_hpactivity 5 0 1 147 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hpbrinepumpspd brine pump speed uint8 (>=0<=100) % False sensor.boiler_brine_pump_speed sensor.boiler_hpbrinepumpspd 5 0 1 148 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hpswitchvalve switch valve boolean False binary_sensor.boiler_switch_valve binary_sensor.boiler_hpswitchvalve 5 0 1 149 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hpcompspd compressor speed uint8 (>=0<=100) % False sensor.boiler_compressor_speed sensor.boiler_hpcompspd 5 0 1 150 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hpcircspd circulation pump speed uint8 (>=0<=100) % False sensor.boiler_circulation_pump_speed sensor.boiler_hpcircspd 5 0 1 151 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hpbrinein brine in/evaporator int16 (>=-3199<=3199) C False sensor.boiler_brine_in/evaporator sensor.boiler_hpbrinein 5 0 1/10 152 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hpbrineout brine out/condenser int16 (>=-3199<=3199) C False sensor.boiler_brine_out/condenser sensor.boiler_hpbrineout 5 0 1/10 153 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hptc0 heat carrier return (TC0) int16 (>=-3199<=3199) C False sensor.boiler_heat_carrier_return_(TC0) sensor.boiler_hptc0 5 0 1/10 154 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hptc1 heat carrier forward (TC1) int16 (>=-3199<=3199) C False sensor.boiler_heat_carrier_forward_(TC1) sensor.boiler_hptc1 5 0 1/10 155 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hptc3 condenser temperature (TC3) int16 (>=-3199<=3199) C False sensor.boiler_condenser_temperature_(TC3) sensor.boiler_hptc3 5 0 1/10 156 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hptr1 compressor temperature (TR1) int16 (>=-3199<=3199) C False sensor.boiler_compressor_temperature_(TR1) sensor.boiler_hptr1 5 0 1/10 157 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hptr3 refrigerant temperature liquid side (condenser output) (TR3) int16 (>=-3199<=3199) C False sensor.boiler_refrigerant_temperature_liquid_side_(condenser_output)_(TR3) sensor.boiler_hptr3 5 0 1/10 158 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hptr4 evaporator inlet temperature (TR4) int16 (>=-3199<=3199) C False sensor.boiler_evaporator_inlet_temperature_(TR4) sensor.boiler_hptr4 5 0 1/10 159 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hptr5 compressor inlet temperature (TR5) int16 (>=-3199<=3199) C False sensor.boiler_compressor_inlet_temperature_(TR5) sensor.boiler_hptr5 5 0 1/10 160 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hptr6 compressor outlet temperature (TR6) int16 (>=-3199<=3199) C False sensor.boiler_compressor_outlet_temperature_(TR6) sensor.boiler_hptr6 5 0 1/10 161 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hptr7 refrigerant temperature gas side (condenser input) (TR7) int16 (>=-3199<=3199) C False sensor.boiler_refrigerant_temperature_gas_side_(condenser_input)_(TR7) sensor.boiler_hptr7 5 0 1/10 162 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hptl2 air inlet temperature (TL2) int16 (>=-3199<=3199) C False sensor.boiler_air_inlet_temperature_(TL2) sensor.boiler_hptl2 5 0 1/10 163 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hppl1 low pressure side temperature (PL1) int16 (>=-3199<=3199) C False sensor.boiler_low_pressure_side_temperature_(PL1) sensor.boiler_hppl1 5 0 1/10 164 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hpph1 high pressure side temperature (PH1) int16 (>=-3199<=3199) C False sensor.boiler_high_pressure_side_temperature_(PH1) sensor.boiler_hpph1 5 0 1/10 165 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hpta4 drain pan temp (TA4) int16 (>=-3199<=3199) C False sensor.boiler_drain_pan_temp_(TA4) sensor.boiler_hpta4 5 0 1/10 166 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hptw1 reservoir temp (TW1) int16 (>=-3199<=3199) C False sensor.boiler_reservoir_temp_(TW1) sensor.boiler_hptw1 5 0 1/10 167 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 poolsettemp pool set temperature uint8 (>=0<=127) C True number.boiler_pool_set_temperature number.boiler_poolsettemp 5 0 1/2 168 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hp4way 4-way valve (VR4) enum [cooling & defrost|heating & dhw] False sensor.boiler_4-way_valve_(VR4) sensor.boiler_hp4way 5 0 1 169 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hpin1 input 1 state boolean False binary_sensor.boiler_input_1_state binary_sensor.boiler_hpin1 5 0 1 170 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hpin1opt input 1 options string True sensor.boiler_input_1_options sensor.boiler_hpin1opt 5 0 1 171 8
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hpin2 input 2 state boolean False binary_sensor.boiler_input_2_state binary_sensor.boiler_hpin2 5 0 1 179 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hpin2opt input 2 options string True sensor.boiler_input_2_options sensor.boiler_hpin2opt 5 0 1 180 8
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hpin3 input 3 state boolean False binary_sensor.boiler_input_3_state binary_sensor.boiler_hpin3 5 0 1 188 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hpin3opt input 3 options string True sensor.boiler_input_3_options sensor.boiler_hpin3opt 5 0 1 189 8
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hpin4 input 4 state boolean False binary_sensor.boiler_input_4_state binary_sensor.boiler_hpin4 5 0 1 197 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hpin4opt input 4 options string True sensor.boiler_input_4_options sensor.boiler_hpin4opt 5 0 1 198 8
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 maxheatcomp heat limit compressor enum [0 kW|2 kW|3 kW|4 kW|6 kW|9 kW] True select.boiler_heat_limit_compressor select.boiler_maxheatcomp 5 0 1 206 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 maxheatheat heat limit heating enum [0 kW|2 kW|3 kW|4 kW|6 kW|9 kW] True select.boiler_heat_limit_heating select.boiler_maxheatheat 5 0 1 207 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.maxheat heat limit enum [0 kW|2 kW|3 kW|4 kW|6 kW|9 kW] True select.boiler_dhw_heat_limit select.boiler_dhw_maxheat 5 9 1 14 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 auxheatersource aux heater source enum [not installed|electric heater|exclusive|parallel|hybrid] True select.boiler_aux_heater_source select.boiler_auxheatersource 5 0 1 208 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 pvcooling cooling only with PV boolean True switch.boiler_cooling_only_with_PV switch.boiler_pvcooling 5 0 1 209 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 auxheateronly aux heater only boolean True switch.boiler_aux_heater_only switch.boiler_auxheateronly 5 0 1 210 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 auxheateroff disable aux heater boolean True switch.boiler_disable_aux_heater switch.boiler_auxheateroff 5 0 1 211 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 auxheaterstatus aux heater status enum [off|heating|cooling|hot water|pool|pool heating|defrost|compressor alarm] False sensor.boiler_aux_heater_status sensor.boiler_auxheaterstatus 5 0 1 212 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 auxheaterlevel aux heater level uint8 (>=0<=100) % False sensor.boiler_aux_heater_level sensor.boiler_auxheaterlevel 5 0 1 213 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 auxheaterdelay aux heater on delay uint16 (>=10<=1000) K*min True number.boiler_aux_heater_on_delay number.boiler_auxheaterdelay 5 0 10 214 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 auxmaxlimit aux heater max limit uint8 (>=0<=10) K True number.boiler_aux_heater_max_limit number.boiler_auxmaxlimit 5 0 1/10 215 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 auxlimitstart aux heater limit start uint8 (>=0<=10) K True number.boiler_aux_heater_limit_start number.boiler_auxlimitstart 5 0 1/10 216 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 auxheatrmode aux heater mode enum [eco|comfort] True select.boiler_aux_heater_mode select.boiler_auxheatrmode 5 0 1 217 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hphystheat on/off hyst heat uint16 (>=50<=1500) K*min True number.boiler_on/off_hyst_heat number.boiler_hphystheat 5 0 5 218 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hphystcool on/off hyst cool uint16 (>=50<=1500) K*min True number.boiler_on/off_hyst_cool number.boiler_hphystcool 5 0 5 219 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hphystpool on/off hyst pool uint16 (>=50<=1500) K*min True number.boiler_on/off_hyst_pool number.boiler_hphystpool 5 0 5 220 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 silentmode silent mode enum [off|auto|on] True select.boiler_silent_mode select.boiler_silentmode 5 0 1 221 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 silentfrom silent mode from uint8 (>=0<=3810) minutes True number.boiler_silent_mode_from number.boiler_silentfrom 5 0 15 222 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 silentto silent mode to uint8 (>=0<=3810) minutes True number.boiler_silent_mode_to number.boiler_silentto 5 0 15 223 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 mintempsilent min outside temp for silent mode int8 (>=-126<=126) C True number.boiler_min_outside_temp_for_silent_mode number.boiler_mintempsilent 5 0 1 224 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 tempparmode outside temp parallel mode int8 (>=-126<=126) C True number.boiler_outside_temp_parallel_mode number.boiler_tempparmode 5 0 1 225 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 auxheatmix aux heater mixing valve int8 (>=-100<=100) % False sensor.boiler_aux_heater_mixing_valve sensor.boiler_auxheatmix 5 0 1 226 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 tempdiffheat temp diff TC3/TC0 heat uint8 (>=2<=10) K True number.boiler_temp_diff_TC3/TC0_heat number.boiler_tempdiffheat 5 0 1/10 227 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 tempdiffcool temp diff TC3/TC0 cool uint8 (>=2<=10) K True number.boiler_temp_diff_TC3/TC0_cool number.boiler_tempdiffcool 5 0 1/10 228 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 vpcooling valve/pump cooling boolean True switch.boiler_valve/pump_cooling switch.boiler_vpcooling 5 0 1 229 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 heatcable heating cable boolean True switch.boiler_heating_cable switch.boiler_heatcable 5 0 1 230 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 vc0valve VC0 valve boolean True switch.boiler_VC0_valve switch.boiler_vc0valve 5 0 1 231 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 primepump primary heatpump boolean True switch.boiler_primary_heatpump switch.boiler_primepump 5 0 1 232 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 primepumpmod primary heatpump modulation uint8 (>=0<=100) % True number.boiler_primary_heatpump_modulation number.boiler_primepumpmod 5 0 1 233 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hp3way 3-way valve boolean True switch.boiler_3-way_valve switch.boiler_hp3way 5 0 1 234 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 elheatstep1 el. heater step 1 boolean True switch.boiler_el._heater_step_1 switch.boiler_elheatstep1 5 0 1 235 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 elheatstep2 el. heater step 2 boolean True switch.boiler_el._heater_step_2 switch.boiler_elheatstep2 5 0 1 236 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 elheatstep3 el. heater step 3 boolean True switch.boiler_el._heater_step_3 switch.boiler_elheatstep3 5 0 1 237 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hpea0 condensate reservoir heating (EA0) boolean False binary_sensor.boiler_condensate_reservoir_heating_(EA0) binary_sensor.boiler_hpea0 5 0 1 238 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hppumpmode primary heatpump mode enum [auto|continuous] True select.boiler_primary_heatpump_mode select.boiler_hppumpmode 5 0 1 239 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 fan fan uint8 (>=20<=100) % True number.boiler_fan number.boiler_fan 5 0 1 240 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 shutdown shutdown cmd [off|on] True sensor.boiler_shutdown sensor.boiler_shutdown 5 0 1 241 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hpcurrpower compressor current power uint16 (>=0<=31999) W False sensor.boiler_compressor_current_power sensor.boiler_hpcurrpower 5 0 1 242 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 hppowerlimit power limit uint16 (>=0<=31999) W True number.boiler_power_limit number.boiler_hppowerlimit 5 0 1 243 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.alternatingop alternating operation boolean True switch.boiler_dhw_alternating_operation switch.boiler_dhw_alternatingop 5 9 1 15 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.altopprioheat prioritise heating during dhw uint8 (>=20<=120) minutes True number.boiler_dhw_prioritise_heating_during_dhw number.boiler_dhw_altopprioheat 5 9 1 16 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.altopprio prioritise dhw during heating uint8 (>=30<=120) minutes True number.boiler_dhw_prioritise_dhw_during_heating number.boiler_dhw_altopprio 5 9 1 17 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.comfoff comfort switch off uint8 (>=15<=65) C True number.boiler_dhw_comfort_switch_off number.boiler_dhw_comfoff 5 9 1 18 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.ecooff eco switch off uint8 (>=15<=65) C True number.boiler_dhw_eco_switch_off number.boiler_dhw_ecooff 5 9 1 19 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.ecoplusoff eco+ switch off uint8 (>=48<=63) C True number.boiler_dhw_eco+_switch_off number.boiler_dhw_ecoplusoff 5 9 1 20 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.comfdiff comfort diff uint8 (>=6<=12) K True number.boiler_dhw_comfort_diff number.boiler_dhw_comfdiff 5 9 1 21 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.ecodiff eco diff uint8 (>=6<=12) K True number.boiler_dhw_eco_diff number.boiler_dhw_ecodiff 5 9 1 22 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.ecoplusdiff eco+ diff uint8 (>=6<=12) K True number.boiler_dhw_eco+_diff number.boiler_dhw_ecoplusdiff 5 9 1 23 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.comfstop comfort stop temp uint8 (>=0<=254) C True number.boiler_dhw_comfort_stop_temp number.boiler_dhw_comfstop 5 9 1 24 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.ecostop eco stop temp uint8 (>=0<=254) C True number.boiler_dhw_eco_stop_temp number.boiler_dhw_ecostop 5 9 1 25 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.ecoplusstop eco+ stop temp uint8 (>=0<=254) C True number.boiler_dhw_eco+_stop_temp number.boiler_dhw_ecoplusstop 5 9 1 26 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.hpcircpump circulation pump available during dhw boolean True switch.boiler_dhw_circulation_pump_available_during_dhw switch.boiler_dhw_hpcircpump 5 9 1 27 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.tapactivated turn on/off boolean True switch.boiler_dhw_turn_on/off switch.boiler_dhw_tapactivated 5 9 1 28 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.settemp set temperature uint8 (>=0<=254) C False sensor.boiler_dhw_set_temperature sensor.boiler_dhw_settemp 5 9 1 29 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_temperature number.boiler_dhw_seltemp 5 9 1 30 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.seltemplow selected lower temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_lower_temperature number.boiler_dhw_seltemplow 5 9 1 31 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.tempecoplus selected eco+ temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_eco+_temperature number.boiler_dhw_tempecoplus 5 9 1 32 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.seltempoff selected temperature for off uint8 (>=0<=254) C False sensor.boiler_dhw_selected_temperature_for_off sensor.boiler_dhw_seltempoff 5 9 1 33 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.seltempsingle single charge temperature uint8 (>=0<=254) C True number.boiler_dhw_single_charge_temperature number.boiler_dhw_seltempsingle 5 9 1 34 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.solartemp solar boiler temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_solar_boiler_temperature sensor.boiler_dhw_solartemp 5 9 1/10 35 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.type type enum [off|flow|buffered flow|buffer|layered buffer] False sensor.boiler_dhw_type sensor.boiler_dhw_type 5 9 1 36 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.comfort comfort enum [hot|eco|intelligent] True select.boiler_dhw_comfort select.boiler_dhw_comfort 5 9 1 37 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.comfort1 comfort mode enum [high comfort|eco] True select.boiler_dhw_comfort_mode select.boiler_dhw_comfort1 5 9 1 38 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.flowtempoffset flow temperature offset uint8 (>=0<=100) C True number.boiler_dhw_flow_temperature_offset number.boiler_dhw_flowtempoffset 5 9 1 39 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.chargeoptimization charge optimization boolean True switch.boiler_dhw_charge_optimization switch.boiler_dhw_chargeoptimization 5 9 1 40 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.maxpower max power uint8 (>=0<=254) % True number.boiler_dhw_max_power number.boiler_dhw_maxpower 5 9 1 41 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.maxtemp maximum temperature uint8 (>=0<=80) C True number.boiler_dhw_maximum_temperature number.boiler_dhw_maxtemp 5 9 1 42 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.circpump circulation pump available boolean True switch.boiler_dhw_circulation_pump_available switch.boiler_dhw_circpump 5 9 1 43 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.chargetype charging type enum [chargepump|3-way valve] False sensor.boiler_dhw_charging_type sensor.boiler_dhw_chargetype 5 9 1 44 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_on_temperature number.boiler_dhw_hyston 5 9 1 45 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_off_temperature number.boiler_dhw_hystoff 5 9 1 46 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.disinfectiontemp disinfection temperature uint8 (>=60<=80) C True number.boiler_dhw_disinfection_temperature number.boiler_dhw_disinfectiontemp 5 9 1 47 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.boiler_dhw_circulation_pump_mode select.boiler_dhw_circmode 5 9 1 48 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.circ circulation active boolean True switch.boiler_dhw_circulation_active switch.boiler_dhw_circ 5 9 1 49 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.curtemp current intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_intern_temperature sensor.boiler_dhw_curtemp 5 9 1/10 50 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_extern_temperature sensor.boiler_dhw_curtemp2 5 9 1/10 51 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.curflow current tap water flow uint8 (>=0<=25) l/min False sensor.boiler_dhw_current_tap_water_flow sensor.boiler_dhw_curflow 5 9 1/10 52 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_intern_temperature sensor.boiler_dhw_storagetemp1 5 9 1/10 53 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.storagetemp2 storage extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_extern_temperature sensor.boiler_dhw_storagetemp2 5 9 1/10 54 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.activated activated boolean True switch.boiler_dhw_activated switch.boiler_dhw_activated 5 9 1 55 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.onetime one time charging boolean True switch.boiler_dhw_one_time_charging switch.boiler_dhw_onetime 5 9 1 56 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.disinfecting disinfecting boolean True switch.boiler_dhw_disinfecting switch.boiler_dhw_disinfecting 5 9 1 57 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.charging charging boolean False binary_sensor.boiler_dhw_charging binary_sensor.boiler_dhw_charging 5 9 1 58 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.recharging recharging boolean False binary_sensor.boiler_dhw_recharging binary_sensor.boiler_dhw_recharging 5 9 1 59 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.tempok temperature ok boolean False binary_sensor.boiler_dhw_temperature_ok binary_sensor.boiler_dhw_tempok 5 9 1 60 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.active active boolean False binary_sensor.boiler_dhw_active binary_sensor.boiler_dhw_active 5 9 1 61 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.3wayvalve 3-way valve active boolean False binary_sensor.boiler_dhw_3-way_valve_active binary_sensor.boiler_dhw_3wayvalve 5 9 1 62 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.mixertemp mixer temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_mixer_temperature sensor.boiler_dhw_mixertemp 5 9 1/10 63 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.cylmiddletemp cylinder middle temperature (TS3) uint16 (>=0<=3199) C False sensor.boiler_dhw_cylinder_middle_temperature_(TS3) sensor.boiler_dhw_cylmiddletemp 5 9 1/10 64 1
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.starts starts uint24 (>=0<=16777214) False sensor.boiler_dhw_starts sensor.boiler_dhw_starts 5 9 1 65 2
Enviline, Compress 6000AW, Hybrid 3000-7000iAW, SupraEco/Geo 5xx, WLW196i/WSW196i boiler 172 dhw.workm active time time (>=0<=16777214) minutes False sensor.boiler_dhw_active_time sensor.boiler_dhw_workm 5 9 1 67 2
Geo 5xx boiler 173 reset reset cmd [-|maintenance|error|history|message] True sensor.boiler_reset sensor.boiler_reset 5 0 1 0 1
Geo 5xx boiler 173 heatingoff force heating off boolean True switch.boiler_force_heating_off switch.boiler_heatingoff 5 0 1 1 1
Geo 5xx boiler 173 heatingactive heating active boolean False binary_sensor.boiler_heating_active binary_sensor.boiler_heatingactive 5 0 1 2 1
Geo 5xx boiler 173 tapwateractive tapwater active boolean False binary_sensor.boiler_tapwater_active binary_sensor.boiler_tapwateractive 5 0 1 3 1
Geo 5xx boiler 173 selflowtemp selected flow temperature uint8 (>=0<=90) C True number.boiler_selected_flow_temperature number.boiler_selflowtemp 5 0 1 4 1
Geo 5xx boiler 173 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.boiler_heating_pump_modulation sensor.boiler_heatingpumpmod 5 0 1 5 1
Geo 5xx boiler 173 outdoortemp outside temperature int16 (>=-3199<=3199) C False sensor.boiler_outside_temperature sensor.boiler_outdoortemp 5 0 1/10 6 1
Geo 5xx boiler 173 curflowtemp current flow temperature uint16 (>=0<=3199) C False sensor.boiler_current_flow_temperature sensor.boiler_curflowtemp 5 0 1/10 7 1
Geo 5xx boiler 173 rettemp return temperature uint16 (>=0<=3199) C False sensor.boiler_return_temperature sensor.boiler_rettemp 5 0 1/10 8 1
Geo 5xx boiler 173 switchtemp mixing switch temperature uint16 (>=0<=3199) C False sensor.boiler_mixing_switch_temperature sensor.boiler_switchtemp 5 0 1/10 9 1
Geo 5xx boiler 173 syspress system pressure uint8 (>=0<=25) bar False sensor.boiler_system_pressure sensor.boiler_syspress 5 0 1/10 10 1
Geo 5xx boiler 173 boiltemp actual boiler temperature uint16 (>=0<=3199) C False sensor.boiler_actual_boiler_temperature sensor.boiler_boiltemp 5 0 1/10 11 1
Geo 5xx boiler 173 headertemp low loss header uint16 (>=0<=3199) C False sensor.boiler_low_loss_header sensor.boiler_headertemp 5 0 1/10 12 1
Geo 5xx boiler 173 heatingactivated heating activated boolean True switch.boiler_heating_activated switch.boiler_heatingactivated 5 0 1 13 1
Geo 5xx boiler 173 heatingtemp heating temperature uint8 (>=0<=90) C True number.boiler_heating_temperature number.boiler_heatingtemp 5 0 1 14 1
Geo 5xx boiler 173 heatingpump heating pump boolean False binary_sensor.boiler_heating_pump binary_sensor.boiler_heatingpump 5 0 1 15 1
Geo 5xx boiler 173 pumpmodmax boiler pump max power uint8 (>=0<=100) % True number.boiler_boiler_pump_max_power number.boiler_pumpmodmax 5 0 1 16 1
Geo 5xx boiler 173 pumpmodmin boiler pump min power uint8 (>=0<=100) % True number.boiler_boiler_pump_min_power number.boiler_pumpmodmin 5 0 1 17 1
Geo 5xx boiler 173 pumpmode boiler pump mode enum [proportional|deltaP-1|deltaP-2|deltaP-3|deltaP-4] True select.boiler_boiler_pump_mode select.boiler_pumpmode 5 0 1 18 1
Geo 5xx boiler 173 pumpcharacter boiler pump characteristic enum [proportional|150mbar|200mbar|250mbar|300mbar|350mbar|400mbar] True select.boiler_boiler_pump_characteristic select.boiler_pumpcharacter 5 0 1 19 1
Geo 5xx boiler 173 pumpdelay pump delay uint8 (>=0<=60) minutes True number.boiler_pump_delay number.boiler_pumpdelay 5 0 1 20 1
Geo 5xx boiler 173 pumpontemp pump logic temperature uint8 (>=0<=60) C True number.boiler_pump_logic_temperature number.boiler_pumpontemp 5 0 1 21 1
Geo 5xx boiler 173 selburnpow burner selected max power uint8 (>=0<=254) % True number.boiler_burner_selected_max_power number.boiler_selburnpow 5 0 1 22 1
Geo 5xx boiler 173 curburnpow burner current power uint8 (>=0<=100) % False sensor.boiler_burner_current_power sensor.boiler_curburnpow 5 0 1 23 1
Geo 5xx boiler 173 burnstarts burner starts uint24 (>=0<=16777214) False sensor.boiler_burner_starts sensor.boiler_burnstarts 5 0 1 24 2
Geo 5xx boiler 173 burnworkmin total burner operating time time (>=0<=16777214) minutes False sensor.boiler_total_burner_operating_time sensor.boiler_burnworkmin 5 0 1 26 2
Geo 5xx boiler 173 burn2workmin burner stage 2 operating time time (>=0<=16777214) minutes False sensor.boiler_burner_stage_2_operating_time sensor.boiler_burn2workmin 5 0 1 28 2
Geo 5xx boiler 173 heatworkmin total heat operating time time (>=0<=16777214) minutes False sensor.boiler_total_heat_operating_time sensor.boiler_heatworkmin 5 0 1 30 2
Geo 5xx boiler 173 heatstarts burner starts heating uint24 (>=0<=16777214) False sensor.boiler_burner_starts_heating sensor.boiler_heatstarts 5 0 1 32 2
Geo 5xx boiler 173 ubauptime total UBA operating time time (>=0<=16777214) minutes False sensor.boiler_total_UBA_operating_time sensor.boiler_ubauptime 5 0 1 34 2
Geo 5xx boiler 173 lastcode last error code string False sensor.boiler_last_error_code sensor.boiler_lastcode 5 0 1 36 28
Geo 5xx boiler 173 servicecode service code string False sensor.boiler_service_code sensor.boiler_servicecode 5 0 1 64 2
Geo 5xx boiler 173 servicecodenumber service code number uint16 (>=0<=31999) False sensor.boiler_service_code_number sensor.boiler_servicecodenumber 5 0 1 66 1
Geo 5xx boiler 173 maintenancemessage maintenance message string False sensor.boiler_maintenance_message sensor.boiler_maintenancemessage 5 0 1 67 2
Geo 5xx boiler 173 maintenance maintenance scheduled enum [off|time|date|manual] True select.boiler_maintenance_scheduled select.boiler_maintenance 5 0 1 69 1
Geo 5xx boiler 173 maintenancetime time to next maintenance uint16 (>=0<=31999) hours True number.boiler_time_to_next_maintenance number.boiler_maintenancetime 5 0 1 70 1
Geo 5xx boiler 173 maintenancedate next maintenance date string True sensor.boiler_next_maintenance_date sensor.boiler_maintenancedate 5 0 1 71 6
Geo 5xx boiler 173 emergencyops emergency operation boolean True switch.boiler_emergency_operation switch.boiler_emergencyops 5 0 1 77 1
Geo 5xx boiler 173 emergencytemp emergency temperature uint8 (>=15<=70) C True number.boiler_emergency_temperature number.boiler_emergencytemp 5 0 1 78 1
Geo 5xx boiler 173 pc0flow Flow PC0 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC0 sensor.boiler_pc0flow 5 0 1 79 1
Geo 5xx boiler 173 pc1flow Flow PC1 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC1 sensor.boiler_pc1flow 5 0 1 80 1
Geo 5xx boiler 173 pc1on PC1 boolean False binary_sensor.boiler_PC1 binary_sensor.boiler_pc1on 5 0 1 81 1
Geo 5xx boiler 173 pc1rate PC1 rate uint8 (>=0<=100) % False sensor.boiler_PC1_rate sensor.boiler_pc1rate 5 0 1 82 1
Geo 5xx boiler 173 nrgtotal total energy uint24 (>=0<=167772) kWh False sensor.boiler_total_energy sensor.boiler_nrgtotal 5 0 1/100 83 2
Geo 5xx boiler 173 dhw.nrg energy uint24 (>=0<=167772) kWh False sensor.boiler_dhw_energy sensor.boiler_dhw_nrg 5 9 1/100 0 2
Geo 5xx boiler 173 nrgheat energy heating uint24 (>=0<=167772) kWh False sensor.boiler_energy_heating sensor.boiler_nrgheat 5 0 1/100 85 2
Geo 5xx boiler 173 nrgcool energy cooling uint24 (>=0<=167772) kWh False sensor.boiler_energy_cooling sensor.boiler_nrgcool 5 0 1/100 87 2
Geo 5xx boiler 173 metertotal meter total uint24 (>=0<=167772) kWh False sensor.boiler_meter_total sensor.boiler_metertotal 5 0 1/100 89 2
Geo 5xx boiler 173 metercomp meter compressor uint24 (>=0<=167772) kWh False sensor.boiler_meter_compressor sensor.boiler_metercomp 5 0 1/100 91 2
Geo 5xx boiler 173 metereheat meter e-heater uint24 (>=0<=167772) kWh False sensor.boiler_meter_e-heater sensor.boiler_metereheat 5 0 1/100 93 2
Geo 5xx boiler 173 meterheat meter heating uint24 (>=0<=167772) kWh False sensor.boiler_meter_heating sensor.boiler_meterheat 5 0 1/100 95 2
Geo 5xx boiler 173 metercool meter cooling uint24 (>=0<=167772) kWh False sensor.boiler_meter_cooling sensor.boiler_metercool 5 0 1/100 97 2
Geo 5xx boiler 173 dhw.meter meter uint24 (>=0<=167772) kWh False sensor.boiler_dhw_meter sensor.boiler_dhw_meter 5 9 1/100 2 2
Geo 5xx boiler 173 uptimetotal heatpump total uptime time (>=0<=279620) minutes False sensor.boiler_heatpump_total_uptime sensor.boiler_uptimetotal 5 0 1/60 99 2
Geo 5xx boiler 173 uptimecontrol total operating time heat time (>=0<=279620) minutes False sensor.boiler_total_operating_time_heat sensor.boiler_uptimecontrol 5 0 1/60 101 2
Geo 5xx boiler 173 uptimecompheating operating time compressor heating time (>=0<=279620) minutes False sensor.boiler_operating_time_compressor_heating sensor.boiler_uptimecompheating 5 0 1/60 103 2
Geo 5xx boiler 173 uptimecompcooling operating time compressor cooling time (>=0<=279620) minutes False sensor.boiler_operating_time_compressor_cooling sensor.boiler_uptimecompcooling 5 0 1/60 105 2
Geo 5xx boiler 173 dhw.uptimecomp operating time compressor time (>=0<=279620) minutes False sensor.boiler_dhw_operating_time_compressor sensor.boiler_dhw_uptimecomp 5 9 1/60 4 2
Geo 5xx boiler 173 uptimecomppool operating time compressor pool time (>=0<=279620) minutes False sensor.boiler_operating_time_compressor_pool sensor.boiler_uptimecomppool 5 0 1/60 107 2
Geo 5xx boiler 173 totalcompstarts total compressor control starts uint24 (>=0<=16777214) False sensor.boiler_total_compressor_control_starts sensor.boiler_totalcompstarts 5 0 1 109 2
Geo 5xx boiler 173 heatingstarts heating control starts uint24 (>=0<=16777214) False sensor.boiler_heating_control_starts sensor.boiler_heatingstarts 5 0 1 111 2
Geo 5xx boiler 173 coolingstarts cooling control starts uint24 (>=0<=16777214) False sensor.boiler_cooling_control_starts sensor.boiler_coolingstarts 5 0 1 113 2
Geo 5xx boiler 173 dhw.startshp starts hp uint24 (>=0<=16777214) False sensor.boiler_dhw_starts_hp sensor.boiler_dhw_startshp 5 9 1 6 2
Geo 5xx boiler 173 poolstarts pool control starts uint24 (>=0<=16777214) False sensor.boiler_pool_control_starts sensor.boiler_poolstarts 5 0 1 115 2
Geo 5xx boiler 173 nrgconstotal total energy consumption uint24 (>=0<=16777214) kWh False sensor.boiler_total_energy_consumption sensor.boiler_nrgconstotal 5 0 1 117 2
Geo 5xx boiler 173 nrgconscomptotal total energy consumption compressor uint24 (>=0<=16777214) kWh False sensor.boiler_total_energy_consumption_compressor sensor.boiler_nrgconscomptotal 5 0 1 119 2
Geo 5xx boiler 173 nrgconscompheating energy consumption compressor heating uint24 (>=0<=16777214) kWh False sensor.boiler_energy_consumption_compressor_heating sensor.boiler_nrgconscompheating 5 0 1 121 2
Geo 5xx boiler 173 dhw.nrgconscomp energy consumption compressor uint24 (>=0<=16777214) kWh False sensor.boiler_dhw_energy_consumption_compressor sensor.boiler_dhw_nrgconscomp 5 9 1 8 2
Geo 5xx boiler 173 nrgconscompcooling energy consumption compressor cooling uint24 (>=0<=16777214) kWh False sensor.boiler_energy_consumption_compressor_cooling sensor.boiler_nrgconscompcooling 5 0 1 123 2
Geo 5xx boiler 173 nrgconscomppool energy consumption compressor pool uint24 (>=0<=16777214) kWh False sensor.boiler_energy_consumption_compressor_pool sensor.boiler_nrgconscomppool 5 0 1 125 2
Geo 5xx boiler 173 auxelecheatnrgconstotal total aux elec. heater energy consumption uint24 (>=0<=16777214) kWh False sensor.boiler_total_aux_elec._heater_energy_consumption sensor.boiler_auxelecheatnrgconstotal 5 0 1 127 2
Geo 5xx boiler 173 auxelecheatnrgconsheating aux elec. heater energy consumption heating uint24 (>=0<=16777214) kWh False sensor.boiler_aux_elec._heater_energy_consumption_heating sensor.boiler_auxelecheatnrgconsheating 5 0 1 129 2
Geo 5xx boiler 173 dhw.auxelecheatnrgcons aux elec. heater energy consumption uint24 (>=0<=16777214) kWh False sensor.boiler_dhw_aux_elec._heater_energy_consumption sensor.boiler_dhw_auxelecheatnrgcons 5 9 1 10 2
Geo 5xx boiler 173 auxelecheatnrgconspool aux elec. heater energy consumption pool uint24 (>=0<=16777214) kWh False sensor.boiler_aux_elec._heater_energy_consumption_pool sensor.boiler_auxelecheatnrgconspool 5 0 1 131 2
Geo 5xx boiler 173 nrgsupptotal total energy supplied uint24 (>=0<=16777214) kWh False sensor.boiler_total_energy_supplied sensor.boiler_nrgsupptotal 5 0 1 133 2
Geo 5xx boiler 173 nrgsuppheating total energy supplied heating uint24 (>=0<=16777214) kWh False sensor.boiler_total_energy_supplied_heating sensor.boiler_nrgsuppheating 5 0 1 135 2
Geo 5xx boiler 173 dhw.nrgsupp total energy warm supplied uint24 (>=0<=16777214) kWh False sensor.boiler_dhw_total_energy_warm_supplied sensor.boiler_dhw_nrgsupp 5 9 1 12 2
Geo 5xx boiler 173 nrgsuppcooling total energy supplied cooling uint24 (>=0<=16777214) kWh False sensor.boiler_total_energy_supplied_cooling sensor.boiler_nrgsuppcooling 5 0 1 137 2
Geo 5xx boiler 173 nrgsupppool total energy supplied pool uint24 (>=0<=16777214) kWh False sensor.boiler_total_energy_supplied_pool sensor.boiler_nrgsupppool 5 0 1 139 2
Geo 5xx boiler 173 hppower compressor power output uint16 (>=0<=3199) kW False sensor.boiler_compressor_power_output sensor.boiler_hppower 5 0 1/10 141 1
Geo 5xx boiler 173 hpmaxpower compressor max power uint8 (>=0<=100) % True number.boiler_compressor_max_power number.boiler_hpmaxpower 5 0 1 142 1
Geo 5xx boiler 173 pvmaxcomp pv compressor max power uint8 (>=0<=25) kW True number.boiler_pv_compressor_max_power number.boiler_pvmaxcomp 5 0 1/10 143 1
Geo 5xx boiler 173 powerreduction power reduction uint8 (>=30<=60) % True number.boiler_power_reduction number.boiler_powerreduction 5 0 10 144 1
Geo 5xx boiler 173 hpsetdiffpress set differential pressure uint8 (>=150<=750) mbar True number.boiler_set_differential_pressure number.boiler_hpsetdiffpress 5 0 50 145 1
Geo 5xx boiler 173 hpcompon hp compressor boolean False binary_sensor.boiler_hp_compressor binary_sensor.boiler_hpcompon 5 0 1 146 1
Geo 5xx boiler 173 hpactivity compressor activity enum [off|heating|cooling|hot water|pool|pool heating|defrost|compressor alarm] False sensor.boiler_compressor_activity sensor.boiler_hpactivity 5 0 1 147 1
Geo 5xx boiler 173 hpbrinepumpspd brine pump speed uint8 (>=0<=100) % False sensor.boiler_brine_pump_speed sensor.boiler_hpbrinepumpspd 5 0 1 148 1
Geo 5xx boiler 173 hpswitchvalve switch valve boolean False binary_sensor.boiler_switch_valve binary_sensor.boiler_hpswitchvalve 5 0 1 149 1
Geo 5xx boiler 173 hpcompspd compressor speed uint8 (>=0<=100) % False sensor.boiler_compressor_speed sensor.boiler_hpcompspd 5 0 1 150 1
Geo 5xx boiler 173 hpcircspd circulation pump speed uint8 (>=0<=100) % False sensor.boiler_circulation_pump_speed sensor.boiler_hpcircspd 5 0 1 151 1
Geo 5xx boiler 173 hpbrinein brine in/evaporator int16 (>=-3199<=3199) C False sensor.boiler_brine_in/evaporator sensor.boiler_hpbrinein 5 0 1/10 152 1
Geo 5xx boiler 173 hpbrineout brine out/condenser int16 (>=-3199<=3199) C False sensor.boiler_brine_out/condenser sensor.boiler_hpbrineout 5 0 1/10 153 1
Geo 5xx boiler 173 hptc0 heat carrier return (TC0) int16 (>=-3199<=3199) C False sensor.boiler_heat_carrier_return_(TC0) sensor.boiler_hptc0 5 0 1/10 154 1
Geo 5xx boiler 173 hptc1 heat carrier forward (TC1) int16 (>=-3199<=3199) C False sensor.boiler_heat_carrier_forward_(TC1) sensor.boiler_hptc1 5 0 1/10 155 1
Geo 5xx boiler 173 hptc3 condenser temperature (TC3) int16 (>=-3199<=3199) C False sensor.boiler_condenser_temperature_(TC3) sensor.boiler_hptc3 5 0 1/10 156 1
Geo 5xx boiler 173 hptr1 compressor temperature (TR1) int16 (>=-3199<=3199) C False sensor.boiler_compressor_temperature_(TR1) sensor.boiler_hptr1 5 0 1/10 157 1
Geo 5xx boiler 173 hptr3 refrigerant temperature liquid side (condenser output) (TR3) int16 (>=-3199<=3199) C False sensor.boiler_refrigerant_temperature_liquid_side_(condenser_output)_(TR3) sensor.boiler_hptr3 5 0 1/10 158 1
Geo 5xx boiler 173 hptr4 evaporator inlet temperature (TR4) int16 (>=-3199<=3199) C False sensor.boiler_evaporator_inlet_temperature_(TR4) sensor.boiler_hptr4 5 0 1/10 159 1
Geo 5xx boiler 173 hptr5 compressor inlet temperature (TR5) int16 (>=-3199<=3199) C False sensor.boiler_compressor_inlet_temperature_(TR5) sensor.boiler_hptr5 5 0 1/10 160 1
Geo 5xx boiler 173 hptr6 compressor outlet temperature (TR6) int16 (>=-3199<=3199) C False sensor.boiler_compressor_outlet_temperature_(TR6) sensor.boiler_hptr6 5 0 1/10 161 1
Geo 5xx boiler 173 hptr7 refrigerant temperature gas side (condenser input) (TR7) int16 (>=-3199<=3199) C False sensor.boiler_refrigerant_temperature_gas_side_(condenser_input)_(TR7) sensor.boiler_hptr7 5 0 1/10 162 1
Geo 5xx boiler 173 hptl2 air inlet temperature (TL2) int16 (>=-3199<=3199) C False sensor.boiler_air_inlet_temperature_(TL2) sensor.boiler_hptl2 5 0 1/10 163 1
Geo 5xx boiler 173 hppl1 low pressure side temperature (PL1) int16 (>=-3199<=3199) C False sensor.boiler_low_pressure_side_temperature_(PL1) sensor.boiler_hppl1 5 0 1/10 164 1
Geo 5xx boiler 173 hpph1 high pressure side temperature (PH1) int16 (>=-3199<=3199) C False sensor.boiler_high_pressure_side_temperature_(PH1) sensor.boiler_hpph1 5 0 1/10 165 1
Geo 5xx boiler 173 hpta4 drain pan temp (TA4) int16 (>=-3199<=3199) C False sensor.boiler_drain_pan_temp_(TA4) sensor.boiler_hpta4 5 0 1/10 166 1
Geo 5xx boiler 173 hptw1 reservoir temp (TW1) int16 (>=-3199<=3199) C False sensor.boiler_reservoir_temp_(TW1) sensor.boiler_hptw1 5 0 1/10 167 1
Geo 5xx boiler 173 poolsettemp pool set temperature uint8 (>=0<=127) C True number.boiler_pool_set_temperature number.boiler_poolsettemp 5 0 1/2 168 1
Geo 5xx boiler 173 hp4way 4-way valve (VR4) enum [cooling & defrost|heating & dhw] False sensor.boiler_4-way_valve_(VR4) sensor.boiler_hp4way 5 0 1 169 1
Geo 5xx boiler 173 hpin1 input 1 state boolean False binary_sensor.boiler_input_1_state binary_sensor.boiler_hpin1 5 0 1 170 1
Geo 5xx boiler 173 hpin1opt input 1 options string True sensor.boiler_input_1_options sensor.boiler_hpin1opt 5 0 1 171 8
Geo 5xx boiler 173 hpin2 input 2 state boolean False binary_sensor.boiler_input_2_state binary_sensor.boiler_hpin2 5 0 1 179 1
Geo 5xx boiler 173 hpin2opt input 2 options string True sensor.boiler_input_2_options sensor.boiler_hpin2opt 5 0 1 180 8
Geo 5xx boiler 173 hpin3 input 3 state boolean False binary_sensor.boiler_input_3_state binary_sensor.boiler_hpin3 5 0 1 188 1
Geo 5xx boiler 173 hpin3opt input 3 options string True sensor.boiler_input_3_options sensor.boiler_hpin3opt 5 0 1 189 8
Geo 5xx boiler 173 hpin4 input 4 state boolean False binary_sensor.boiler_input_4_state binary_sensor.boiler_hpin4 5 0 1 197 1
Geo 5xx boiler 173 hpin4opt input 4 options string True sensor.boiler_input_4_options sensor.boiler_hpin4opt 5 0 1 198 8
Geo 5xx boiler 173 maxheatcomp heat limit compressor enum [0 kW|2 kW|3 kW|4 kW|6 kW|9 kW] True select.boiler_heat_limit_compressor select.boiler_maxheatcomp 5 0 1 206 1
Geo 5xx boiler 173 maxheatheat heat limit heating enum [0 kW|2 kW|3 kW|4 kW|6 kW|9 kW] True select.boiler_heat_limit_heating select.boiler_maxheatheat 5 0 1 207 1
Geo 5xx boiler 173 dhw.maxheat heat limit enum [0 kW|2 kW|3 kW|4 kW|6 kW|9 kW] True select.boiler_dhw_heat_limit select.boiler_dhw_maxheat 5 9 1 14 1
Geo 5xx boiler 173 auxheatersource aux heater source enum [not installed|electric heater|exclusive|parallel|hybrid] True select.boiler_aux_heater_source select.boiler_auxheatersource 5 0 1 208 1
Geo 5xx boiler 173 pvcooling cooling only with PV boolean True switch.boiler_cooling_only_with_PV switch.boiler_pvcooling 5 0 1 209 1
Geo 5xx boiler 173 auxheateronly aux heater only boolean True switch.boiler_aux_heater_only switch.boiler_auxheateronly 5 0 1 210 1
Geo 5xx boiler 173 auxheateroff disable aux heater boolean True switch.boiler_disable_aux_heater switch.boiler_auxheateroff 5 0 1 211 1
Geo 5xx boiler 173 auxheaterstatus aux heater status enum [off|heating|cooling|hot water|pool|pool heating|defrost|compressor alarm] False sensor.boiler_aux_heater_status sensor.boiler_auxheaterstatus 5 0 1 212 1
Geo 5xx boiler 173 auxheaterlevel aux heater level uint8 (>=0<=100) % False sensor.boiler_aux_heater_level sensor.boiler_auxheaterlevel 5 0 1 213 1
Geo 5xx boiler 173 auxheaterdelay aux heater on delay uint16 (>=10<=1000) K*min True number.boiler_aux_heater_on_delay number.boiler_auxheaterdelay 5 0 10 214 1
Geo 5xx boiler 173 auxmaxlimit aux heater max limit uint8 (>=0<=10) K True number.boiler_aux_heater_max_limit number.boiler_auxmaxlimit 5 0 1/10 215 1
Geo 5xx boiler 173 auxlimitstart aux heater limit start uint8 (>=0<=10) K True number.boiler_aux_heater_limit_start number.boiler_auxlimitstart 5 0 1/10 216 1
Geo 5xx boiler 173 auxheatrmode aux heater mode enum [eco|comfort] True select.boiler_aux_heater_mode select.boiler_auxheatrmode 5 0 1 217 1
Geo 5xx boiler 173 hphystheat on/off hyst heat uint16 (>=50<=1500) K*min True number.boiler_on/off_hyst_heat number.boiler_hphystheat 5 0 5 218 1
Geo 5xx boiler 173 hphystcool on/off hyst cool uint16 (>=50<=1500) K*min True number.boiler_on/off_hyst_cool number.boiler_hphystcool 5 0 5 219 1
Geo 5xx boiler 173 hphystpool on/off hyst pool uint16 (>=50<=1500) K*min True number.boiler_on/off_hyst_pool number.boiler_hphystpool 5 0 5 220 1
Geo 5xx boiler 173 silentmode silent mode enum [off|auto|on] True select.boiler_silent_mode select.boiler_silentmode 5 0 1 221 1
Geo 5xx boiler 173 silentfrom silent mode from uint8 (>=0<=3810) minutes True number.boiler_silent_mode_from number.boiler_silentfrom 5 0 15 222 1
Geo 5xx boiler 173 silentto silent mode to uint8 (>=0<=3810) minutes True number.boiler_silent_mode_to number.boiler_silentto 5 0 15 223 1
Geo 5xx boiler 173 mintempsilent min outside temp for silent mode int8 (>=-126<=126) C True number.boiler_min_outside_temp_for_silent_mode number.boiler_mintempsilent 5 0 1 224 1
Geo 5xx boiler 173 tempparmode outside temp parallel mode int8 (>=-126<=126) C True number.boiler_outside_temp_parallel_mode number.boiler_tempparmode 5 0 1 225 1
Geo 5xx boiler 173 auxheatmix aux heater mixing valve int8 (>=-100<=100) % False sensor.boiler_aux_heater_mixing_valve sensor.boiler_auxheatmix 5 0 1 226 1
Geo 5xx boiler 173 tempdiffheat temp diff TC3/TC0 heat uint8 (>=2<=10) K True number.boiler_temp_diff_TC3/TC0_heat number.boiler_tempdiffheat 5 0 1/10 227 1
Geo 5xx boiler 173 tempdiffcool temp diff TC3/TC0 cool uint8 (>=2<=10) K True number.boiler_temp_diff_TC3/TC0_cool number.boiler_tempdiffcool 5 0 1/10 228 1
Geo 5xx boiler 173 vpcooling valve/pump cooling boolean True switch.boiler_valve/pump_cooling switch.boiler_vpcooling 5 0 1 229 1
Geo 5xx boiler 173 heatcable heating cable boolean True switch.boiler_heating_cable switch.boiler_heatcable 5 0 1 230 1
Geo 5xx boiler 173 vc0valve VC0 valve boolean True switch.boiler_VC0_valve switch.boiler_vc0valve 5 0 1 231 1
Geo 5xx boiler 173 primepump primary heatpump boolean True switch.boiler_primary_heatpump switch.boiler_primepump 5 0 1 232 1
Geo 5xx boiler 173 primepumpmod primary heatpump modulation uint8 (>=0<=100) % True number.boiler_primary_heatpump_modulation number.boiler_primepumpmod 5 0 1 233 1
Geo 5xx boiler 173 hp3way 3-way valve boolean True switch.boiler_3-way_valve switch.boiler_hp3way 5 0 1 234 1
Geo 5xx boiler 173 elheatstep1 el. heater step 1 boolean True switch.boiler_el._heater_step_1 switch.boiler_elheatstep1 5 0 1 235 1
Geo 5xx boiler 173 elheatstep2 el. heater step 2 boolean True switch.boiler_el._heater_step_2 switch.boiler_elheatstep2 5 0 1 236 1
Geo 5xx boiler 173 elheatstep3 el. heater step 3 boolean True switch.boiler_el._heater_step_3 switch.boiler_elheatstep3 5 0 1 237 1
Geo 5xx boiler 173 hpea0 condensate reservoir heating (EA0) boolean False binary_sensor.boiler_condensate_reservoir_heating_(EA0) binary_sensor.boiler_hpea0 5 0 1 238 1
Geo 5xx boiler 173 hppumpmode primary heatpump mode enum [auto|continuous] True select.boiler_primary_heatpump_mode select.boiler_hppumpmode 5 0 1 239 1
Geo 5xx boiler 173 fan fan uint8 (>=20<=100) % True number.boiler_fan number.boiler_fan 5 0 1 240 1
Geo 5xx boiler 173 shutdown shutdown cmd [off|on] True sensor.boiler_shutdown sensor.boiler_shutdown 5 0 1 241 1
Geo 5xx boiler 173 hpcurrpower compressor current power uint16 (>=0<=31999) W False sensor.boiler_compressor_current_power sensor.boiler_hpcurrpower 5 0 1 242 1
Geo 5xx boiler 173 hppowerlimit power limit uint16 (>=0<=31999) W True number.boiler_power_limit number.boiler_hppowerlimit 5 0 1 243 1
Geo 5xx boiler 173 dhw.alternatingop alternating operation boolean True switch.boiler_dhw_alternating_operation switch.boiler_dhw_alternatingop 5 9 1 15 1
Geo 5xx boiler 173 dhw.altopprioheat prioritise heating during dhw uint8 (>=20<=120) minutes True number.boiler_dhw_prioritise_heating_during_dhw number.boiler_dhw_altopprioheat 5 9 1 16 1
Geo 5xx boiler 173 dhw.altopprio prioritise dhw during heating uint8 (>=30<=120) minutes True number.boiler_dhw_prioritise_dhw_during_heating number.boiler_dhw_altopprio 5 9 1 17 1
Geo 5xx boiler 173 dhw.comfoff comfort switch off uint8 (>=15<=65) C True number.boiler_dhw_comfort_switch_off number.boiler_dhw_comfoff 5 9 1 18 1
Geo 5xx boiler 173 dhw.ecooff eco switch off uint8 (>=15<=65) C True number.boiler_dhw_eco_switch_off number.boiler_dhw_ecooff 5 9 1 19 1
Geo 5xx boiler 173 dhw.ecoplusoff eco+ switch off uint8 (>=48<=63) C True number.boiler_dhw_eco+_switch_off number.boiler_dhw_ecoplusoff 5 9 1 20 1
Geo 5xx boiler 173 dhw.comfdiff comfort diff uint8 (>=6<=12) K True number.boiler_dhw_comfort_diff number.boiler_dhw_comfdiff 5 9 1 21 1
Geo 5xx boiler 173 dhw.ecodiff eco diff uint8 (>=6<=12) K True number.boiler_dhw_eco_diff number.boiler_dhw_ecodiff 5 9 1 22 1
Geo 5xx boiler 173 dhw.ecoplusdiff eco+ diff uint8 (>=6<=12) K True number.boiler_dhw_eco+_diff number.boiler_dhw_ecoplusdiff 5 9 1 23 1
Geo 5xx boiler 173 dhw.comfstop comfort stop temp uint8 (>=0<=254) C True number.boiler_dhw_comfort_stop_temp number.boiler_dhw_comfstop 5 9 1 24 1
Geo 5xx boiler 173 dhw.ecostop eco stop temp uint8 (>=0<=254) C True number.boiler_dhw_eco_stop_temp number.boiler_dhw_ecostop 5 9 1 25 1
Geo 5xx boiler 173 dhw.ecoplusstop eco+ stop temp uint8 (>=0<=254) C True number.boiler_dhw_eco+_stop_temp number.boiler_dhw_ecoplusstop 5 9 1 26 1
Geo 5xx boiler 173 dhw.hpcircpump circulation pump available during dhw boolean True switch.boiler_dhw_circulation_pump_available_during_dhw switch.boiler_dhw_hpcircpump 5 9 1 27 1
Geo 5xx boiler 173 dhw.tapactivated turn on/off boolean True switch.boiler_dhw_turn_on/off switch.boiler_dhw_tapactivated 5 9 1 28 1
Geo 5xx boiler 173 dhw.settemp set temperature uint8 (>=0<=254) C False sensor.boiler_dhw_set_temperature sensor.boiler_dhw_settemp 5 9 1 29 1
Geo 5xx boiler 173 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_temperature number.boiler_dhw_seltemp 5 9 1 30 1
Geo 5xx boiler 173 dhw.seltemplow selected lower temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_lower_temperature number.boiler_dhw_seltemplow 5 9 1 31 1
Geo 5xx boiler 173 dhw.tempecoplus selected eco+ temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_eco+_temperature number.boiler_dhw_tempecoplus 5 9 1 32 1
Geo 5xx boiler 173 dhw.seltempoff selected temperature for off uint8 (>=0<=254) C False sensor.boiler_dhw_selected_temperature_for_off sensor.boiler_dhw_seltempoff 5 9 1 33 1
Geo 5xx boiler 173 dhw.seltempsingle single charge temperature uint8 (>=0<=254) C True number.boiler_dhw_single_charge_temperature number.boiler_dhw_seltempsingle 5 9 1 34 1
Geo 5xx boiler 173 dhw.solartemp solar boiler temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_solar_boiler_temperature sensor.boiler_dhw_solartemp 5 9 1/10 35 1
Geo 5xx boiler 173 dhw.type type enum [off|flow|buffered flow|buffer|layered buffer] False sensor.boiler_dhw_type sensor.boiler_dhw_type 5 9 1 36 1
Geo 5xx boiler 173 dhw.comfort comfort enum [hot|eco|intelligent] True select.boiler_dhw_comfort select.boiler_dhw_comfort 5 9 1 37 1
Geo 5xx boiler 173 dhw.comfort1 comfort mode enum [high comfort|eco] True select.boiler_dhw_comfort_mode select.boiler_dhw_comfort1 5 9 1 38 1
Geo 5xx boiler 173 dhw.flowtempoffset flow temperature offset uint8 (>=0<=100) C True number.boiler_dhw_flow_temperature_offset number.boiler_dhw_flowtempoffset 5 9 1 39 1
Geo 5xx boiler 173 dhw.chargeoptimization charge optimization boolean True switch.boiler_dhw_charge_optimization switch.boiler_dhw_chargeoptimization 5 9 1 40 1
Geo 5xx boiler 173 dhw.maxpower max power uint8 (>=0<=254) % True number.boiler_dhw_max_power number.boiler_dhw_maxpower 5 9 1 41 1
Geo 5xx boiler 173 dhw.maxtemp maximum temperature uint8 (>=0<=80) C True number.boiler_dhw_maximum_temperature number.boiler_dhw_maxtemp 5 9 1 42 1
Geo 5xx boiler 173 dhw.circpump circulation pump available boolean True switch.boiler_dhw_circulation_pump_available switch.boiler_dhw_circpump 5 9 1 43 1
Geo 5xx boiler 173 dhw.chargetype charging type enum [chargepump|3-way valve] False sensor.boiler_dhw_charging_type sensor.boiler_dhw_chargetype 5 9 1 44 1
Geo 5xx boiler 173 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_on_temperature number.boiler_dhw_hyston 5 9 1 45 1
Geo 5xx boiler 173 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_off_temperature number.boiler_dhw_hystoff 5 9 1 46 1
Geo 5xx boiler 173 dhw.disinfectiontemp disinfection temperature uint8 (>=60<=80) C True number.boiler_dhw_disinfection_temperature number.boiler_dhw_disinfectiontemp 5 9 1 47 1
Geo 5xx boiler 173 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.boiler_dhw_circulation_pump_mode select.boiler_dhw_circmode 5 9 1 48 1
Geo 5xx boiler 173 dhw.circ circulation active boolean True switch.boiler_dhw_circulation_active switch.boiler_dhw_circ 5 9 1 49 1
Geo 5xx boiler 173 dhw.curtemp current intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_intern_temperature sensor.boiler_dhw_curtemp 5 9 1/10 50 1
Geo 5xx boiler 173 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_extern_temperature sensor.boiler_dhw_curtemp2 5 9 1/10 51 1
Geo 5xx boiler 173 dhw.curflow current tap water flow uint8 (>=0<=25) l/min False sensor.boiler_dhw_current_tap_water_flow sensor.boiler_dhw_curflow 5 9 1/10 52 1
Geo 5xx boiler 173 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_intern_temperature sensor.boiler_dhw_storagetemp1 5 9 1/10 53 1
Geo 5xx boiler 173 dhw.storagetemp2 storage extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_extern_temperature sensor.boiler_dhw_storagetemp2 5 9 1/10 54 1
Geo 5xx boiler 173 dhw.activated activated boolean True switch.boiler_dhw_activated switch.boiler_dhw_activated 5 9 1 55 1
Geo 5xx boiler 173 dhw.onetime one time charging boolean True switch.boiler_dhw_one_time_charging switch.boiler_dhw_onetime 5 9 1 56 1
Geo 5xx boiler 173 dhw.disinfecting disinfecting boolean True switch.boiler_dhw_disinfecting switch.boiler_dhw_disinfecting 5 9 1 57 1
Geo 5xx boiler 173 dhw.charging charging boolean False binary_sensor.boiler_dhw_charging binary_sensor.boiler_dhw_charging 5 9 1 58 1
Geo 5xx boiler 173 dhw.recharging recharging boolean False binary_sensor.boiler_dhw_recharging binary_sensor.boiler_dhw_recharging 5 9 1 59 1
Geo 5xx boiler 173 dhw.tempok temperature ok boolean False binary_sensor.boiler_dhw_temperature_ok binary_sensor.boiler_dhw_tempok 5 9 1 60 1
Geo 5xx boiler 173 dhw.active active boolean False binary_sensor.boiler_dhw_active binary_sensor.boiler_dhw_active 5 9 1 61 1
Geo 5xx boiler 173 dhw.3wayvalve 3-way valve active boolean False binary_sensor.boiler_dhw_3-way_valve_active binary_sensor.boiler_dhw_3wayvalve 5 9 1 62 1
Geo 5xx boiler 173 dhw.mixertemp mixer temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_mixer_temperature sensor.boiler_dhw_mixertemp 5 9 1/10 63 1
Geo 5xx boiler 173 dhw.cylmiddletemp cylinder middle temperature (TS3) uint16 (>=0<=3199) C False sensor.boiler_dhw_cylinder_middle_temperature_(TS3) sensor.boiler_dhw_cylmiddletemp 5 9 1/10 64 1
Geo 5xx boiler 173 dhw.starts starts uint24 (>=0<=16777214) False sensor.boiler_dhw_starts sensor.boiler_dhw_starts 5 9 1 65 2
Geo 5xx boiler 173 dhw.workm active time time (>=0<=16777214) minutes False sensor.boiler_dhw_active_time sensor.boiler_dhw_workm 5 9 1 67 2
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 reset reset cmd [-|maintenance|error|history|message] True sensor.boiler_reset sensor.boiler_reset 5 0 1 0 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 heatingoff force heating off boolean True switch.boiler_force_heating_off switch.boiler_heatingoff 5 0 1 1 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 heatingactive heating active boolean False binary_sensor.boiler_heating_active binary_sensor.boiler_heatingactive 5 0 1 2 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 tapwateractive tapwater active boolean False binary_sensor.boiler_tapwater_active binary_sensor.boiler_tapwateractive 5 0 1 3 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 selflowtemp selected flow temperature uint8 (>=0<=90) C True number.boiler_selected_flow_temperature number.boiler_selflowtemp 5 0 1 4 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.boiler_heating_pump_modulation sensor.boiler_heatingpumpmod 5 0 1 5 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 outdoortemp outside temperature int16 (>=-3199<=3199) C False sensor.boiler_outside_temperature sensor.boiler_outdoortemp 5 0 1/10 6 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 curflowtemp current flow temperature uint16 (>=0<=3199) C False sensor.boiler_current_flow_temperature sensor.boiler_curflowtemp 5 0 1/10 7 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 rettemp return temperature uint16 (>=0<=3199) C False sensor.boiler_return_temperature sensor.boiler_rettemp 5 0 1/10 8 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 switchtemp mixing switch temperature uint16 (>=0<=3199) C False sensor.boiler_mixing_switch_temperature sensor.boiler_switchtemp 5 0 1/10 9 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 syspress system pressure uint8 (>=0<=25) bar False sensor.boiler_system_pressure sensor.boiler_syspress 5 0 1/10 10 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 boiltemp actual boiler temperature uint16 (>=0<=3199) C False sensor.boiler_actual_boiler_temperature sensor.boiler_boiltemp 5 0 1/10 11 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 headertemp low loss header uint16 (>=0<=3199) C False sensor.boiler_low_loss_header sensor.boiler_headertemp 5 0 1/10 12 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 exhausttemp exhaust temperature uint16 (>=0<=3199) C False sensor.boiler_exhaust_temperature sensor.boiler_exhausttemp 5 0 1/10 244 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 burngas gas boolean False binary_sensor.boiler_gas binary_sensor.boiler_burngas 5 0 1 245 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 burngas2 gas stage 2 boolean False binary_sensor.boiler_gas_stage_2 binary_sensor.boiler_burngas2 5 0 1 246 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 flamecurr flame current uint16 (>=0<=3199) µA False sensor.boiler_flame_current sensor.boiler_flamecurr 5 0 1/10 247 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 fanwork fan boolean False binary_sensor.boiler_fan binary_sensor.boiler_fanwork 5 0 1 248 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 ignwork ignition boolean False binary_sensor.boiler_ignition binary_sensor.boiler_ignwork 5 0 1 249 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 oilpreheat oil preheating boolean False binary_sensor.boiler_oil_preheating binary_sensor.boiler_oilpreheat 5 0 1 250 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 burnminpower burner min power uint8 (>=0<=100) % True number.boiler_burner_min_power number.boiler_burnminpower 5 0 1 251 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 burnmaxpower burner max power uint8 (>=0<=254) % True number.boiler_burner_max_power number.boiler_burnmaxpower 5 0 1 252 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 burnminperiod burner min period uint8 (>=0<=120) minutes True number.boiler_burner_min_period number.boiler_burnminperiod 5 0 1 253 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 absburnpow burner current power (absolute) uint8 (>=0<=100) % False sensor.boiler_burner_current_power_(absolute) sensor.boiler_absburnpow 5 0 1 254 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 heatblock heating block uint16 (>=0<=3199) C False sensor.boiler_heating_block sensor.boiler_heatblock 5 0 1/10 255 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 boilhyston hysteresis on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_on_temperature number.boiler_boilhyston 5 0 1 256 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 boilhystoff hysteresis off temperature int8 (>=0<=20) C True number.boiler_hysteresis_off_temperature number.boiler_boilhystoff 5 0 1 257 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 boil2hyston hysteresis stage 2 on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_stage_2_on_temperature number.boiler_boil2hyston 5 0 1 258 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 boil2hystoff hysteresis stage 2 off temperature int8 (>=0<=20) C True number.boiler_hysteresis_stage_2_off_temperature number.boiler_boil2hystoff 5 0 1 259 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 curveon heatingcurve on boolean True switch.boiler_heatingcurve_on switch.boiler_curveon 5 0 1 260 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 curvebase heatingcurve base uint8 (>=20<=90) C True number.boiler_heatingcurve_base number.boiler_curvebase 5 0 1 261 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 curveend heatingcurve end uint8 (>=20<=90) C True number.boiler_heatingcurve_end number.boiler_curveend 5 0 1 262 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 summertemp summer temperature uint8 (>=0<=45) C True number.boiler_summer_temperature number.boiler_summertemp 5 0 1 263 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 nofrostmode nofrost mode boolean True switch.boiler_nofrost_mode switch.boiler_nofrostmode 5 0 1 264 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 nofrosttemp nofrost temperature uint8 (>=0<=10) C True number.boiler_nofrost_temperature number.boiler_nofrosttemp 5 0 1 265 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 heatingactivated heating activated boolean True switch.boiler_heating_activated switch.boiler_heatingactivated 5 0 1 13 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 heatingtemp heating temperature uint8 (>=0<=90) C True number.boiler_heating_temperature number.boiler_heatingtemp 5 0 1 14 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 heatingpump heating pump boolean False binary_sensor.boiler_heating_pump binary_sensor.boiler_heatingpump 5 0 1 15 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 pumpmodmax boiler pump max power uint8 (>=0<=100) % True number.boiler_boiler_pump_max_power number.boiler_pumpmodmax 5 0 1 16 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 pumpmodmin boiler pump min power uint8 (>=0<=100) % True number.boiler_boiler_pump_min_power number.boiler_pumpmodmin 5 0 1 17 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 pumpmode boiler pump mode enum [proportional|deltaP-1|deltaP-2|deltaP-3|deltaP-4] True select.boiler_boiler_pump_mode select.boiler_pumpmode 5 0 1 18 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 pumpcharacter boiler pump characteristic enum [proportional|150mbar|200mbar|250mbar|300mbar|350mbar|400mbar] True select.boiler_boiler_pump_characteristic select.boiler_pumpcharacter 5 0 1 19 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 pumpdelay pump delay uint8 (>=0<=60) minutes True number.boiler_pump_delay number.boiler_pumpdelay 5 0 1 20 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 pumpontemp pump logic temperature uint8 (>=0<=60) C True number.boiler_pump_logic_temperature number.boiler_pumpontemp 5 0 1 21 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 selburnpow burner selected max power uint8 (>=0<=254) % True number.boiler_burner_selected_max_power number.boiler_selburnpow 5 0 1 22 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 curburnpow burner current power uint8 (>=0<=100) % False sensor.boiler_burner_current_power sensor.boiler_curburnpow 5 0 1 23 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 burnstarts burner starts uint24 (>=0<=16777214) False sensor.boiler_burner_starts sensor.boiler_burnstarts 5 0 1 24 2
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 burnworkmin total burner operating time time (>=0<=16777214) minutes False sensor.boiler_total_burner_operating_time sensor.boiler_burnworkmin 5 0 1 26 2
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 burn2workmin burner stage 2 operating time time (>=0<=16777214) minutes False sensor.boiler_burner_stage_2_operating_time sensor.boiler_burn2workmin 5 0 1 28 2
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 heatworkmin total heat operating time time (>=0<=16777214) minutes False sensor.boiler_total_heat_operating_time sensor.boiler_heatworkmin 5 0 1 30 2
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 heatstarts burner starts heating uint24 (>=0<=16777214) False sensor.boiler_burner_starts_heating sensor.boiler_heatstarts 5 0 1 32 2
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 ubauptime total UBA operating time time (>=0<=16777214) minutes False sensor.boiler_total_UBA_operating_time sensor.boiler_ubauptime 5 0 1 34 2
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 lastcode last error code string False sensor.boiler_last_error_code sensor.boiler_lastcode 5 0 1 36 28
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 servicecode service code string False sensor.boiler_service_code sensor.boiler_servicecode 5 0 1 64 2
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 servicecodenumber service code number uint16 (>=0<=31999) False sensor.boiler_service_code_number sensor.boiler_servicecodenumber 5 0 1 66 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 maintenancemessage maintenance message string False sensor.boiler_maintenance_message sensor.boiler_maintenancemessage 5 0 1 67 2
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 maintenance maintenance scheduled enum [off|time|date|manual] True select.boiler_maintenance_scheduled select.boiler_maintenance 5 0 1 69 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 maintenancetime time to next maintenance uint16 (>=0<=31999) hours True number.boiler_time_to_next_maintenance number.boiler_maintenancetime 5 0 1 70 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 maintenancedate next maintenance date string True sensor.boiler_next_maintenance_date sensor.boiler_maintenancedate 5 0 1 71 6
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 emergencyops emergency operation boolean True switch.boiler_emergency_operation switch.boiler_emergencyops 5 0 1 77 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 emergencytemp emergency temperature uint8 (>=15<=70) C True number.boiler_emergency_temperature number.boiler_emergencytemp 5 0 1 78 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 pc0flow Flow PC0 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC0 sensor.boiler_pc0flow 5 0 1 79 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 pc1flow Flow PC1 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC1 sensor.boiler_pc1flow 5 0 1 80 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 pc1on PC1 boolean False binary_sensor.boiler_PC1 binary_sensor.boiler_pc1on 5 0 1 81 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 pc1rate PC1 rate uint8 (>=0<=100) % False sensor.boiler_PC1_rate sensor.boiler_pc1rate 5 0 1 82 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 meterheat meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_meter_heating sensor.boiler_meterheat 5 0 1/10 95 2
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.meter meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_meter sensor.boiler_dhw_meter 5 9 1/10 2 2
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 gasmeterheat gas meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_gas_meter_heating sensor.boiler_gasmeterheat 5 0 1/10 266 2
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.gasmeter gas meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_gas_meter sensor.boiler_dhw_gasmeter 5 9 1/10 69 2
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 nrgheat2 energy heating 2 uint24 (>=0<=1677721) kWh False sensor.boiler_energy_heating_2 sensor.boiler_nrgheat2 5 0 1/10 268 2
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.nrg2 energy 2 uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_energy_2 sensor.boiler_dhw_nrg2 5 9 1/10 71 2
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.tapactivated turn on/off boolean True switch.boiler_dhw_turn_on/off switch.boiler_dhw_tapactivated 5 9 1 28 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.settemp set temperature uint8 (>=0<=254) C False sensor.boiler_dhw_set_temperature sensor.boiler_dhw_settemp 5 9 1 29 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_temperature number.boiler_dhw_seltemp 5 9 1 30 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.seltemplow selected lower temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_lower_temperature number.boiler_dhw_seltemplow 5 9 1 31 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.tempecoplus selected eco+ temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_eco+_temperature number.boiler_dhw_tempecoplus 5 9 1 32 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.seltempoff selected temperature for off uint8 (>=0<=254) C False sensor.boiler_dhw_selected_temperature_for_off sensor.boiler_dhw_seltempoff 5 9 1 33 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.seltempsingle single charge temperature uint8 (>=0<=254) C True number.boiler_dhw_single_charge_temperature number.boiler_dhw_seltempsingle 5 9 1 34 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.solartemp solar boiler temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_solar_boiler_temperature sensor.boiler_dhw_solartemp 5 9 1/10 35 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.type type enum [off|flow|buffered flow|buffer|layered buffer] False sensor.boiler_dhw_type sensor.boiler_dhw_type 5 9 1 36 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.comfort comfort enum [hot|eco|intelligent] True select.boiler_dhw_comfort select.boiler_dhw_comfort 5 9 1 37 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.comfort1 comfort mode enum [high comfort|eco] True select.boiler_dhw_comfort_mode select.boiler_dhw_comfort1 5 9 1 38 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.flowtempoffset flow temperature offset uint8 (>=0<=100) C True number.boiler_dhw_flow_temperature_offset number.boiler_dhw_flowtempoffset 5 9 1 39 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.chargeoptimization charge optimization boolean True switch.boiler_dhw_charge_optimization switch.boiler_dhw_chargeoptimization 5 9 1 40 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.maxpower max power uint8 (>=0<=254) % True number.boiler_dhw_max_power number.boiler_dhw_maxpower 5 9 1 41 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.maxtemp maximum temperature uint8 (>=0<=80) C True number.boiler_dhw_maximum_temperature number.boiler_dhw_maxtemp 5 9 1 42 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.circpump circulation pump available boolean True switch.boiler_dhw_circulation_pump_available switch.boiler_dhw_circpump 5 9 1 43 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.chargetype charging type enum [chargepump|3-way valve] False sensor.boiler_dhw_charging_type sensor.boiler_dhw_chargetype 5 9 1 44 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_on_temperature number.boiler_dhw_hyston 5 9 1 45 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_off_temperature number.boiler_dhw_hystoff 5 9 1 46 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.disinfectiontemp disinfection temperature uint8 (>=60<=80) C True number.boiler_dhw_disinfection_temperature number.boiler_dhw_disinfectiontemp 5 9 1 47 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.boiler_dhw_circulation_pump_mode select.boiler_dhw_circmode 5 9 1 48 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.circ circulation active boolean True switch.boiler_dhw_circulation_active switch.boiler_dhw_circ 5 9 1 49 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.curtemp current intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_intern_temperature sensor.boiler_dhw_curtemp 5 9 1/10 50 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_extern_temperature sensor.boiler_dhw_curtemp2 5 9 1/10 51 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.curflow current tap water flow uint8 (>=0<=25) l/min False sensor.boiler_dhw_current_tap_water_flow sensor.boiler_dhw_curflow 5 9 1/10 52 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_intern_temperature sensor.boiler_dhw_storagetemp1 5 9 1/10 53 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.storagetemp2 storage extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_extern_temperature sensor.boiler_dhw_storagetemp2 5 9 1/10 54 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.activated activated boolean True switch.boiler_dhw_activated switch.boiler_dhw_activated 5 9 1 55 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.onetime one time charging boolean True switch.boiler_dhw_one_time_charging switch.boiler_dhw_onetime 5 9 1 56 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.disinfecting disinfecting boolean True switch.boiler_dhw_disinfecting switch.boiler_dhw_disinfecting 5 9 1 57 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.charging charging boolean False binary_sensor.boiler_dhw_charging binary_sensor.boiler_dhw_charging 5 9 1 58 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.recharging recharging boolean False binary_sensor.boiler_dhw_recharging binary_sensor.boiler_dhw_recharging 5 9 1 59 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.tempok temperature ok boolean False binary_sensor.boiler_dhw_temperature_ok binary_sensor.boiler_dhw_tempok 5 9 1 60 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.active active boolean False binary_sensor.boiler_dhw_active binary_sensor.boiler_dhw_active 5 9 1 61 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.3wayvalve 3-way valve active boolean False binary_sensor.boiler_dhw_3-way_valve_active binary_sensor.boiler_dhw_3wayvalve 5 9 1 62 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.mixertemp mixer temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_mixer_temperature sensor.boiler_dhw_mixertemp 5 9 1/10 63 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.cylmiddletemp cylinder middle temperature (TS3) uint16 (>=0<=3199) C False sensor.boiler_dhw_cylinder_middle_temperature_(TS3) sensor.boiler_dhw_cylmiddletemp 5 9 1/10 64 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.starts starts uint24 (>=0<=16777214) False sensor.boiler_dhw_starts sensor.boiler_dhw_starts 5 9 1 65 2
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.workm active time time (>=0<=16777214) minutes False sensor.boiler_dhw_active_time sensor.boiler_dhw_workm 5 9 1 67 2
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 nompower nominal Power uint8 (>=0<=254) kW True number.boiler_nominal_Power number.boiler_nompower 5 0 1 270 1
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 nrgtotal total energy uint24 (>=0<=167772) kWh False sensor.boiler_total_energy sensor.boiler_nrgtotal 5 0 1/100 83 2
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 nrgheat energy heating uint24 (>=0<=10000000) kWh True number.boiler_energy_heating number.boiler_nrgheat 5 0 1/100 85 2
Condens 5000i, Greenstar 8000/GC9800IW, GB192i*2 boiler 195 dhw.nrg energy uint24 (>=0<=10000000) kWh True number.boiler_dhw_energy number.boiler_dhw_nrg 5 9 1/100 0 2
Logamax U122, Cerapur boiler 203 reset reset cmd [-|maintenance|error|history|message] True sensor.boiler_reset sensor.boiler_reset 5 0 1 0 1
Logamax U122, Cerapur boiler 203 heatingoff force heating off boolean True switch.boiler_force_heating_off switch.boiler_heatingoff 5 0 1 1 1
Logamax U122, Cerapur boiler 203 heatingactive heating active boolean False binary_sensor.boiler_heating_active binary_sensor.boiler_heatingactive 5 0 1 2 1
Logamax U122, Cerapur boiler 203 tapwateractive tapwater active boolean False binary_sensor.boiler_tapwater_active binary_sensor.boiler_tapwateractive 5 0 1 3 1
Logamax U122, Cerapur boiler 203 selflowtemp selected flow temperature uint8 (>=0<=90) C True number.boiler_selected_flow_temperature number.boiler_selflowtemp 5 0 1 4 1
Logamax U122, Cerapur boiler 203 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.boiler_heating_pump_modulation sensor.boiler_heatingpumpmod 5 0 1 5 1
Logamax U122, Cerapur boiler 203 outdoortemp outside temperature int16 (>=-3199<=3199) C False sensor.boiler_outside_temperature sensor.boiler_outdoortemp 5 0 1/10 6 1
Logamax U122, Cerapur boiler 203 curflowtemp current flow temperature uint16 (>=0<=3199) C False sensor.boiler_current_flow_temperature sensor.boiler_curflowtemp 5 0 1/10 7 1
Logamax U122, Cerapur boiler 203 rettemp return temperature uint16 (>=0<=3199) C False sensor.boiler_return_temperature sensor.boiler_rettemp 5 0 1/10 8 1
Logamax U122, Cerapur boiler 203 switchtemp mixing switch temperature uint16 (>=0<=3199) C False sensor.boiler_mixing_switch_temperature sensor.boiler_switchtemp 5 0 1/10 9 1
Logamax U122, Cerapur boiler 203 syspress system pressure uint8 (>=0<=25) bar False sensor.boiler_system_pressure sensor.boiler_syspress 5 0 1/10 10 1
Logamax U122, Cerapur boiler 203 boiltemp actual boiler temperature uint16 (>=0<=3199) C False sensor.boiler_actual_boiler_temperature sensor.boiler_boiltemp 5 0 1/10 11 1
Logamax U122, Cerapur boiler 203 headertemp low loss header uint16 (>=0<=3199) C False sensor.boiler_low_loss_header sensor.boiler_headertemp 5 0 1/10 12 1
Logamax U122, Cerapur boiler 203 exhausttemp exhaust temperature uint16 (>=0<=3199) C False sensor.boiler_exhaust_temperature sensor.boiler_exhausttemp 5 0 1/10 244 1
Logamax U122, Cerapur boiler 203 burngas gas boolean False binary_sensor.boiler_gas binary_sensor.boiler_burngas 5 0 1 245 1
Logamax U122, Cerapur boiler 203 burngas2 gas stage 2 boolean False binary_sensor.boiler_gas_stage_2 binary_sensor.boiler_burngas2 5 0 1 246 1
Logamax U122, Cerapur boiler 203 flamecurr flame current uint16 (>=0<=3199) µA False sensor.boiler_flame_current sensor.boiler_flamecurr 5 0 1/10 247 1
Logamax U122, Cerapur boiler 203 fanwork fan boolean False binary_sensor.boiler_fan binary_sensor.boiler_fanwork 5 0 1 248 1
Logamax U122, Cerapur boiler 203 ignwork ignition boolean False binary_sensor.boiler_ignition binary_sensor.boiler_ignwork 5 0 1 249 1
Logamax U122, Cerapur boiler 203 oilpreheat oil preheating boolean False binary_sensor.boiler_oil_preheating binary_sensor.boiler_oilpreheat 5 0 1 250 1
Logamax U122, Cerapur boiler 203 burnminpower burner min power uint8 (>=0<=100) % True number.boiler_burner_min_power number.boiler_burnminpower 5 0 1 251 1
Logamax U122, Cerapur boiler 203 burnmaxpower burner max power uint8 (>=0<=254) % True number.boiler_burner_max_power number.boiler_burnmaxpower 5 0 1 252 1
Logamax U122, Cerapur boiler 203 burnminperiod burner min period uint8 (>=0<=120) minutes True number.boiler_burner_min_period number.boiler_burnminperiod 5 0 1 253 1
Logamax U122, Cerapur boiler 203 absburnpow burner current power (absolute) uint8 (>=0<=100) % False sensor.boiler_burner_current_power_(absolute) sensor.boiler_absburnpow 5 0 1 254 1
Logamax U122, Cerapur boiler 203 heatblock heating block uint16 (>=0<=3199) C False sensor.boiler_heating_block sensor.boiler_heatblock 5 0 1/10 255 1
Logamax U122, Cerapur boiler 203 boilhyston hysteresis on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_on_temperature number.boiler_boilhyston 5 0 1 256 1
Logamax U122, Cerapur boiler 203 boilhystoff hysteresis off temperature int8 (>=0<=20) C True number.boiler_hysteresis_off_temperature number.boiler_boilhystoff 5 0 1 257 1
Logamax U122, Cerapur boiler 203 boil2hyston hysteresis stage 2 on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_stage_2_on_temperature number.boiler_boil2hyston 5 0 1 258 1
Logamax U122, Cerapur boiler 203 boil2hystoff hysteresis stage 2 off temperature int8 (>=0<=20) C True number.boiler_hysteresis_stage_2_off_temperature number.boiler_boil2hystoff 5 0 1 259 1
Logamax U122, Cerapur boiler 203 curveon heatingcurve on boolean True switch.boiler_heatingcurve_on switch.boiler_curveon 5 0 1 260 1
Logamax U122, Cerapur boiler 203 curvebase heatingcurve base uint8 (>=20<=90) C True number.boiler_heatingcurve_base number.boiler_curvebase 5 0 1 261 1
Logamax U122, Cerapur boiler 203 curveend heatingcurve end uint8 (>=20<=90) C True number.boiler_heatingcurve_end number.boiler_curveend 5 0 1 262 1
Logamax U122, Cerapur boiler 203 summertemp summer temperature uint8 (>=0<=45) C True number.boiler_summer_temperature number.boiler_summertemp 5 0 1 263 1
Logamax U122, Cerapur boiler 203 nofrostmode nofrost mode boolean True switch.boiler_nofrost_mode switch.boiler_nofrostmode 5 0 1 264 1
Logamax U122, Cerapur boiler 203 nofrosttemp nofrost temperature uint8 (>=0<=10) C True number.boiler_nofrost_temperature number.boiler_nofrosttemp 5 0 1 265 1
Logamax U122, Cerapur boiler 203 heatingactivated heating activated boolean True switch.boiler_heating_activated switch.boiler_heatingactivated 5 0 1 13 1
Logamax U122, Cerapur boiler 203 heatingtemp heating temperature uint8 (>=0<=90) C True number.boiler_heating_temperature number.boiler_heatingtemp 5 0 1 14 1
Logamax U122, Cerapur boiler 203 heatingpump heating pump boolean False binary_sensor.boiler_heating_pump binary_sensor.boiler_heatingpump 5 0 1 15 1
Logamax U122, Cerapur boiler 203 pumpmodmax boiler pump max power uint8 (>=0<=100) % True number.boiler_boiler_pump_max_power number.boiler_pumpmodmax 5 0 1 16 1
Logamax U122, Cerapur boiler 203 pumpmodmin boiler pump min power uint8 (>=0<=100) % True number.boiler_boiler_pump_min_power number.boiler_pumpmodmin 5 0 1 17 1
Logamax U122, Cerapur boiler 203 pumpmode boiler pump mode enum [proportional|deltaP-1|deltaP-2|deltaP-3|deltaP-4] True select.boiler_boiler_pump_mode select.boiler_pumpmode 5 0 1 18 1
Logamax U122, Cerapur boiler 203 pumpcharacter boiler pump characteristic enum [proportional|150mbar|200mbar|250mbar|300mbar|350mbar|400mbar] True select.boiler_boiler_pump_characteristic select.boiler_pumpcharacter 5 0 1 19 1
Logamax U122, Cerapur boiler 203 pumpdelay pump delay uint8 (>=0<=60) minutes True number.boiler_pump_delay number.boiler_pumpdelay 5 0 1 20 1
Logamax U122, Cerapur boiler 203 pumpontemp pump logic temperature uint8 (>=0<=60) C True number.boiler_pump_logic_temperature number.boiler_pumpontemp 5 0 1 21 1
Logamax U122, Cerapur boiler 203 selburnpow burner selected max power uint8 (>=0<=254) % True number.boiler_burner_selected_max_power number.boiler_selburnpow 5 0 1 22 1
Logamax U122, Cerapur boiler 203 curburnpow burner current power uint8 (>=0<=100) % False sensor.boiler_burner_current_power sensor.boiler_curburnpow 5 0 1 23 1
Logamax U122, Cerapur boiler 203 burnstarts burner starts uint24 (>=0<=16777214) False sensor.boiler_burner_starts sensor.boiler_burnstarts 5 0 1 24 2
Logamax U122, Cerapur boiler 203 burnworkmin total burner operating time time (>=0<=16777214) minutes False sensor.boiler_total_burner_operating_time sensor.boiler_burnworkmin 5 0 1 26 2
Logamax U122, Cerapur boiler 203 burn2workmin burner stage 2 operating time time (>=0<=16777214) minutes False sensor.boiler_burner_stage_2_operating_time sensor.boiler_burn2workmin 5 0 1 28 2
Logamax U122, Cerapur boiler 203 heatworkmin total heat operating time time (>=0<=16777214) minutes False sensor.boiler_total_heat_operating_time sensor.boiler_heatworkmin 5 0 1 30 2
Logamax U122, Cerapur boiler 203 heatstarts burner starts heating uint24 (>=0<=16777214) False sensor.boiler_burner_starts_heating sensor.boiler_heatstarts 5 0 1 32 2
Logamax U122, Cerapur boiler 203 ubauptime total UBA operating time time (>=0<=16777214) minutes False sensor.boiler_total_UBA_operating_time sensor.boiler_ubauptime 5 0 1 34 2
Logamax U122, Cerapur boiler 203 lastcode last error code string False sensor.boiler_last_error_code sensor.boiler_lastcode 5 0 1 36 28
Logamax U122, Cerapur boiler 203 servicecode service code string False sensor.boiler_service_code sensor.boiler_servicecode 5 0 1 64 2
Logamax U122, Cerapur boiler 203 servicecodenumber service code number uint16 (>=0<=31999) False sensor.boiler_service_code_number sensor.boiler_servicecodenumber 5 0 1 66 1
Logamax U122, Cerapur boiler 203 maintenancemessage maintenance message string False sensor.boiler_maintenance_message sensor.boiler_maintenancemessage 5 0 1 67 2
Logamax U122, Cerapur boiler 203 maintenance maintenance scheduled enum [off|time|date|manual] True select.boiler_maintenance_scheduled select.boiler_maintenance 5 0 1 69 1
Logamax U122, Cerapur boiler 203 maintenancetime time to next maintenance uint16 (>=0<=31999) hours True number.boiler_time_to_next_maintenance number.boiler_maintenancetime 5 0 1 70 1
Logamax U122, Cerapur boiler 203 maintenancedate next maintenance date string True sensor.boiler_next_maintenance_date sensor.boiler_maintenancedate 5 0 1 71 6
Logamax U122, Cerapur boiler 203 emergencyops emergency operation boolean True switch.boiler_emergency_operation switch.boiler_emergencyops 5 0 1 77 1
Logamax U122, Cerapur boiler 203 emergencytemp emergency temperature uint8 (>=15<=70) C True number.boiler_emergency_temperature number.boiler_emergencytemp 5 0 1 78 1
Logamax U122, Cerapur boiler 203 pc0flow Flow PC0 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC0 sensor.boiler_pc0flow 5 0 1 79 1
Logamax U122, Cerapur boiler 203 pc1flow Flow PC1 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC1 sensor.boiler_pc1flow 5 0 1 80 1
Logamax U122, Cerapur boiler 203 pc1on PC1 boolean False binary_sensor.boiler_PC1 binary_sensor.boiler_pc1on 5 0 1 81 1
Logamax U122, Cerapur boiler 203 pc1rate PC1 rate uint8 (>=0<=100) % False sensor.boiler_PC1_rate sensor.boiler_pc1rate 5 0 1 82 1
Logamax U122, Cerapur boiler 203 meterheat meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_meter_heating sensor.boiler_meterheat 5 0 1/10 95 2
Logamax U122, Cerapur boiler 203 dhw.meter meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_meter sensor.boiler_dhw_meter 5 9 1/10 2 2
Logamax U122, Cerapur boiler 203 gasmeterheat gas meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_gas_meter_heating sensor.boiler_gasmeterheat 5 0 1/10 266 2
Logamax U122, Cerapur boiler 203 dhw.gasmeter gas meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_gas_meter sensor.boiler_dhw_gasmeter 5 9 1/10 69 2
Logamax U122, Cerapur boiler 203 nrgheat2 energy heating 2 uint24 (>=0<=1677721) kWh False sensor.boiler_energy_heating_2 sensor.boiler_nrgheat2 5 0 1/10 268 2
Logamax U122, Cerapur boiler 203 dhw.nrg2 energy 2 uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_energy_2 sensor.boiler_dhw_nrg2 5 9 1/10 71 2
Logamax U122, Cerapur boiler 203 dhw.tapactivated turn on/off boolean True switch.boiler_dhw_turn_on/off switch.boiler_dhw_tapactivated 5 9 1 28 1
Logamax U122, Cerapur boiler 203 dhw.settemp set temperature uint8 (>=0<=254) C False sensor.boiler_dhw_set_temperature sensor.boiler_dhw_settemp 5 9 1 29 1
Logamax U122, Cerapur boiler 203 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_temperature number.boiler_dhw_seltemp 5 9 1 30 1
Logamax U122, Cerapur boiler 203 dhw.seltemplow selected lower temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_lower_temperature number.boiler_dhw_seltemplow 5 9 1 31 1
Logamax U122, Cerapur boiler 203 dhw.tempecoplus selected eco+ temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_eco+_temperature number.boiler_dhw_tempecoplus 5 9 1 32 1
Logamax U122, Cerapur boiler 203 dhw.seltempoff selected temperature for off uint8 (>=0<=254) C False sensor.boiler_dhw_selected_temperature_for_off sensor.boiler_dhw_seltempoff 5 9 1 33 1
Logamax U122, Cerapur boiler 203 dhw.seltempsingle single charge temperature uint8 (>=0<=254) C True number.boiler_dhw_single_charge_temperature number.boiler_dhw_seltempsingle 5 9 1 34 1
Logamax U122, Cerapur boiler 203 dhw.solartemp solar boiler temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_solar_boiler_temperature sensor.boiler_dhw_solartemp 5 9 1/10 35 1
Logamax U122, Cerapur boiler 203 dhw.type type enum [off|flow|buffered flow|buffer|layered buffer] False sensor.boiler_dhw_type sensor.boiler_dhw_type 5 9 1 36 1
Logamax U122, Cerapur boiler 203 dhw.comfort comfort enum [hot|eco|intelligent] True select.boiler_dhw_comfort select.boiler_dhw_comfort 5 9 1 37 1
Logamax U122, Cerapur boiler 203 dhw.comfort1 comfort mode enum [high comfort|eco] True select.boiler_dhw_comfort_mode select.boiler_dhw_comfort1 5 9 1 38 1
Logamax U122, Cerapur boiler 203 dhw.flowtempoffset flow temperature offset uint8 (>=0<=100) C True number.boiler_dhw_flow_temperature_offset number.boiler_dhw_flowtempoffset 5 9 1 39 1
Logamax U122, Cerapur boiler 203 dhw.chargeoptimization charge optimization boolean True switch.boiler_dhw_charge_optimization switch.boiler_dhw_chargeoptimization 5 9 1 40 1
Logamax U122, Cerapur boiler 203 dhw.maxpower max power uint8 (>=0<=254) % True number.boiler_dhw_max_power number.boiler_dhw_maxpower 5 9 1 41 1
Logamax U122, Cerapur boiler 203 dhw.maxtemp maximum temperature uint8 (>=0<=80) C True number.boiler_dhw_maximum_temperature number.boiler_dhw_maxtemp 5 9 1 42 1
Logamax U122, Cerapur boiler 203 dhw.circpump circulation pump available boolean True switch.boiler_dhw_circulation_pump_available switch.boiler_dhw_circpump 5 9 1 43 1
Logamax U122, Cerapur boiler 203 dhw.chargetype charging type enum [chargepump|3-way valve] False sensor.boiler_dhw_charging_type sensor.boiler_dhw_chargetype 5 9 1 44 1
Logamax U122, Cerapur boiler 203 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_on_temperature number.boiler_dhw_hyston 5 9 1 45 1
Logamax U122, Cerapur boiler 203 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_off_temperature number.boiler_dhw_hystoff 5 9 1 46 1
Logamax U122, Cerapur boiler 203 dhw.disinfectiontemp disinfection temperature uint8 (>=60<=80) C True number.boiler_dhw_disinfection_temperature number.boiler_dhw_disinfectiontemp 5 9 1 47 1
Logamax U122, Cerapur boiler 203 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.boiler_dhw_circulation_pump_mode select.boiler_dhw_circmode 5 9 1 48 1
Logamax U122, Cerapur boiler 203 dhw.circ circulation active boolean True switch.boiler_dhw_circulation_active switch.boiler_dhw_circ 5 9 1 49 1
Logamax U122, Cerapur boiler 203 dhw.curtemp current intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_intern_temperature sensor.boiler_dhw_curtemp 5 9 1/10 50 1
Logamax U122, Cerapur boiler 203 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_extern_temperature sensor.boiler_dhw_curtemp2 5 9 1/10 51 1
Logamax U122, Cerapur boiler 203 dhw.curflow current tap water flow uint8 (>=0<=25) l/min False sensor.boiler_dhw_current_tap_water_flow sensor.boiler_dhw_curflow 5 9 1/10 52 1
Logamax U122, Cerapur boiler 203 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_intern_temperature sensor.boiler_dhw_storagetemp1 5 9 1/10 53 1
Logamax U122, Cerapur boiler 203 dhw.storagetemp2 storage extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_extern_temperature sensor.boiler_dhw_storagetemp2 5 9 1/10 54 1
Logamax U122, Cerapur boiler 203 dhw.activated activated boolean True switch.boiler_dhw_activated switch.boiler_dhw_activated 5 9 1 55 1
Logamax U122, Cerapur boiler 203 dhw.onetime one time charging boolean True switch.boiler_dhw_one_time_charging switch.boiler_dhw_onetime 5 9 1 56 1
Logamax U122, Cerapur boiler 203 dhw.disinfecting disinfecting boolean True switch.boiler_dhw_disinfecting switch.boiler_dhw_disinfecting 5 9 1 57 1
Logamax U122, Cerapur boiler 203 dhw.charging charging boolean False binary_sensor.boiler_dhw_charging binary_sensor.boiler_dhw_charging 5 9 1 58 1
Logamax U122, Cerapur boiler 203 dhw.recharging recharging boolean False binary_sensor.boiler_dhw_recharging binary_sensor.boiler_dhw_recharging 5 9 1 59 1
Logamax U122, Cerapur boiler 203 dhw.tempok temperature ok boolean False binary_sensor.boiler_dhw_temperature_ok binary_sensor.boiler_dhw_tempok 5 9 1 60 1
Logamax U122, Cerapur boiler 203 dhw.active active boolean False binary_sensor.boiler_dhw_active binary_sensor.boiler_dhw_active 5 9 1 61 1
Logamax U122, Cerapur boiler 203 dhw.3wayvalve 3-way valve active boolean False binary_sensor.boiler_dhw_3-way_valve_active binary_sensor.boiler_dhw_3wayvalve 5 9 1 62 1
Logamax U122, Cerapur boiler 203 dhw.mixertemp mixer temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_mixer_temperature sensor.boiler_dhw_mixertemp 5 9 1/10 63 1
Logamax U122, Cerapur boiler 203 dhw.cylmiddletemp cylinder middle temperature (TS3) uint16 (>=0<=3199) C False sensor.boiler_dhw_cylinder_middle_temperature_(TS3) sensor.boiler_dhw_cylmiddletemp 5 9 1/10 64 1
Logamax U122, Cerapur boiler 203 dhw.starts starts uint24 (>=0<=16777214) False sensor.boiler_dhw_starts sensor.boiler_dhw_starts 5 9 1 65 2
Logamax U122, Cerapur boiler 203 dhw.workm active time time (>=0<=16777214) minutes False sensor.boiler_dhw_active_time sensor.boiler_dhw_workm 5 9 1 67 2
Logamax U122, Cerapur boiler 203 nompower nominal Power uint8 (>=0<=254) kW True number.boiler_nominal_Power number.boiler_nompower 5 0 1 270 1
Logamax U122, Cerapur boiler 203 nrgtotal total energy uint24 (>=0<=167772) kWh False sensor.boiler_total_energy sensor.boiler_nrgtotal 5 0 1/100 83 2
Logamax U122, Cerapur boiler 203 nrgheat energy heating uint24 (>=0<=10000000) kWh True number.boiler_energy_heating number.boiler_nrgheat 5 0 1/100 85 2
Logamax U122, Cerapur boiler 203 dhw.nrg energy uint24 (>=0<=10000000) kWh True number.boiler_dhw_energy number.boiler_dhw_nrg 5 9 1/100 0 2
Ecomline Excellent boiler 206 reset reset cmd [-|maintenance|error|history|message] True sensor.boiler_reset sensor.boiler_reset 5 0 1 0 1
Ecomline Excellent boiler 206 heatingoff force heating off boolean True switch.boiler_force_heating_off switch.boiler_heatingoff 5 0 1 1 1
Ecomline Excellent boiler 206 heatingactive heating active boolean False binary_sensor.boiler_heating_active binary_sensor.boiler_heatingactive 5 0 1 2 1
Ecomline Excellent boiler 206 tapwateractive tapwater active boolean False binary_sensor.boiler_tapwater_active binary_sensor.boiler_tapwateractive 5 0 1 3 1
Ecomline Excellent boiler 206 selflowtemp selected flow temperature uint8 (>=0<=90) C True number.boiler_selected_flow_temperature number.boiler_selflowtemp 5 0 1 4 1
Ecomline Excellent boiler 206 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.boiler_heating_pump_modulation sensor.boiler_heatingpumpmod 5 0 1 5 1
Ecomline Excellent boiler 206 outdoortemp outside temperature int16 (>=-3199<=3199) C False sensor.boiler_outside_temperature sensor.boiler_outdoortemp 5 0 1/10 6 1
Ecomline Excellent boiler 206 curflowtemp current flow temperature uint16 (>=0<=3199) C False sensor.boiler_current_flow_temperature sensor.boiler_curflowtemp 5 0 1/10 7 1
Ecomline Excellent boiler 206 rettemp return temperature uint16 (>=0<=3199) C False sensor.boiler_return_temperature sensor.boiler_rettemp 5 0 1/10 8 1
Ecomline Excellent boiler 206 switchtemp mixing switch temperature uint16 (>=0<=3199) C False sensor.boiler_mixing_switch_temperature sensor.boiler_switchtemp 5 0 1/10 9 1
Ecomline Excellent boiler 206 syspress system pressure uint8 (>=0<=25) bar False sensor.boiler_system_pressure sensor.boiler_syspress 5 0 1/10 10 1
Ecomline Excellent boiler 206 boiltemp actual boiler temperature uint16 (>=0<=3199) C False sensor.boiler_actual_boiler_temperature sensor.boiler_boiltemp 5 0 1/10 11 1
Ecomline Excellent boiler 206 headertemp low loss header uint16 (>=0<=3199) C False sensor.boiler_low_loss_header sensor.boiler_headertemp 5 0 1/10 12 1
Ecomline Excellent boiler 206 exhausttemp exhaust temperature uint16 (>=0<=3199) C False sensor.boiler_exhaust_temperature sensor.boiler_exhausttemp 5 0 1/10 244 1
Ecomline Excellent boiler 206 burngas gas boolean False binary_sensor.boiler_gas binary_sensor.boiler_burngas 5 0 1 245 1
Ecomline Excellent boiler 206 burngas2 gas stage 2 boolean False binary_sensor.boiler_gas_stage_2 binary_sensor.boiler_burngas2 5 0 1 246 1
Ecomline Excellent boiler 206 flamecurr flame current uint16 (>=0<=3199) µA False sensor.boiler_flame_current sensor.boiler_flamecurr 5 0 1/10 247 1
Ecomline Excellent boiler 206 fanwork fan boolean False binary_sensor.boiler_fan binary_sensor.boiler_fanwork 5 0 1 248 1
Ecomline Excellent boiler 206 ignwork ignition boolean False binary_sensor.boiler_ignition binary_sensor.boiler_ignwork 5 0 1 249 1
Ecomline Excellent boiler 206 oilpreheat oil preheating boolean False binary_sensor.boiler_oil_preheating binary_sensor.boiler_oilpreheat 5 0 1 250 1
Ecomline Excellent boiler 206 burnminpower burner min power uint8 (>=0<=100) % True number.boiler_burner_min_power number.boiler_burnminpower 5 0 1 251 1
Ecomline Excellent boiler 206 burnmaxpower burner max power uint8 (>=0<=254) % True number.boiler_burner_max_power number.boiler_burnmaxpower 5 0 1 252 1
Ecomline Excellent boiler 206 burnminperiod burner min period uint8 (>=0<=120) minutes True number.boiler_burner_min_period number.boiler_burnminperiod 5 0 1 253 1
Ecomline Excellent boiler 206 absburnpow burner current power (absolute) uint8 (>=0<=100) % False sensor.boiler_burner_current_power_(absolute) sensor.boiler_absburnpow 5 0 1 254 1
Ecomline Excellent boiler 206 heatblock heating block uint16 (>=0<=3199) C False sensor.boiler_heating_block sensor.boiler_heatblock 5 0 1/10 255 1
Ecomline Excellent boiler 206 boilhyston hysteresis on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_on_temperature number.boiler_boilhyston 5 0 1 256 1
Ecomline Excellent boiler 206 boilhystoff hysteresis off temperature int8 (>=0<=20) C True number.boiler_hysteresis_off_temperature number.boiler_boilhystoff 5 0 1 257 1
Ecomline Excellent boiler 206 boil2hyston hysteresis stage 2 on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_stage_2_on_temperature number.boiler_boil2hyston 5 0 1 258 1
Ecomline Excellent boiler 206 boil2hystoff hysteresis stage 2 off temperature int8 (>=0<=20) C True number.boiler_hysteresis_stage_2_off_temperature number.boiler_boil2hystoff 5 0 1 259 1
Ecomline Excellent boiler 206 curveon heatingcurve on boolean True switch.boiler_heatingcurve_on switch.boiler_curveon 5 0 1 260 1
Ecomline Excellent boiler 206 curvebase heatingcurve base uint8 (>=20<=90) C True number.boiler_heatingcurve_base number.boiler_curvebase 5 0 1 261 1
Ecomline Excellent boiler 206 curveend heatingcurve end uint8 (>=20<=90) C True number.boiler_heatingcurve_end number.boiler_curveend 5 0 1 262 1
Ecomline Excellent boiler 206 summertemp summer temperature uint8 (>=0<=45) C True number.boiler_summer_temperature number.boiler_summertemp 5 0 1 263 1
Ecomline Excellent boiler 206 nofrostmode nofrost mode boolean True switch.boiler_nofrost_mode switch.boiler_nofrostmode 5 0 1 264 1
Ecomline Excellent boiler 206 nofrosttemp nofrost temperature uint8 (>=0<=10) C True number.boiler_nofrost_temperature number.boiler_nofrosttemp 5 0 1 265 1
Ecomline Excellent boiler 206 heatingactivated heating activated boolean True switch.boiler_heating_activated switch.boiler_heatingactivated 5 0 1 13 1
Ecomline Excellent boiler 206 heatingtemp heating temperature uint8 (>=0<=90) C True number.boiler_heating_temperature number.boiler_heatingtemp 5 0 1 14 1
Ecomline Excellent boiler 206 heatingpump heating pump boolean False binary_sensor.boiler_heating_pump binary_sensor.boiler_heatingpump 5 0 1 15 1
Ecomline Excellent boiler 206 pumpmodmax boiler pump max power uint8 (>=0<=100) % True number.boiler_boiler_pump_max_power number.boiler_pumpmodmax 5 0 1 16 1
Ecomline Excellent boiler 206 pumpmodmin boiler pump min power uint8 (>=0<=100) % True number.boiler_boiler_pump_min_power number.boiler_pumpmodmin 5 0 1 17 1
Ecomline Excellent boiler 206 pumpmode boiler pump mode enum [proportional|deltaP-1|deltaP-2|deltaP-3|deltaP-4] True select.boiler_boiler_pump_mode select.boiler_pumpmode 5 0 1 18 1
Ecomline Excellent boiler 206 pumpcharacter boiler pump characteristic enum [proportional|150mbar|200mbar|250mbar|300mbar|350mbar|400mbar] True select.boiler_boiler_pump_characteristic select.boiler_pumpcharacter 5 0 1 19 1
Ecomline Excellent boiler 206 pumpdelay pump delay uint8 (>=0<=60) minutes True number.boiler_pump_delay number.boiler_pumpdelay 5 0 1 20 1
Ecomline Excellent boiler 206 pumpontemp pump logic temperature uint8 (>=0<=60) C True number.boiler_pump_logic_temperature number.boiler_pumpontemp 5 0 1 21 1
Ecomline Excellent boiler 206 selburnpow burner selected max power uint8 (>=0<=254) % True number.boiler_burner_selected_max_power number.boiler_selburnpow 5 0 1 22 1
Ecomline Excellent boiler 206 curburnpow burner current power uint8 (>=0<=100) % False sensor.boiler_burner_current_power sensor.boiler_curburnpow 5 0 1 23 1
Ecomline Excellent boiler 206 burnstarts burner starts uint24 (>=0<=16777214) False sensor.boiler_burner_starts sensor.boiler_burnstarts 5 0 1 24 2
Ecomline Excellent boiler 206 burnworkmin total burner operating time time (>=0<=16777214) minutes False sensor.boiler_total_burner_operating_time sensor.boiler_burnworkmin 5 0 1 26 2
Ecomline Excellent boiler 206 burn2workmin burner stage 2 operating time time (>=0<=16777214) minutes False sensor.boiler_burner_stage_2_operating_time sensor.boiler_burn2workmin 5 0 1 28 2
Ecomline Excellent boiler 206 heatworkmin total heat operating time time (>=0<=16777214) minutes False sensor.boiler_total_heat_operating_time sensor.boiler_heatworkmin 5 0 1 30 2
Ecomline Excellent boiler 206 heatstarts burner starts heating uint24 (>=0<=16777214) False sensor.boiler_burner_starts_heating sensor.boiler_heatstarts 5 0 1 32 2
Ecomline Excellent boiler 206 ubauptime total UBA operating time time (>=0<=16777214) minutes False sensor.boiler_total_UBA_operating_time sensor.boiler_ubauptime 5 0 1 34 2
Ecomline Excellent boiler 206 lastcode last error code string False sensor.boiler_last_error_code sensor.boiler_lastcode 5 0 1 36 28
Ecomline Excellent boiler 206 servicecode service code string False sensor.boiler_service_code sensor.boiler_servicecode 5 0 1 64 2
Ecomline Excellent boiler 206 servicecodenumber service code number uint16 (>=0<=31999) False sensor.boiler_service_code_number sensor.boiler_servicecodenumber 5 0 1 66 1
Ecomline Excellent boiler 206 maintenancemessage maintenance message string False sensor.boiler_maintenance_message sensor.boiler_maintenancemessage 5 0 1 67 2
Ecomline Excellent boiler 206 maintenance maintenance scheduled enum [off|time|date|manual] True select.boiler_maintenance_scheduled select.boiler_maintenance 5 0 1 69 1
Ecomline Excellent boiler 206 maintenancetime time to next maintenance uint16 (>=0<=31999) hours True number.boiler_time_to_next_maintenance number.boiler_maintenancetime 5 0 1 70 1
Ecomline Excellent boiler 206 maintenancedate next maintenance date string True sensor.boiler_next_maintenance_date sensor.boiler_maintenancedate 5 0 1 71 6
Ecomline Excellent boiler 206 emergencyops emergency operation boolean True switch.boiler_emergency_operation switch.boiler_emergencyops 5 0 1 77 1
Ecomline Excellent boiler 206 emergencytemp emergency temperature uint8 (>=15<=70) C True number.boiler_emergency_temperature number.boiler_emergencytemp 5 0 1 78 1
Ecomline Excellent boiler 206 pc0flow Flow PC0 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC0 sensor.boiler_pc0flow 5 0 1 79 1
Ecomline Excellent boiler 206 pc1flow Flow PC1 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC1 sensor.boiler_pc1flow 5 0 1 80 1
Ecomline Excellent boiler 206 pc1on PC1 boolean False binary_sensor.boiler_PC1 binary_sensor.boiler_pc1on 5 0 1 81 1
Ecomline Excellent boiler 206 pc1rate PC1 rate uint8 (>=0<=100) % False sensor.boiler_PC1_rate sensor.boiler_pc1rate 5 0 1 82 1
Ecomline Excellent boiler 206 meterheat meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_meter_heating sensor.boiler_meterheat 5 0 1/10 95 2
Ecomline Excellent boiler 206 dhw.meter meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_meter sensor.boiler_dhw_meter 5 9 1/10 2 2
Ecomline Excellent boiler 206 gasmeterheat gas meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_gas_meter_heating sensor.boiler_gasmeterheat 5 0 1/10 266 2
Ecomline Excellent boiler 206 dhw.gasmeter gas meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_gas_meter sensor.boiler_dhw_gasmeter 5 9 1/10 69 2
Ecomline Excellent boiler 206 nrgheat2 energy heating 2 uint24 (>=0<=1677721) kWh False sensor.boiler_energy_heating_2 sensor.boiler_nrgheat2 5 0 1/10 268 2
Ecomline Excellent boiler 206 dhw.nrg2 energy 2 uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_energy_2 sensor.boiler_dhw_nrg2 5 9 1/10 71 2
Ecomline Excellent boiler 206 dhw.tapactivated turn on/off boolean True switch.boiler_dhw_turn_on/off switch.boiler_dhw_tapactivated 5 9 1 28 1
Ecomline Excellent boiler 206 dhw.settemp set temperature uint8 (>=0<=254) C False sensor.boiler_dhw_set_temperature sensor.boiler_dhw_settemp 5 9 1 29 1
Ecomline Excellent boiler 206 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_temperature number.boiler_dhw_seltemp 5 9 1 30 1
Ecomline Excellent boiler 206 dhw.seltemplow selected lower temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_lower_temperature number.boiler_dhw_seltemplow 5 9 1 31 1
Ecomline Excellent boiler 206 dhw.tempecoplus selected eco+ temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_eco+_temperature number.boiler_dhw_tempecoplus 5 9 1 32 1
Ecomline Excellent boiler 206 dhw.seltempoff selected temperature for off uint8 (>=0<=254) C False sensor.boiler_dhw_selected_temperature_for_off sensor.boiler_dhw_seltempoff 5 9 1 33 1
Ecomline Excellent boiler 206 dhw.seltempsingle single charge temperature uint8 (>=0<=254) C True number.boiler_dhw_single_charge_temperature number.boiler_dhw_seltempsingle 5 9 1 34 1
Ecomline Excellent boiler 206 dhw.solartemp solar boiler temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_solar_boiler_temperature sensor.boiler_dhw_solartemp 5 9 1/10 35 1
Ecomline Excellent boiler 206 dhw.type type enum [off|flow|buffered flow|buffer|layered buffer] False sensor.boiler_dhw_type sensor.boiler_dhw_type 5 9 1 36 1
Ecomline Excellent boiler 206 dhw.comfort comfort enum [hot|eco|intelligent] True select.boiler_dhw_comfort select.boiler_dhw_comfort 5 9 1 37 1
Ecomline Excellent boiler 206 dhw.comfort1 comfort mode enum [high comfort|eco] True select.boiler_dhw_comfort_mode select.boiler_dhw_comfort1 5 9 1 38 1
Ecomline Excellent boiler 206 dhw.flowtempoffset flow temperature offset uint8 (>=0<=100) C True number.boiler_dhw_flow_temperature_offset number.boiler_dhw_flowtempoffset 5 9 1 39 1
Ecomline Excellent boiler 206 dhw.chargeoptimization charge optimization boolean True switch.boiler_dhw_charge_optimization switch.boiler_dhw_chargeoptimization 5 9 1 40 1
Ecomline Excellent boiler 206 dhw.maxpower max power uint8 (>=0<=254) % True number.boiler_dhw_max_power number.boiler_dhw_maxpower 5 9 1 41 1
Ecomline Excellent boiler 206 dhw.maxtemp maximum temperature uint8 (>=0<=80) C True number.boiler_dhw_maximum_temperature number.boiler_dhw_maxtemp 5 9 1 42 1
Ecomline Excellent boiler 206 dhw.circpump circulation pump available boolean True switch.boiler_dhw_circulation_pump_available switch.boiler_dhw_circpump 5 9 1 43 1
Ecomline Excellent boiler 206 dhw.chargetype charging type enum [chargepump|3-way valve] False sensor.boiler_dhw_charging_type sensor.boiler_dhw_chargetype 5 9 1 44 1
Ecomline Excellent boiler 206 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_on_temperature number.boiler_dhw_hyston 5 9 1 45 1
Ecomline Excellent boiler 206 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_off_temperature number.boiler_dhw_hystoff 5 9 1 46 1
Ecomline Excellent boiler 206 dhw.disinfectiontemp disinfection temperature uint8 (>=60<=80) C True number.boiler_dhw_disinfection_temperature number.boiler_dhw_disinfectiontemp 5 9 1 47 1
Ecomline Excellent boiler 206 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.boiler_dhw_circulation_pump_mode select.boiler_dhw_circmode 5 9 1 48 1
Ecomline Excellent boiler 206 dhw.circ circulation active boolean True switch.boiler_dhw_circulation_active switch.boiler_dhw_circ 5 9 1 49 1
Ecomline Excellent boiler 206 dhw.curtemp current intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_intern_temperature sensor.boiler_dhw_curtemp 5 9 1/10 50 1
Ecomline Excellent boiler 206 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_extern_temperature sensor.boiler_dhw_curtemp2 5 9 1/10 51 1
Ecomline Excellent boiler 206 dhw.curflow current tap water flow uint8 (>=0<=25) l/min False sensor.boiler_dhw_current_tap_water_flow sensor.boiler_dhw_curflow 5 9 1/10 52 1
Ecomline Excellent boiler 206 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_intern_temperature sensor.boiler_dhw_storagetemp1 5 9 1/10 53 1
Ecomline Excellent boiler 206 dhw.storagetemp2 storage extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_extern_temperature sensor.boiler_dhw_storagetemp2 5 9 1/10 54 1
Ecomline Excellent boiler 206 dhw.activated activated boolean True switch.boiler_dhw_activated switch.boiler_dhw_activated 5 9 1 55 1
Ecomline Excellent boiler 206 dhw.onetime one time charging boolean True switch.boiler_dhw_one_time_charging switch.boiler_dhw_onetime 5 9 1 56 1
Ecomline Excellent boiler 206 dhw.disinfecting disinfecting boolean True switch.boiler_dhw_disinfecting switch.boiler_dhw_disinfecting 5 9 1 57 1
Ecomline Excellent boiler 206 dhw.charging charging boolean False binary_sensor.boiler_dhw_charging binary_sensor.boiler_dhw_charging 5 9 1 58 1
Ecomline Excellent boiler 206 dhw.recharging recharging boolean False binary_sensor.boiler_dhw_recharging binary_sensor.boiler_dhw_recharging 5 9 1 59 1
Ecomline Excellent boiler 206 dhw.tempok temperature ok boolean False binary_sensor.boiler_dhw_temperature_ok binary_sensor.boiler_dhw_tempok 5 9 1 60 1
Ecomline Excellent boiler 206 dhw.active active boolean False binary_sensor.boiler_dhw_active binary_sensor.boiler_dhw_active 5 9 1 61 1
Ecomline Excellent boiler 206 dhw.3wayvalve 3-way valve active boolean False binary_sensor.boiler_dhw_3-way_valve_active binary_sensor.boiler_dhw_3wayvalve 5 9 1 62 1
Ecomline Excellent boiler 206 dhw.mixertemp mixer temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_mixer_temperature sensor.boiler_dhw_mixertemp 5 9 1/10 63 1
Ecomline Excellent boiler 206 dhw.cylmiddletemp cylinder middle temperature (TS3) uint16 (>=0<=3199) C False sensor.boiler_dhw_cylinder_middle_temperature_(TS3) sensor.boiler_dhw_cylmiddletemp 5 9 1/10 64 1
Ecomline Excellent boiler 206 dhw.starts starts uint24 (>=0<=16777214) False sensor.boiler_dhw_starts sensor.boiler_dhw_starts 5 9 1 65 2
Ecomline Excellent boiler 206 dhw.workm active time time (>=0<=16777214) minutes False sensor.boiler_dhw_active_time sensor.boiler_dhw_workm 5 9 1 67 2
Ecomline Excellent boiler 206 nompower nominal Power uint8 (>=0<=254) kW True number.boiler_nominal_Power number.boiler_nompower 5 0 1 270 1
Ecomline Excellent boiler 206 nrgtotal total energy uint24 (>=0<=167772) kWh False sensor.boiler_total_energy sensor.boiler_nrgtotal 5 0 1/100 83 2
Ecomline Excellent boiler 206 nrgheat energy heating uint24 (>=0<=10000000) kWh True number.boiler_energy_heating number.boiler_nrgheat 5 0 1/100 85 2
Ecomline Excellent boiler 206 dhw.nrg energy uint24 (>=0<=10000000) kWh True number.boiler_dhw_energy number.boiler_dhw_nrg 5 9 1/100 0 2
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 reset reset cmd [-|maintenance|error|history|message] True sensor.boiler_reset sensor.boiler_reset 5 0 1 0 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 heatingoff force heating off boolean True switch.boiler_force_heating_off switch.boiler_heatingoff 5 0 1 1 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 heatingactive heating active boolean False binary_sensor.boiler_heating_active binary_sensor.boiler_heatingactive 5 0 1 2 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 tapwateractive tapwater active boolean False binary_sensor.boiler_tapwater_active binary_sensor.boiler_tapwateractive 5 0 1 3 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 selflowtemp selected flow temperature uint8 (>=0<=90) C True number.boiler_selected_flow_temperature number.boiler_selflowtemp 5 0 1 4 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.boiler_heating_pump_modulation sensor.boiler_heatingpumpmod 5 0 1 5 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 outdoortemp outside temperature int16 (>=-3199<=3199) C False sensor.boiler_outside_temperature sensor.boiler_outdoortemp 5 0 1/10 6 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 curflowtemp current flow temperature uint16 (>=0<=3199) C False sensor.boiler_current_flow_temperature sensor.boiler_curflowtemp 5 0 1/10 7 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 rettemp return temperature uint16 (>=0<=3199) C False sensor.boiler_return_temperature sensor.boiler_rettemp 5 0 1/10 8 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 switchtemp mixing switch temperature uint16 (>=0<=3199) C False sensor.boiler_mixing_switch_temperature sensor.boiler_switchtemp 5 0 1/10 9 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 syspress system pressure uint8 (>=0<=25) bar False sensor.boiler_system_pressure sensor.boiler_syspress 5 0 1/10 10 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 boiltemp actual boiler temperature uint16 (>=0<=3199) C False sensor.boiler_actual_boiler_temperature sensor.boiler_boiltemp 5 0 1/10 11 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 headertemp low loss header uint16 (>=0<=3199) C False sensor.boiler_low_loss_header sensor.boiler_headertemp 5 0 1/10 12 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 exhausttemp exhaust temperature uint16 (>=0<=3199) C False sensor.boiler_exhaust_temperature sensor.boiler_exhausttemp 5 0 1/10 244 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 burngas gas boolean False binary_sensor.boiler_gas binary_sensor.boiler_burngas 5 0 1 245 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 burngas2 gas stage 2 boolean False binary_sensor.boiler_gas_stage_2 binary_sensor.boiler_burngas2 5 0 1 246 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 flamecurr flame current uint16 (>=0<=3199) µA False sensor.boiler_flame_current sensor.boiler_flamecurr 5 0 1/10 247 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 fanwork fan boolean False binary_sensor.boiler_fan binary_sensor.boiler_fanwork 5 0 1 248 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 ignwork ignition boolean False binary_sensor.boiler_ignition binary_sensor.boiler_ignwork 5 0 1 249 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 oilpreheat oil preheating boolean False binary_sensor.boiler_oil_preheating binary_sensor.boiler_oilpreheat 5 0 1 250 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 burnminpower burner min power uint8 (>=0<=100) % True number.boiler_burner_min_power number.boiler_burnminpower 5 0 1 251 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 burnmaxpower burner max power uint8 (>=0<=254) % True number.boiler_burner_max_power number.boiler_burnmaxpower 5 0 1 252 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 burnminperiod burner min period uint8 (>=0<=120) minutes True number.boiler_burner_min_period number.boiler_burnminperiod 5 0 1 253 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 absburnpow burner current power (absolute) uint8 (>=0<=100) % False sensor.boiler_burner_current_power_(absolute) sensor.boiler_absburnpow 5 0 1 254 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 heatblock heating block uint16 (>=0<=3199) C False sensor.boiler_heating_block sensor.boiler_heatblock 5 0 1/10 255 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 boilhyston hysteresis on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_on_temperature number.boiler_boilhyston 5 0 1 256 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 boilhystoff hysteresis off temperature int8 (>=0<=20) C True number.boiler_hysteresis_off_temperature number.boiler_boilhystoff 5 0 1 257 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 boil2hyston hysteresis stage 2 on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_stage_2_on_temperature number.boiler_boil2hyston 5 0 1 258 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 boil2hystoff hysteresis stage 2 off temperature int8 (>=0<=20) C True number.boiler_hysteresis_stage_2_off_temperature number.boiler_boil2hystoff 5 0 1 259 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 curveon heatingcurve on boolean True switch.boiler_heatingcurve_on switch.boiler_curveon 5 0 1 260 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 curvebase heatingcurve base uint8 (>=20<=90) C True number.boiler_heatingcurve_base number.boiler_curvebase 5 0 1 261 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 curveend heatingcurve end uint8 (>=20<=90) C True number.boiler_heatingcurve_end number.boiler_curveend 5 0 1 262 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 summertemp summer temperature uint8 (>=0<=45) C True number.boiler_summer_temperature number.boiler_summertemp 5 0 1 263 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 nofrostmode nofrost mode boolean True switch.boiler_nofrost_mode switch.boiler_nofrostmode 5 0 1 264 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 nofrosttemp nofrost temperature uint8 (>=0<=10) C True number.boiler_nofrost_temperature number.boiler_nofrosttemp 5 0 1 265 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 heatingactivated heating activated boolean True switch.boiler_heating_activated switch.boiler_heatingactivated 5 0 1 13 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 heatingtemp heating temperature uint8 (>=0<=90) C True number.boiler_heating_temperature number.boiler_heatingtemp 5 0 1 14 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 heatingpump heating pump boolean False binary_sensor.boiler_heating_pump binary_sensor.boiler_heatingpump 5 0 1 15 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 pumpmodmax boiler pump max power uint8 (>=0<=100) % True number.boiler_boiler_pump_max_power number.boiler_pumpmodmax 5 0 1 16 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 pumpmodmin boiler pump min power uint8 (>=0<=100) % True number.boiler_boiler_pump_min_power number.boiler_pumpmodmin 5 0 1 17 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 pumpmode boiler pump mode enum [proportional|deltaP-1|deltaP-2|deltaP-3|deltaP-4] True select.boiler_boiler_pump_mode select.boiler_pumpmode 5 0 1 18 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 pumpcharacter boiler pump characteristic enum [proportional|150mbar|200mbar|250mbar|300mbar|350mbar|400mbar] True select.boiler_boiler_pump_characteristic select.boiler_pumpcharacter 5 0 1 19 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 pumpdelay pump delay uint8 (>=0<=60) minutes True number.boiler_pump_delay number.boiler_pumpdelay 5 0 1 20 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 pumpontemp pump logic temperature uint8 (>=0<=60) C True number.boiler_pump_logic_temperature number.boiler_pumpontemp 5 0 1 21 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 selburnpow burner selected max power uint8 (>=0<=254) % True number.boiler_burner_selected_max_power number.boiler_selburnpow 5 0 1 22 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 curburnpow burner current power uint8 (>=0<=100) % False sensor.boiler_burner_current_power sensor.boiler_curburnpow 5 0 1 23 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 burnstarts burner starts uint24 (>=0<=16777214) False sensor.boiler_burner_starts sensor.boiler_burnstarts 5 0 1 24 2
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 burnworkmin total burner operating time time (>=0<=16777214) minutes False sensor.boiler_total_burner_operating_time sensor.boiler_burnworkmin 5 0 1 26 2
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 burn2workmin burner stage 2 operating time time (>=0<=16777214) minutes False sensor.boiler_burner_stage_2_operating_time sensor.boiler_burn2workmin 5 0 1 28 2
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 heatworkmin total heat operating time time (>=0<=16777214) minutes False sensor.boiler_total_heat_operating_time sensor.boiler_heatworkmin 5 0 1 30 2
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 heatstarts burner starts heating uint24 (>=0<=16777214) False sensor.boiler_burner_starts_heating sensor.boiler_heatstarts 5 0 1 32 2
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 ubauptime total UBA operating time time (>=0<=16777214) minutes False sensor.boiler_total_UBA_operating_time sensor.boiler_ubauptime 5 0 1 34 2
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 lastcode last error code string False sensor.boiler_last_error_code sensor.boiler_lastcode 5 0 1 36 28
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 servicecode service code string False sensor.boiler_service_code sensor.boiler_servicecode 5 0 1 64 2
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 servicecodenumber service code number uint16 (>=0<=31999) False sensor.boiler_service_code_number sensor.boiler_servicecodenumber 5 0 1 66 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 maintenancemessage maintenance message string False sensor.boiler_maintenance_message sensor.boiler_maintenancemessage 5 0 1 67 2
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 maintenance maintenance scheduled enum [off|time|date|manual] True select.boiler_maintenance_scheduled select.boiler_maintenance 5 0 1 69 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 maintenancetime time to next maintenance uint16 (>=0<=31999) hours True number.boiler_time_to_next_maintenance number.boiler_maintenancetime 5 0 1 70 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 maintenancedate next maintenance date string True sensor.boiler_next_maintenance_date sensor.boiler_maintenancedate 5 0 1 71 6
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 emergencyops emergency operation boolean True switch.boiler_emergency_operation switch.boiler_emergencyops 5 0 1 77 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 emergencytemp emergency temperature uint8 (>=15<=70) C True number.boiler_emergency_temperature number.boiler_emergencytemp 5 0 1 78 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 pc0flow Flow PC0 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC0 sensor.boiler_pc0flow 5 0 1 79 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 pc1flow Flow PC1 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC1 sensor.boiler_pc1flow 5 0 1 80 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 pc1on PC1 boolean False binary_sensor.boiler_PC1 binary_sensor.boiler_pc1on 5 0 1 81 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 pc1rate PC1 rate uint8 (>=0<=100) % False sensor.boiler_PC1_rate sensor.boiler_pc1rate 5 0 1 82 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 meterheat meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_meter_heating sensor.boiler_meterheat 5 0 1/10 95 2
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.meter meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_meter sensor.boiler_dhw_meter 5 9 1/10 2 2
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 gasmeterheat gas meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_gas_meter_heating sensor.boiler_gasmeterheat 5 0 1/10 266 2
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.gasmeter gas meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_gas_meter sensor.boiler_dhw_gasmeter 5 9 1/10 69 2
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 nrgheat2 energy heating 2 uint24 (>=0<=1677721) kWh False sensor.boiler_energy_heating_2 sensor.boiler_nrgheat2 5 0 1/10 268 2
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.nrg2 energy 2 uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_energy_2 sensor.boiler_dhw_nrg2 5 9 1/10 71 2
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.tapactivated turn on/off boolean True switch.boiler_dhw_turn_on/off switch.boiler_dhw_tapactivated 5 9 1 28 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.settemp set temperature uint8 (>=0<=254) C False sensor.boiler_dhw_set_temperature sensor.boiler_dhw_settemp 5 9 1 29 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_temperature number.boiler_dhw_seltemp 5 9 1 30 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.seltemplow selected lower temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_lower_temperature number.boiler_dhw_seltemplow 5 9 1 31 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.tempecoplus selected eco+ temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_eco+_temperature number.boiler_dhw_tempecoplus 5 9 1 32 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.seltempoff selected temperature for off uint8 (>=0<=254) C False sensor.boiler_dhw_selected_temperature_for_off sensor.boiler_dhw_seltempoff 5 9 1 33 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.seltempsingle single charge temperature uint8 (>=0<=254) C True number.boiler_dhw_single_charge_temperature number.boiler_dhw_seltempsingle 5 9 1 34 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.solartemp solar boiler temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_solar_boiler_temperature sensor.boiler_dhw_solartemp 5 9 1/10 35 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.type type enum [off|flow|buffered flow|buffer|layered buffer] False sensor.boiler_dhw_type sensor.boiler_dhw_type 5 9 1 36 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.comfort comfort enum [hot|eco|intelligent] True select.boiler_dhw_comfort select.boiler_dhw_comfort 5 9 1 37 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.comfort1 comfort mode enum [high comfort|eco] True select.boiler_dhw_comfort_mode select.boiler_dhw_comfort1 5 9 1 38 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.flowtempoffset flow temperature offset uint8 (>=0<=100) C True number.boiler_dhw_flow_temperature_offset number.boiler_dhw_flowtempoffset 5 9 1 39 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.chargeoptimization charge optimization boolean True switch.boiler_dhw_charge_optimization switch.boiler_dhw_chargeoptimization 5 9 1 40 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.maxpower max power uint8 (>=0<=254) % True number.boiler_dhw_max_power number.boiler_dhw_maxpower 5 9 1 41 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.maxtemp maximum temperature uint8 (>=0<=80) C True number.boiler_dhw_maximum_temperature number.boiler_dhw_maxtemp 5 9 1 42 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.circpump circulation pump available boolean True switch.boiler_dhw_circulation_pump_available switch.boiler_dhw_circpump 5 9 1 43 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.chargetype charging type enum [chargepump|3-way valve] False sensor.boiler_dhw_charging_type sensor.boiler_dhw_chargetype 5 9 1 44 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_on_temperature number.boiler_dhw_hyston 5 9 1 45 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_off_temperature number.boiler_dhw_hystoff 5 9 1 46 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.disinfectiontemp disinfection temperature uint8 (>=60<=80) C True number.boiler_dhw_disinfection_temperature number.boiler_dhw_disinfectiontemp 5 9 1 47 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.boiler_dhw_circulation_pump_mode select.boiler_dhw_circmode 5 9 1 48 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.circ circulation active boolean True switch.boiler_dhw_circulation_active switch.boiler_dhw_circ 5 9 1 49 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.curtemp current intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_intern_temperature sensor.boiler_dhw_curtemp 5 9 1/10 50 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_extern_temperature sensor.boiler_dhw_curtemp2 5 9 1/10 51 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.curflow current tap water flow uint8 (>=0<=25) l/min False sensor.boiler_dhw_current_tap_water_flow sensor.boiler_dhw_curflow 5 9 1/10 52 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_intern_temperature sensor.boiler_dhw_storagetemp1 5 9 1/10 53 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.storagetemp2 storage extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_extern_temperature sensor.boiler_dhw_storagetemp2 5 9 1/10 54 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.activated activated boolean True switch.boiler_dhw_activated switch.boiler_dhw_activated 5 9 1 55 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.onetime one time charging boolean True switch.boiler_dhw_one_time_charging switch.boiler_dhw_onetime 5 9 1 56 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.disinfecting disinfecting boolean True switch.boiler_dhw_disinfecting switch.boiler_dhw_disinfecting 5 9 1 57 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.charging charging boolean False binary_sensor.boiler_dhw_charging binary_sensor.boiler_dhw_charging 5 9 1 58 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.recharging recharging boolean False binary_sensor.boiler_dhw_recharging binary_sensor.boiler_dhw_recharging 5 9 1 59 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.tempok temperature ok boolean False binary_sensor.boiler_dhw_temperature_ok binary_sensor.boiler_dhw_tempok 5 9 1 60 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.active active boolean False binary_sensor.boiler_dhw_active binary_sensor.boiler_dhw_active 5 9 1 61 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.3wayvalve 3-way valve active boolean False binary_sensor.boiler_dhw_3-way_valve_active binary_sensor.boiler_dhw_3wayvalve 5 9 1 62 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.mixertemp mixer temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_mixer_temperature sensor.boiler_dhw_mixertemp 5 9 1/10 63 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.cylmiddletemp cylinder middle temperature (TS3) uint16 (>=0<=3199) C False sensor.boiler_dhw_cylinder_middle_temperature_(TS3) sensor.boiler_dhw_cylmiddletemp 5 9 1/10 64 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.starts starts uint24 (>=0<=16777214) False sensor.boiler_dhw_starts sensor.boiler_dhw_starts 5 9 1 65 2
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.workm active time time (>=0<=16777214) minutes False sensor.boiler_dhw_active_time sensor.boiler_dhw_workm 5 9 1 67 2
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 nompower nominal Power uint8 (>=0<=254) kW True number.boiler_nominal_Power number.boiler_nompower 5 0 1 270 1
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 nrgtotal total energy uint24 (>=0<=167772) kWh False sensor.boiler_total_energy sensor.boiler_nrgtotal 5 0 1/100 83 2
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 nrgheat energy heating uint24 (>=0<=10000000) kWh True number.boiler_energy_heating number.boiler_nrgheat 5 0 1/100 85 2
Logamax Plus, GB192, Condens GC9000, Greenstar ErP boiler 208 dhw.nrg energy uint24 (>=0<=10000000) kWh True number.boiler_dhw_energy number.boiler_dhw_nrg 5 9 1/100 0 2
Cascade MC400 boiler 210 reset reset cmd [-|maintenance|error|history|message] True sensor.boiler_reset sensor.boiler_reset 5 0 1 0 1
Cascade MC400 boiler 210 heatingoff force heating off boolean True switch.boiler_force_heating_off switch.boiler_heatingoff 5 0 1 1 1
Cascade MC400 boiler 210 heatingactive heating active boolean False binary_sensor.boiler_heating_active binary_sensor.boiler_heatingactive 5 0 1 2 1
Cascade MC400 boiler 210 tapwateractive tapwater active boolean False binary_sensor.boiler_tapwater_active binary_sensor.boiler_tapwateractive 5 0 1 3 1
Cascade MC400 boiler 210 selflowtemp selected flow temperature uint8 (>=0<=90) C True number.boiler_selected_flow_temperature number.boiler_selflowtemp 5 0 1 4 1
Cascade MC400 boiler 210 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.boiler_heating_pump_modulation sensor.boiler_heatingpumpmod 5 0 1 5 1
Cascade MC400 boiler 210 outdoortemp outside temperature int16 (>=-3199<=3199) C False sensor.boiler_outside_temperature sensor.boiler_outdoortemp 5 0 1/10 6 1
Cascade MC400 boiler 210 curflowtemp current flow temperature uint16 (>=0<=3199) C False sensor.boiler_current_flow_temperature sensor.boiler_curflowtemp 5 0 1/10 7 1
Cascade MC400 boiler 210 rettemp return temperature uint16 (>=0<=3199) C False sensor.boiler_return_temperature sensor.boiler_rettemp 5 0 1/10 8 1
Cascade MC400 boiler 210 switchtemp mixing switch temperature uint16 (>=0<=3199) C False sensor.boiler_mixing_switch_temperature sensor.boiler_switchtemp 5 0 1/10 9 1
Cascade MC400 boiler 210 syspress system pressure uint8 (>=0<=25) bar False sensor.boiler_system_pressure sensor.boiler_syspress 5 0 1/10 10 1
Cascade MC400 boiler 210 boiltemp actual boiler temperature uint16 (>=0<=3199) C False sensor.boiler_actual_boiler_temperature sensor.boiler_boiltemp 5 0 1/10 11 1
Cascade MC400 boiler 210 headertemp low loss header uint16 (>=0<=3199) C False sensor.boiler_low_loss_header sensor.boiler_headertemp 5 0 1/10 12 1
Cascade MC400 boiler 210 exhausttemp exhaust temperature uint16 (>=0<=3199) C False sensor.boiler_exhaust_temperature sensor.boiler_exhausttemp 5 0 1/10 244 1
Cascade MC400 boiler 210 burngas gas boolean False binary_sensor.boiler_gas binary_sensor.boiler_burngas 5 0 1 245 1
Cascade MC400 boiler 210 burngas2 gas stage 2 boolean False binary_sensor.boiler_gas_stage_2 binary_sensor.boiler_burngas2 5 0 1 246 1
Cascade MC400 boiler 210 flamecurr flame current uint16 (>=0<=3199) µA False sensor.boiler_flame_current sensor.boiler_flamecurr 5 0 1/10 247 1
Cascade MC400 boiler 210 fanwork fan boolean False binary_sensor.boiler_fan binary_sensor.boiler_fanwork 5 0 1 248 1
Cascade MC400 boiler 210 ignwork ignition boolean False binary_sensor.boiler_ignition binary_sensor.boiler_ignwork 5 0 1 249 1
Cascade MC400 boiler 210 oilpreheat oil preheating boolean False binary_sensor.boiler_oil_preheating binary_sensor.boiler_oilpreheat 5 0 1 250 1
Cascade MC400 boiler 210 burnminpower burner min power uint8 (>=0<=100) % True number.boiler_burner_min_power number.boiler_burnminpower 5 0 1 251 1
Cascade MC400 boiler 210 burnmaxpower burner max power uint8 (>=0<=254) % True number.boiler_burner_max_power number.boiler_burnmaxpower 5 0 1 252 1
Cascade MC400 boiler 210 burnminperiod burner min period uint8 (>=0<=120) minutes True number.boiler_burner_min_period number.boiler_burnminperiod 5 0 1 253 1
Cascade MC400 boiler 210 absburnpow burner current power (absolute) uint8 (>=0<=100) % False sensor.boiler_burner_current_power_(absolute) sensor.boiler_absburnpow 5 0 1 254 1
Cascade MC400 boiler 210 heatblock heating block uint16 (>=0<=3199) C False sensor.boiler_heating_block sensor.boiler_heatblock 5 0 1/10 255 1
Cascade MC400 boiler 210 boilhyston hysteresis on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_on_temperature number.boiler_boilhyston 5 0 1 256 1
Cascade MC400 boiler 210 boilhystoff hysteresis off temperature int8 (>=0<=20) C True number.boiler_hysteresis_off_temperature number.boiler_boilhystoff 5 0 1 257 1
Cascade MC400 boiler 210 boil2hyston hysteresis stage 2 on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_stage_2_on_temperature number.boiler_boil2hyston 5 0 1 258 1
Cascade MC400 boiler 210 boil2hystoff hysteresis stage 2 off temperature int8 (>=0<=20) C True number.boiler_hysteresis_stage_2_off_temperature number.boiler_boil2hystoff 5 0 1 259 1
Cascade MC400 boiler 210 curveon heatingcurve on boolean True switch.boiler_heatingcurve_on switch.boiler_curveon 5 0 1 260 1
Cascade MC400 boiler 210 curvebase heatingcurve base uint8 (>=20<=90) C True number.boiler_heatingcurve_base number.boiler_curvebase 5 0 1 261 1
Cascade MC400 boiler 210 curveend heatingcurve end uint8 (>=20<=90) C True number.boiler_heatingcurve_end number.boiler_curveend 5 0 1 262 1
Cascade MC400 boiler 210 summertemp summer temperature uint8 (>=0<=45) C True number.boiler_summer_temperature number.boiler_summertemp 5 0 1 263 1
Cascade MC400 boiler 210 nofrostmode nofrost mode boolean True switch.boiler_nofrost_mode switch.boiler_nofrostmode 5 0 1 264 1
Cascade MC400 boiler 210 nofrosttemp nofrost temperature uint8 (>=0<=10) C True number.boiler_nofrost_temperature number.boiler_nofrosttemp 5 0 1 265 1
Cascade MC400 boiler 210 heatingactivated heating activated boolean True switch.boiler_heating_activated switch.boiler_heatingactivated 5 0 1 13 1
Cascade MC400 boiler 210 heatingtemp heating temperature uint8 (>=0<=90) C True number.boiler_heating_temperature number.boiler_heatingtemp 5 0 1 14 1
Cascade MC400 boiler 210 heatingpump heating pump boolean False binary_sensor.boiler_heating_pump binary_sensor.boiler_heatingpump 5 0 1 15 1
Cascade MC400 boiler 210 pumpmodmax boiler pump max power uint8 (>=0<=100) % True number.boiler_boiler_pump_max_power number.boiler_pumpmodmax 5 0 1 16 1
Cascade MC400 boiler 210 pumpmodmin boiler pump min power uint8 (>=0<=100) % True number.boiler_boiler_pump_min_power number.boiler_pumpmodmin 5 0 1 17 1
Cascade MC400 boiler 210 pumpmode boiler pump mode enum [proportional|deltaP-1|deltaP-2|deltaP-3|deltaP-4] True select.boiler_boiler_pump_mode select.boiler_pumpmode 5 0 1 18 1
Cascade MC400 boiler 210 pumpcharacter boiler pump characteristic enum [proportional|150mbar|200mbar|250mbar|300mbar|350mbar|400mbar] True select.boiler_boiler_pump_characteristic select.boiler_pumpcharacter 5 0 1 19 1
Cascade MC400 boiler 210 pumpdelay pump delay uint8 (>=0<=60) minutes True number.boiler_pump_delay number.boiler_pumpdelay 5 0 1 20 1
Cascade MC400 boiler 210 pumpontemp pump logic temperature uint8 (>=0<=60) C True number.boiler_pump_logic_temperature number.boiler_pumpontemp 5 0 1 21 1
Cascade MC400 boiler 210 selburnpow burner selected max power uint8 (>=0<=254) % True number.boiler_burner_selected_max_power number.boiler_selburnpow 5 0 1 22 1
Cascade MC400 boiler 210 curburnpow burner current power uint8 (>=0<=100) % False sensor.boiler_burner_current_power sensor.boiler_curburnpow 5 0 1 23 1
Cascade MC400 boiler 210 burnstarts burner starts uint24 (>=0<=16777214) False sensor.boiler_burner_starts sensor.boiler_burnstarts 5 0 1 24 2
Cascade MC400 boiler 210 burnworkmin total burner operating time time (>=0<=16777214) minutes False sensor.boiler_total_burner_operating_time sensor.boiler_burnworkmin 5 0 1 26 2
Cascade MC400 boiler 210 burn2workmin burner stage 2 operating time time (>=0<=16777214) minutes False sensor.boiler_burner_stage_2_operating_time sensor.boiler_burn2workmin 5 0 1 28 2
Cascade MC400 boiler 210 heatworkmin total heat operating time time (>=0<=16777214) minutes False sensor.boiler_total_heat_operating_time sensor.boiler_heatworkmin 5 0 1 30 2
Cascade MC400 boiler 210 heatstarts burner starts heating uint24 (>=0<=16777214) False sensor.boiler_burner_starts_heating sensor.boiler_heatstarts 5 0 1 32 2
Cascade MC400 boiler 210 ubauptime total UBA operating time time (>=0<=16777214) minutes False sensor.boiler_total_UBA_operating_time sensor.boiler_ubauptime 5 0 1 34 2
Cascade MC400 boiler 210 lastcode last error code string False sensor.boiler_last_error_code sensor.boiler_lastcode 5 0 1 36 28
Cascade MC400 boiler 210 servicecode service code string False sensor.boiler_service_code sensor.boiler_servicecode 5 0 1 64 2
Cascade MC400 boiler 210 servicecodenumber service code number uint16 (>=0<=31999) False sensor.boiler_service_code_number sensor.boiler_servicecodenumber 5 0 1 66 1
Cascade MC400 boiler 210 maintenancemessage maintenance message string False sensor.boiler_maintenance_message sensor.boiler_maintenancemessage 5 0 1 67 2
Cascade MC400 boiler 210 maintenance maintenance scheduled enum [off|time|date|manual] True select.boiler_maintenance_scheduled select.boiler_maintenance 5 0 1 69 1
Cascade MC400 boiler 210 maintenancetime time to next maintenance uint16 (>=0<=31999) hours True number.boiler_time_to_next_maintenance number.boiler_maintenancetime 5 0 1 70 1
Cascade MC400 boiler 210 maintenancedate next maintenance date string True sensor.boiler_next_maintenance_date sensor.boiler_maintenancedate 5 0 1 71 6
Cascade MC400 boiler 210 emergencyops emergency operation boolean True switch.boiler_emergency_operation switch.boiler_emergencyops 5 0 1 77 1
Cascade MC400 boiler 210 emergencytemp emergency temperature uint8 (>=15<=70) C True number.boiler_emergency_temperature number.boiler_emergencytemp 5 0 1 78 1
Cascade MC400 boiler 210 pc0flow Flow PC0 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC0 sensor.boiler_pc0flow 5 0 1 79 1
Cascade MC400 boiler 210 pc1flow Flow PC1 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC1 sensor.boiler_pc1flow 5 0 1 80 1
Cascade MC400 boiler 210 pc1on PC1 boolean False binary_sensor.boiler_PC1 binary_sensor.boiler_pc1on 5 0 1 81 1
Cascade MC400 boiler 210 pc1rate PC1 rate uint8 (>=0<=100) % False sensor.boiler_PC1_rate sensor.boiler_pc1rate 5 0 1 82 1
Cascade MC400 boiler 210 meterheat meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_meter_heating sensor.boiler_meterheat 5 0 1/10 95 2
Cascade MC400 boiler 210 dhw.meter meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_meter sensor.boiler_dhw_meter 5 9 1/10 2 2
Cascade MC400 boiler 210 gasmeterheat gas meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_gas_meter_heating sensor.boiler_gasmeterheat 5 0 1/10 266 2
Cascade MC400 boiler 210 dhw.gasmeter gas meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_gas_meter sensor.boiler_dhw_gasmeter 5 9 1/10 69 2
Cascade MC400 boiler 210 nrgheat2 energy heating 2 uint24 (>=0<=1677721) kWh False sensor.boiler_energy_heating_2 sensor.boiler_nrgheat2 5 0 1/10 268 2
Cascade MC400 boiler 210 dhw.nrg2 energy 2 uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_energy_2 sensor.boiler_dhw_nrg2 5 9 1/10 71 2
Cascade MC400 boiler 210 dhw.tapactivated turn on/off boolean True switch.boiler_dhw_turn_on/off switch.boiler_dhw_tapactivated 5 9 1 28 1
Cascade MC400 boiler 210 dhw.settemp set temperature uint8 (>=0<=254) C False sensor.boiler_dhw_set_temperature sensor.boiler_dhw_settemp 5 9 1 29 1
Cascade MC400 boiler 210 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_temperature number.boiler_dhw_seltemp 5 9 1 30 1
Cascade MC400 boiler 210 dhw.seltemplow selected lower temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_lower_temperature number.boiler_dhw_seltemplow 5 9 1 31 1
Cascade MC400 boiler 210 dhw.tempecoplus selected eco+ temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_eco+_temperature number.boiler_dhw_tempecoplus 5 9 1 32 1
Cascade MC400 boiler 210 dhw.seltempoff selected temperature for off uint8 (>=0<=254) C False sensor.boiler_dhw_selected_temperature_for_off sensor.boiler_dhw_seltempoff 5 9 1 33 1
Cascade MC400 boiler 210 dhw.seltempsingle single charge temperature uint8 (>=0<=254) C True number.boiler_dhw_single_charge_temperature number.boiler_dhw_seltempsingle 5 9 1 34 1
Cascade MC400 boiler 210 dhw.solartemp solar boiler temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_solar_boiler_temperature sensor.boiler_dhw_solartemp 5 9 1/10 35 1
Cascade MC400 boiler 210 dhw.type type enum [off|flow|buffered flow|buffer|layered buffer] False sensor.boiler_dhw_type sensor.boiler_dhw_type 5 9 1 36 1
Cascade MC400 boiler 210 dhw.comfort comfort enum [hot|eco|intelligent] True select.boiler_dhw_comfort select.boiler_dhw_comfort 5 9 1 37 1
Cascade MC400 boiler 210 dhw.comfort1 comfort mode enum [high comfort|eco] True select.boiler_dhw_comfort_mode select.boiler_dhw_comfort1 5 9 1 38 1
Cascade MC400 boiler 210 dhw.flowtempoffset flow temperature offset uint8 (>=0<=100) C True number.boiler_dhw_flow_temperature_offset number.boiler_dhw_flowtempoffset 5 9 1 39 1
Cascade MC400 boiler 210 dhw.chargeoptimization charge optimization boolean True switch.boiler_dhw_charge_optimization switch.boiler_dhw_chargeoptimization 5 9 1 40 1
Cascade MC400 boiler 210 dhw.maxpower max power uint8 (>=0<=254) % True number.boiler_dhw_max_power number.boiler_dhw_maxpower 5 9 1 41 1
Cascade MC400 boiler 210 dhw.maxtemp maximum temperature uint8 (>=0<=80) C True number.boiler_dhw_maximum_temperature number.boiler_dhw_maxtemp 5 9 1 42 1
Cascade MC400 boiler 210 dhw.circpump circulation pump available boolean True switch.boiler_dhw_circulation_pump_available switch.boiler_dhw_circpump 5 9 1 43 1
Cascade MC400 boiler 210 dhw.chargetype charging type enum [chargepump|3-way valve] False sensor.boiler_dhw_charging_type sensor.boiler_dhw_chargetype 5 9 1 44 1
Cascade MC400 boiler 210 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_on_temperature number.boiler_dhw_hyston 5 9 1 45 1
Cascade MC400 boiler 210 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_off_temperature number.boiler_dhw_hystoff 5 9 1 46 1
Cascade MC400 boiler 210 dhw.disinfectiontemp disinfection temperature uint8 (>=60<=80) C True number.boiler_dhw_disinfection_temperature number.boiler_dhw_disinfectiontemp 5 9 1 47 1
Cascade MC400 boiler 210 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.boiler_dhw_circulation_pump_mode select.boiler_dhw_circmode 5 9 1 48 1
Cascade MC400 boiler 210 dhw.circ circulation active boolean True switch.boiler_dhw_circulation_active switch.boiler_dhw_circ 5 9 1 49 1
Cascade MC400 boiler 210 dhw.curtemp current intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_intern_temperature sensor.boiler_dhw_curtemp 5 9 1/10 50 1
Cascade MC400 boiler 210 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_extern_temperature sensor.boiler_dhw_curtemp2 5 9 1/10 51 1
Cascade MC400 boiler 210 dhw.curflow current tap water flow uint8 (>=0<=25) l/min False sensor.boiler_dhw_current_tap_water_flow sensor.boiler_dhw_curflow 5 9 1/10 52 1
Cascade MC400 boiler 210 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_intern_temperature sensor.boiler_dhw_storagetemp1 5 9 1/10 53 1
Cascade MC400 boiler 210 dhw.storagetemp2 storage extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_extern_temperature sensor.boiler_dhw_storagetemp2 5 9 1/10 54 1
Cascade MC400 boiler 210 dhw.activated activated boolean True switch.boiler_dhw_activated switch.boiler_dhw_activated 5 9 1 55 1
Cascade MC400 boiler 210 dhw.onetime one time charging boolean True switch.boiler_dhw_one_time_charging switch.boiler_dhw_onetime 5 9 1 56 1
Cascade MC400 boiler 210 dhw.disinfecting disinfecting boolean True switch.boiler_dhw_disinfecting switch.boiler_dhw_disinfecting 5 9 1 57 1
Cascade MC400 boiler 210 dhw.charging charging boolean False binary_sensor.boiler_dhw_charging binary_sensor.boiler_dhw_charging 5 9 1 58 1
Cascade MC400 boiler 210 dhw.recharging recharging boolean False binary_sensor.boiler_dhw_recharging binary_sensor.boiler_dhw_recharging 5 9 1 59 1
Cascade MC400 boiler 210 dhw.tempok temperature ok boolean False binary_sensor.boiler_dhw_temperature_ok binary_sensor.boiler_dhw_tempok 5 9 1 60 1
Cascade MC400 boiler 210 dhw.active active boolean False binary_sensor.boiler_dhw_active binary_sensor.boiler_dhw_active 5 9 1 61 1
Cascade MC400 boiler 210 dhw.3wayvalve 3-way valve active boolean False binary_sensor.boiler_dhw_3-way_valve_active binary_sensor.boiler_dhw_3wayvalve 5 9 1 62 1
Cascade MC400 boiler 210 dhw.mixertemp mixer temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_mixer_temperature sensor.boiler_dhw_mixertemp 5 9 1/10 63 1
Cascade MC400 boiler 210 dhw.cylmiddletemp cylinder middle temperature (TS3) uint16 (>=0<=3199) C False sensor.boiler_dhw_cylinder_middle_temperature_(TS3) sensor.boiler_dhw_cylmiddletemp 5 9 1/10 64 1
Cascade MC400 boiler 210 dhw.starts starts uint24 (>=0<=16777214) False sensor.boiler_dhw_starts sensor.boiler_dhw_starts 5 9 1 65 2
Cascade MC400 boiler 210 dhw.workm active time time (>=0<=16777214) minutes False sensor.boiler_dhw_active_time sensor.boiler_dhw_workm 5 9 1 67 2
Cascade MC400 boiler 210 nompower nominal Power uint8 (>=0<=254) kW True number.boiler_nominal_Power number.boiler_nompower 5 0 1 270 1
Cascade MC400 boiler 210 nrgtotal total energy uint24 (>=0<=167772) kWh False sensor.boiler_total_energy sensor.boiler_nrgtotal 5 0 1/100 83 2
Cascade MC400 boiler 210 nrgheat energy heating uint24 (>=0<=10000000) kWh True number.boiler_energy_heating number.boiler_nrgheat 5 0 1/100 85 2
Cascade MC400 boiler 210 dhw.nrg energy uint24 (>=0<=10000000) kWh True number.boiler_dhw_energy number.boiler_dhw_nrg 5 9 1/100 0 2
EasyControl Adapter boiler 211 reset reset cmd [-|maintenance|error|history|message] True sensor.boiler_reset sensor.boiler_reset 5 0 1 0 1
EasyControl Adapter boiler 211 heatingoff force heating off boolean True switch.boiler_force_heating_off switch.boiler_heatingoff 5 0 1 1 1
EasyControl Adapter boiler 211 heatingactive heating active boolean False binary_sensor.boiler_heating_active binary_sensor.boiler_heatingactive 5 0 1 2 1
EasyControl Adapter boiler 211 tapwateractive tapwater active boolean False binary_sensor.boiler_tapwater_active binary_sensor.boiler_tapwateractive 5 0 1 3 1
EasyControl Adapter boiler 211 selflowtemp selected flow temperature uint8 (>=0<=90) C True number.boiler_selected_flow_temperature number.boiler_selflowtemp 5 0 1 4 1
EasyControl Adapter boiler 211 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.boiler_heating_pump_modulation sensor.boiler_heatingpumpmod 5 0 1 5 1
EasyControl Adapter boiler 211 outdoortemp outside temperature int16 (>=-3199<=3199) C False sensor.boiler_outside_temperature sensor.boiler_outdoortemp 5 0 1/10 6 1
EasyControl Adapter boiler 211 curflowtemp current flow temperature uint16 (>=0<=3199) C False sensor.boiler_current_flow_temperature sensor.boiler_curflowtemp 5 0 1/10 7 1
EasyControl Adapter boiler 211 rettemp return temperature uint16 (>=0<=3199) C False sensor.boiler_return_temperature sensor.boiler_rettemp 5 0 1/10 8 1
EasyControl Adapter boiler 211 switchtemp mixing switch temperature uint16 (>=0<=3199) C False sensor.boiler_mixing_switch_temperature sensor.boiler_switchtemp 5 0 1/10 9 1
EasyControl Adapter boiler 211 syspress system pressure uint8 (>=0<=25) bar False sensor.boiler_system_pressure sensor.boiler_syspress 5 0 1/10 10 1
EasyControl Adapter boiler 211 boiltemp actual boiler temperature uint16 (>=0<=3199) C False sensor.boiler_actual_boiler_temperature sensor.boiler_boiltemp 5 0 1/10 11 1
EasyControl Adapter boiler 211 headertemp low loss header uint16 (>=0<=3199) C False sensor.boiler_low_loss_header sensor.boiler_headertemp 5 0 1/10 12 1
EasyControl Adapter boiler 211 exhausttemp exhaust temperature uint16 (>=0<=3199) C False sensor.boiler_exhaust_temperature sensor.boiler_exhausttemp 5 0 1/10 244 1
EasyControl Adapter boiler 211 burngas gas boolean False binary_sensor.boiler_gas binary_sensor.boiler_burngas 5 0 1 245 1
EasyControl Adapter boiler 211 burngas2 gas stage 2 boolean False binary_sensor.boiler_gas_stage_2 binary_sensor.boiler_burngas2 5 0 1 246 1
EasyControl Adapter boiler 211 flamecurr flame current uint16 (>=0<=3199) µA False sensor.boiler_flame_current sensor.boiler_flamecurr 5 0 1/10 247 1
EasyControl Adapter boiler 211 fanwork fan boolean False binary_sensor.boiler_fan binary_sensor.boiler_fanwork 5 0 1 248 1
EasyControl Adapter boiler 211 ignwork ignition boolean False binary_sensor.boiler_ignition binary_sensor.boiler_ignwork 5 0 1 249 1
EasyControl Adapter boiler 211 oilpreheat oil preheating boolean False binary_sensor.boiler_oil_preheating binary_sensor.boiler_oilpreheat 5 0 1 250 1
EasyControl Adapter boiler 211 burnminpower burner min power uint8 (>=0<=100) % True number.boiler_burner_min_power number.boiler_burnminpower 5 0 1 251 1
EasyControl Adapter boiler 211 burnmaxpower burner max power uint8 (>=0<=254) % True number.boiler_burner_max_power number.boiler_burnmaxpower 5 0 1 252 1
EasyControl Adapter boiler 211 burnminperiod burner min period uint8 (>=0<=120) minutes True number.boiler_burner_min_period number.boiler_burnminperiod 5 0 1 253 1
EasyControl Adapter boiler 211 absburnpow burner current power (absolute) uint8 (>=0<=100) % False sensor.boiler_burner_current_power_(absolute) sensor.boiler_absburnpow 5 0 1 254 1
EasyControl Adapter boiler 211 heatblock heating block uint16 (>=0<=3199) C False sensor.boiler_heating_block sensor.boiler_heatblock 5 0 1/10 255 1
EasyControl Adapter boiler 211 boilhyston hysteresis on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_on_temperature number.boiler_boilhyston 5 0 1 256 1
EasyControl Adapter boiler 211 boilhystoff hysteresis off temperature int8 (>=0<=20) C True number.boiler_hysteresis_off_temperature number.boiler_boilhystoff 5 0 1 257 1
EasyControl Adapter boiler 211 boil2hyston hysteresis stage 2 on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_stage_2_on_temperature number.boiler_boil2hyston 5 0 1 258 1
EasyControl Adapter boiler 211 boil2hystoff hysteresis stage 2 off temperature int8 (>=0<=20) C True number.boiler_hysteresis_stage_2_off_temperature number.boiler_boil2hystoff 5 0 1 259 1
EasyControl Adapter boiler 211 curveon heatingcurve on boolean True switch.boiler_heatingcurve_on switch.boiler_curveon 5 0 1 260 1
EasyControl Adapter boiler 211 curvebase heatingcurve base uint8 (>=20<=90) C True number.boiler_heatingcurve_base number.boiler_curvebase 5 0 1 261 1
EasyControl Adapter boiler 211 curveend heatingcurve end uint8 (>=20<=90) C True number.boiler_heatingcurve_end number.boiler_curveend 5 0 1 262 1
EasyControl Adapter boiler 211 summertemp summer temperature uint8 (>=0<=45) C True number.boiler_summer_temperature number.boiler_summertemp 5 0 1 263 1
EasyControl Adapter boiler 211 nofrostmode nofrost mode boolean True switch.boiler_nofrost_mode switch.boiler_nofrostmode 5 0 1 264 1
EasyControl Adapter boiler 211 nofrosttemp nofrost temperature uint8 (>=0<=10) C True number.boiler_nofrost_temperature number.boiler_nofrosttemp 5 0 1 265 1
EasyControl Adapter boiler 211 heatingactivated heating activated boolean True switch.boiler_heating_activated switch.boiler_heatingactivated 5 0 1 13 1
EasyControl Adapter boiler 211 heatingtemp heating temperature uint8 (>=0<=90) C True number.boiler_heating_temperature number.boiler_heatingtemp 5 0 1 14 1
EasyControl Adapter boiler 211 heatingpump heating pump boolean False binary_sensor.boiler_heating_pump binary_sensor.boiler_heatingpump 5 0 1 15 1
EasyControl Adapter boiler 211 pumpmodmax boiler pump max power uint8 (>=0<=100) % True number.boiler_boiler_pump_max_power number.boiler_pumpmodmax 5 0 1 16 1
EasyControl Adapter boiler 211 pumpmodmin boiler pump min power uint8 (>=0<=100) % True number.boiler_boiler_pump_min_power number.boiler_pumpmodmin 5 0 1 17 1
EasyControl Adapter boiler 211 pumpmode boiler pump mode enum [proportional|deltaP-1|deltaP-2|deltaP-3|deltaP-4] True select.boiler_boiler_pump_mode select.boiler_pumpmode 5 0 1 18 1
EasyControl Adapter boiler 211 pumpcharacter boiler pump characteristic enum [proportional|150mbar|200mbar|250mbar|300mbar|350mbar|400mbar] True select.boiler_boiler_pump_characteristic select.boiler_pumpcharacter 5 0 1 19 1
EasyControl Adapter boiler 211 pumpdelay pump delay uint8 (>=0<=60) minutes True number.boiler_pump_delay number.boiler_pumpdelay 5 0 1 20 1
EasyControl Adapter boiler 211 pumpontemp pump logic temperature uint8 (>=0<=60) C True number.boiler_pump_logic_temperature number.boiler_pumpontemp 5 0 1 21 1
EasyControl Adapter boiler 211 selburnpow burner selected max power uint8 (>=0<=254) % True number.boiler_burner_selected_max_power number.boiler_selburnpow 5 0 1 22 1
EasyControl Adapter boiler 211 curburnpow burner current power uint8 (>=0<=100) % False sensor.boiler_burner_current_power sensor.boiler_curburnpow 5 0 1 23 1
EasyControl Adapter boiler 211 burnstarts burner starts uint24 (>=0<=16777214) False sensor.boiler_burner_starts sensor.boiler_burnstarts 5 0 1 24 2
EasyControl Adapter boiler 211 burnworkmin total burner operating time time (>=0<=16777214) minutes False sensor.boiler_total_burner_operating_time sensor.boiler_burnworkmin 5 0 1 26 2
EasyControl Adapter boiler 211 burn2workmin burner stage 2 operating time time (>=0<=16777214) minutes False sensor.boiler_burner_stage_2_operating_time sensor.boiler_burn2workmin 5 0 1 28 2
EasyControl Adapter boiler 211 heatworkmin total heat operating time time (>=0<=16777214) minutes False sensor.boiler_total_heat_operating_time sensor.boiler_heatworkmin 5 0 1 30 2
EasyControl Adapter boiler 211 heatstarts burner starts heating uint24 (>=0<=16777214) False sensor.boiler_burner_starts_heating sensor.boiler_heatstarts 5 0 1 32 2
EasyControl Adapter boiler 211 ubauptime total UBA operating time time (>=0<=16777214) minutes False sensor.boiler_total_UBA_operating_time sensor.boiler_ubauptime 5 0 1 34 2
EasyControl Adapter boiler 211 lastcode last error code string False sensor.boiler_last_error_code sensor.boiler_lastcode 5 0 1 36 28
EasyControl Adapter boiler 211 servicecode service code string False sensor.boiler_service_code sensor.boiler_servicecode 5 0 1 64 2
EasyControl Adapter boiler 211 servicecodenumber service code number uint16 (>=0<=31999) False sensor.boiler_service_code_number sensor.boiler_servicecodenumber 5 0 1 66 1
EasyControl Adapter boiler 211 maintenancemessage maintenance message string False sensor.boiler_maintenance_message sensor.boiler_maintenancemessage 5 0 1 67 2
EasyControl Adapter boiler 211 maintenance maintenance scheduled enum [off|time|date|manual] True select.boiler_maintenance_scheduled select.boiler_maintenance 5 0 1 69 1
EasyControl Adapter boiler 211 maintenancetime time to next maintenance uint16 (>=0<=31999) hours True number.boiler_time_to_next_maintenance number.boiler_maintenancetime 5 0 1 70 1
EasyControl Adapter boiler 211 maintenancedate next maintenance date string True sensor.boiler_next_maintenance_date sensor.boiler_maintenancedate 5 0 1 71 6
EasyControl Adapter boiler 211 emergencyops emergency operation boolean True switch.boiler_emergency_operation switch.boiler_emergencyops 5 0 1 77 1
EasyControl Adapter boiler 211 emergencytemp emergency temperature uint8 (>=15<=70) C True number.boiler_emergency_temperature number.boiler_emergencytemp 5 0 1 78 1
EasyControl Adapter boiler 211 pc0flow Flow PC0 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC0 sensor.boiler_pc0flow 5 0 1 79 1
EasyControl Adapter boiler 211 pc1flow Flow PC1 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC1 sensor.boiler_pc1flow 5 0 1 80 1
EasyControl Adapter boiler 211 pc1on PC1 boolean False binary_sensor.boiler_PC1 binary_sensor.boiler_pc1on 5 0 1 81 1
EasyControl Adapter boiler 211 pc1rate PC1 rate uint8 (>=0<=100) % False sensor.boiler_PC1_rate sensor.boiler_pc1rate 5 0 1 82 1
EasyControl Adapter boiler 211 meterheat meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_meter_heating sensor.boiler_meterheat 5 0 1/10 95 2
EasyControl Adapter boiler 211 dhw.meter meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_meter sensor.boiler_dhw_meter 5 9 1/10 2 2
EasyControl Adapter boiler 211 gasmeterheat gas meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_gas_meter_heating sensor.boiler_gasmeterheat 5 0 1/10 266 2
EasyControl Adapter boiler 211 dhw.gasmeter gas meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_gas_meter sensor.boiler_dhw_gasmeter 5 9 1/10 69 2
EasyControl Adapter boiler 211 nrgheat2 energy heating 2 uint24 (>=0<=1677721) kWh False sensor.boiler_energy_heating_2 sensor.boiler_nrgheat2 5 0 1/10 268 2
EasyControl Adapter boiler 211 dhw.nrg2 energy 2 uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_energy_2 sensor.boiler_dhw_nrg2 5 9 1/10 71 2
EasyControl Adapter boiler 211 dhw.tapactivated turn on/off boolean True switch.boiler_dhw_turn_on/off switch.boiler_dhw_tapactivated 5 9 1 28 1
EasyControl Adapter boiler 211 dhw.settemp set temperature uint8 (>=0<=254) C False sensor.boiler_dhw_set_temperature sensor.boiler_dhw_settemp 5 9 1 29 1
EasyControl Adapter boiler 211 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_temperature number.boiler_dhw_seltemp 5 9 1 30 1
EasyControl Adapter boiler 211 dhw.seltemplow selected lower temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_lower_temperature number.boiler_dhw_seltemplow 5 9 1 31 1
EasyControl Adapter boiler 211 dhw.tempecoplus selected eco+ temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_eco+_temperature number.boiler_dhw_tempecoplus 5 9 1 32 1
EasyControl Adapter boiler 211 dhw.seltempoff selected temperature for off uint8 (>=0<=254) C False sensor.boiler_dhw_selected_temperature_for_off sensor.boiler_dhw_seltempoff 5 9 1 33 1
EasyControl Adapter boiler 211 dhw.seltempsingle single charge temperature uint8 (>=0<=254) C True number.boiler_dhw_single_charge_temperature number.boiler_dhw_seltempsingle 5 9 1 34 1
EasyControl Adapter boiler 211 dhw.solartemp solar boiler temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_solar_boiler_temperature sensor.boiler_dhw_solartemp 5 9 1/10 35 1
EasyControl Adapter boiler 211 dhw.type type enum [off|flow|buffered flow|buffer|layered buffer] False sensor.boiler_dhw_type sensor.boiler_dhw_type 5 9 1 36 1
EasyControl Adapter boiler 211 dhw.comfort comfort enum [hot|eco|intelligent] True select.boiler_dhw_comfort select.boiler_dhw_comfort 5 9 1 37 1
EasyControl Adapter boiler 211 dhw.comfort1 comfort mode enum [high comfort|eco] True select.boiler_dhw_comfort_mode select.boiler_dhw_comfort1 5 9 1 38 1
EasyControl Adapter boiler 211 dhw.flowtempoffset flow temperature offset uint8 (>=0<=100) C True number.boiler_dhw_flow_temperature_offset number.boiler_dhw_flowtempoffset 5 9 1 39 1
EasyControl Adapter boiler 211 dhw.chargeoptimization charge optimization boolean True switch.boiler_dhw_charge_optimization switch.boiler_dhw_chargeoptimization 5 9 1 40 1
EasyControl Adapter boiler 211 dhw.maxpower max power uint8 (>=0<=254) % True number.boiler_dhw_max_power number.boiler_dhw_maxpower 5 9 1 41 1
EasyControl Adapter boiler 211 dhw.maxtemp maximum temperature uint8 (>=0<=80) C True number.boiler_dhw_maximum_temperature number.boiler_dhw_maxtemp 5 9 1 42 1
EasyControl Adapter boiler 211 dhw.circpump circulation pump available boolean True switch.boiler_dhw_circulation_pump_available switch.boiler_dhw_circpump 5 9 1 43 1
EasyControl Adapter boiler 211 dhw.chargetype charging type enum [chargepump|3-way valve] False sensor.boiler_dhw_charging_type sensor.boiler_dhw_chargetype 5 9 1 44 1
EasyControl Adapter boiler 211 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_on_temperature number.boiler_dhw_hyston 5 9 1 45 1
EasyControl Adapter boiler 211 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_off_temperature number.boiler_dhw_hystoff 5 9 1 46 1
EasyControl Adapter boiler 211 dhw.disinfectiontemp disinfection temperature uint8 (>=60<=80) C True number.boiler_dhw_disinfection_temperature number.boiler_dhw_disinfectiontemp 5 9 1 47 1
EasyControl Adapter boiler 211 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.boiler_dhw_circulation_pump_mode select.boiler_dhw_circmode 5 9 1 48 1
EasyControl Adapter boiler 211 dhw.circ circulation active boolean True switch.boiler_dhw_circulation_active switch.boiler_dhw_circ 5 9 1 49 1
EasyControl Adapter boiler 211 dhw.curtemp current intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_intern_temperature sensor.boiler_dhw_curtemp 5 9 1/10 50 1
EasyControl Adapter boiler 211 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_extern_temperature sensor.boiler_dhw_curtemp2 5 9 1/10 51 1
EasyControl Adapter boiler 211 dhw.curflow current tap water flow uint8 (>=0<=25) l/min False sensor.boiler_dhw_current_tap_water_flow sensor.boiler_dhw_curflow 5 9 1/10 52 1
EasyControl Adapter boiler 211 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_intern_temperature sensor.boiler_dhw_storagetemp1 5 9 1/10 53 1
EasyControl Adapter boiler 211 dhw.storagetemp2 storage extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_extern_temperature sensor.boiler_dhw_storagetemp2 5 9 1/10 54 1
EasyControl Adapter boiler 211 dhw.activated activated boolean True switch.boiler_dhw_activated switch.boiler_dhw_activated 5 9 1 55 1
EasyControl Adapter boiler 211 dhw.onetime one time charging boolean True switch.boiler_dhw_one_time_charging switch.boiler_dhw_onetime 5 9 1 56 1
EasyControl Adapter boiler 211 dhw.disinfecting disinfecting boolean True switch.boiler_dhw_disinfecting switch.boiler_dhw_disinfecting 5 9 1 57 1
EasyControl Adapter boiler 211 dhw.charging charging boolean False binary_sensor.boiler_dhw_charging binary_sensor.boiler_dhw_charging 5 9 1 58 1
EasyControl Adapter boiler 211 dhw.recharging recharging boolean False binary_sensor.boiler_dhw_recharging binary_sensor.boiler_dhw_recharging 5 9 1 59 1
EasyControl Adapter boiler 211 dhw.tempok temperature ok boolean False binary_sensor.boiler_dhw_temperature_ok binary_sensor.boiler_dhw_tempok 5 9 1 60 1
EasyControl Adapter boiler 211 dhw.active active boolean False binary_sensor.boiler_dhw_active binary_sensor.boiler_dhw_active 5 9 1 61 1
EasyControl Adapter boiler 211 dhw.3wayvalve 3-way valve active boolean False binary_sensor.boiler_dhw_3-way_valve_active binary_sensor.boiler_dhw_3wayvalve 5 9 1 62 1
EasyControl Adapter boiler 211 dhw.mixertemp mixer temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_mixer_temperature sensor.boiler_dhw_mixertemp 5 9 1/10 63 1
EasyControl Adapter boiler 211 dhw.cylmiddletemp cylinder middle temperature (TS3) uint16 (>=0<=3199) C False sensor.boiler_dhw_cylinder_middle_temperature_(TS3) sensor.boiler_dhw_cylmiddletemp 5 9 1/10 64 1
EasyControl Adapter boiler 211 dhw.starts starts uint24 (>=0<=16777214) False sensor.boiler_dhw_starts sensor.boiler_dhw_starts 5 9 1 65 2
EasyControl Adapter boiler 211 dhw.workm active time time (>=0<=16777214) minutes False sensor.boiler_dhw_active_time sensor.boiler_dhw_workm 5 9 1 67 2
EasyControl Adapter boiler 211 nompower nominal Power uint8 (>=0<=254) kW True number.boiler_nominal_Power number.boiler_nompower 5 0 1 270 1
EasyControl Adapter boiler 211 nrgtotal total energy uint24 (>=0<=167772) kWh False sensor.boiler_total_energy sensor.boiler_nrgtotal 5 0 1/100 83 2
EasyControl Adapter boiler 211 nrgheat energy heating uint24 (>=0<=10000000) kWh True number.boiler_energy_heating number.boiler_nrgheat 5 0 1/100 85 2
EasyControl Adapter boiler 211 dhw.nrg energy uint24 (>=0<=10000000) kWh True number.boiler_dhw_energy number.boiler_dhw_nrg 5 9 1/100 0 2
Greenstar HIU, Logamax kompakt WS170 boiler 219 netflowtemp heat network flow temp uint16 (>=0<=3199) C False sensor.boiler_heat_network_flow_temp sensor.boiler_netflowtemp 5 0 1/10 271 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 heatvalve heating valve uint8 (>=0<=100) % False sensor.boiler_heating_valve sensor.boiler_heatvalve 5 0 1 272 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.dhwvalve valve uint8 (>=0<=100) % False sensor.boiler_dhw_valve sensor.boiler_dhw_dhwvalve 5 9 1 73 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 keepwarmtemp keep warm temperature uint8 (>=0<=254) C True number.boiler_keep_warm_temperature number.boiler_keepwarmtemp 5 0 1 273 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 setreturntemp set temp return uint8 (>=0<=254) C True number.boiler_set_temp_return number.boiler_setreturntemp 5 0 1 274 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 heating heating boolean False binary_sensor.boiler_heating binary_sensor.boiler_heating 5 0 1 275 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 reset reset cmd [-|maintenance|error|history|message] True sensor.boiler_reset sensor.boiler_reset 5 0 1 0 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 heatingoff force heating off boolean True switch.boiler_force_heating_off switch.boiler_heatingoff 5 0 1 1 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 heatingactive heating active boolean False binary_sensor.boiler_heating_active binary_sensor.boiler_heatingactive 5 0 1 2 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 tapwateractive tapwater active boolean False binary_sensor.boiler_tapwater_active binary_sensor.boiler_tapwateractive 5 0 1 3 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 selflowtemp selected flow temperature uint8 (>=0<=90) C True number.boiler_selected_flow_temperature number.boiler_selflowtemp 5 0 1 4 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.boiler_heating_pump_modulation sensor.boiler_heatingpumpmod 5 0 1 5 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 outdoortemp outside temperature int16 (>=-3199<=3199) C False sensor.boiler_outside_temperature sensor.boiler_outdoortemp 5 0 1/10 6 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 curflowtemp current flow temperature uint16 (>=0<=3199) C False sensor.boiler_current_flow_temperature sensor.boiler_curflowtemp 5 0 1/10 7 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 rettemp return temperature uint16 (>=0<=3199) C False sensor.boiler_return_temperature sensor.boiler_rettemp 5 0 1/10 8 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 switchtemp mixing switch temperature uint16 (>=0<=3199) C False sensor.boiler_mixing_switch_temperature sensor.boiler_switchtemp 5 0 1/10 9 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 syspress system pressure uint8 (>=0<=25) bar False sensor.boiler_system_pressure sensor.boiler_syspress 5 0 1/10 10 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 boiltemp actual boiler temperature uint16 (>=0<=3199) C False sensor.boiler_actual_boiler_temperature sensor.boiler_boiltemp 5 0 1/10 11 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 headertemp low loss header uint16 (>=0<=3199) C False sensor.boiler_low_loss_header sensor.boiler_headertemp 5 0 1/10 12 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 heatingactivated heating activated boolean True switch.boiler_heating_activated switch.boiler_heatingactivated 5 0 1 13 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 heatingtemp heating temperature uint8 (>=0<=90) C True number.boiler_heating_temperature number.boiler_heatingtemp 5 0 1 14 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 heatingpump heating pump boolean False binary_sensor.boiler_heating_pump binary_sensor.boiler_heatingpump 5 0 1 15 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 pumpmodmax boiler pump max power uint8 (>=0<=100) % True number.boiler_boiler_pump_max_power number.boiler_pumpmodmax 5 0 1 16 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 pumpmodmin boiler pump min power uint8 (>=0<=100) % True number.boiler_boiler_pump_min_power number.boiler_pumpmodmin 5 0 1 17 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 pumpmode boiler pump mode enum [proportional|deltaP-1|deltaP-2|deltaP-3|deltaP-4] True select.boiler_boiler_pump_mode select.boiler_pumpmode 5 0 1 18 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 pumpcharacter boiler pump characteristic enum [proportional|150mbar|200mbar|250mbar|300mbar|350mbar|400mbar] True select.boiler_boiler_pump_characteristic select.boiler_pumpcharacter 5 0 1 19 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 pumpdelay pump delay uint8 (>=0<=60) minutes True number.boiler_pump_delay number.boiler_pumpdelay 5 0 1 20 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 pumpontemp pump logic temperature uint8 (>=0<=60) C True number.boiler_pump_logic_temperature number.boiler_pumpontemp 5 0 1 21 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 selburnpow burner selected max power uint8 (>=0<=254) % True number.boiler_burner_selected_max_power number.boiler_selburnpow 5 0 1 22 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 curburnpow burner current power uint8 (>=0<=100) % False sensor.boiler_burner_current_power sensor.boiler_curburnpow 5 0 1 23 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 burnstarts burner starts uint24 (>=0<=16777214) False sensor.boiler_burner_starts sensor.boiler_burnstarts 5 0 1 24 2
Greenstar HIU, Logamax kompakt WS170 boiler 219 burnworkmin total burner operating time time (>=0<=16777214) minutes False sensor.boiler_total_burner_operating_time sensor.boiler_burnworkmin 5 0 1 26 2
Greenstar HIU, Logamax kompakt WS170 boiler 219 burn2workmin burner stage 2 operating time time (>=0<=16777214) minutes False sensor.boiler_burner_stage_2_operating_time sensor.boiler_burn2workmin 5 0 1 28 2
Greenstar HIU, Logamax kompakt WS170 boiler 219 heatworkmin total heat operating time time (>=0<=16777214) minutes False sensor.boiler_total_heat_operating_time sensor.boiler_heatworkmin 5 0 1 30 2
Greenstar HIU, Logamax kompakt WS170 boiler 219 heatstarts burner starts heating uint24 (>=0<=16777214) False sensor.boiler_burner_starts_heating sensor.boiler_heatstarts 5 0 1 32 2
Greenstar HIU, Logamax kompakt WS170 boiler 219 ubauptime total UBA operating time time (>=0<=16777214) minutes False sensor.boiler_total_UBA_operating_time sensor.boiler_ubauptime 5 0 1 34 2
Greenstar HIU, Logamax kompakt WS170 boiler 219 lastcode last error code string False sensor.boiler_last_error_code sensor.boiler_lastcode 5 0 1 36 28
Greenstar HIU, Logamax kompakt WS170 boiler 219 servicecode service code string False sensor.boiler_service_code sensor.boiler_servicecode 5 0 1 64 2
Greenstar HIU, Logamax kompakt WS170 boiler 219 servicecodenumber service code number uint16 (>=0<=31999) False sensor.boiler_service_code_number sensor.boiler_servicecodenumber 5 0 1 66 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 maintenancemessage maintenance message string False sensor.boiler_maintenance_message sensor.boiler_maintenancemessage 5 0 1 67 2
Greenstar HIU, Logamax kompakt WS170 boiler 219 maintenance maintenance scheduled enum [off|time|date|manual] True select.boiler_maintenance_scheduled select.boiler_maintenance 5 0 1 69 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 maintenancetime time to next maintenance uint16 (>=0<=31999) hours True number.boiler_time_to_next_maintenance number.boiler_maintenancetime 5 0 1 70 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 maintenancedate next maintenance date string True sensor.boiler_next_maintenance_date sensor.boiler_maintenancedate 5 0 1 71 6
Greenstar HIU, Logamax kompakt WS170 boiler 219 emergencyops emergency operation boolean True switch.boiler_emergency_operation switch.boiler_emergencyops 5 0 1 77 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 emergencytemp emergency temperature uint8 (>=15<=70) C True number.boiler_emergency_temperature number.boiler_emergencytemp 5 0 1 78 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 pc0flow Flow PC0 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC0 sensor.boiler_pc0flow 5 0 1 79 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 pc1flow Flow PC1 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC1 sensor.boiler_pc1flow 5 0 1 80 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 pc1on PC1 boolean False binary_sensor.boiler_PC1 binary_sensor.boiler_pc1on 5 0 1 81 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 pc1rate PC1 rate uint8 (>=0<=100) % False sensor.boiler_PC1_rate sensor.boiler_pc1rate 5 0 1 82 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 meterheat meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_meter_heating sensor.boiler_meterheat 5 0 1/10 95 2
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.meter meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_meter sensor.boiler_dhw_meter 5 9 1/10 2 2
Greenstar HIU, Logamax kompakt WS170 boiler 219 gasmeterheat gas meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_gas_meter_heating sensor.boiler_gasmeterheat 5 0 1/10 266 2
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.gasmeter gas meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_gas_meter sensor.boiler_dhw_gasmeter 5 9 1/10 69 2
Greenstar HIU, Logamax kompakt WS170 boiler 219 nrgheat2 energy heating 2 uint24 (>=0<=1677721) kWh False sensor.boiler_energy_heating_2 sensor.boiler_nrgheat2 5 0 1/10 268 2
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.nrg2 energy 2 uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_energy_2 sensor.boiler_dhw_nrg2 5 9 1/10 71 2
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.tapactivated turn on/off boolean True switch.boiler_dhw_turn_on/off switch.boiler_dhw_tapactivated 5 9 1 28 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.settemp set temperature uint8 (>=0<=254) C False sensor.boiler_dhw_set_temperature sensor.boiler_dhw_settemp 5 9 1 29 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_temperature number.boiler_dhw_seltemp 5 9 1 30 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.seltemplow selected lower temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_lower_temperature number.boiler_dhw_seltemplow 5 9 1 31 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.tempecoplus selected eco+ temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_eco+_temperature number.boiler_dhw_tempecoplus 5 9 1 32 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.seltempoff selected temperature for off uint8 (>=0<=254) C False sensor.boiler_dhw_selected_temperature_for_off sensor.boiler_dhw_seltempoff 5 9 1 33 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.seltempsingle single charge temperature uint8 (>=0<=254) C True number.boiler_dhw_single_charge_temperature number.boiler_dhw_seltempsingle 5 9 1 34 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.solartemp solar boiler temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_solar_boiler_temperature sensor.boiler_dhw_solartemp 5 9 1/10 35 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.type type enum [off|flow|buffered flow|buffer|layered buffer] False sensor.boiler_dhw_type sensor.boiler_dhw_type 5 9 1 36 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.comfort comfort enum [hot|eco|intelligent] True select.boiler_dhw_comfort select.boiler_dhw_comfort 5 9 1 37 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.comfort1 comfort mode enum [high comfort|eco] True select.boiler_dhw_comfort_mode select.boiler_dhw_comfort1 5 9 1 38 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.flowtempoffset flow temperature offset uint8 (>=0<=100) C True number.boiler_dhw_flow_temperature_offset number.boiler_dhw_flowtempoffset 5 9 1 39 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.chargeoptimization charge optimization boolean True switch.boiler_dhw_charge_optimization switch.boiler_dhw_chargeoptimization 5 9 1 40 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.maxpower max power uint8 (>=0<=254) % True number.boiler_dhw_max_power number.boiler_dhw_maxpower 5 9 1 41 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.maxtemp maximum temperature uint8 (>=0<=80) C True number.boiler_dhw_maximum_temperature number.boiler_dhw_maxtemp 5 9 1 42 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.circpump circulation pump available boolean True switch.boiler_dhw_circulation_pump_available switch.boiler_dhw_circpump 5 9 1 43 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.chargetype charging type enum [chargepump|3-way valve] False sensor.boiler_dhw_charging_type sensor.boiler_dhw_chargetype 5 9 1 44 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_on_temperature number.boiler_dhw_hyston 5 9 1 45 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_off_temperature number.boiler_dhw_hystoff 5 9 1 46 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.disinfectiontemp disinfection temperature uint8 (>=60<=80) C True number.boiler_dhw_disinfection_temperature number.boiler_dhw_disinfectiontemp 5 9 1 47 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.boiler_dhw_circulation_pump_mode select.boiler_dhw_circmode 5 9 1 48 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.circ circulation active boolean True switch.boiler_dhw_circulation_active switch.boiler_dhw_circ 5 9 1 49 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.curtemp current intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_intern_temperature sensor.boiler_dhw_curtemp 5 9 1/10 50 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_extern_temperature sensor.boiler_dhw_curtemp2 5 9 1/10 51 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.curflow current tap water flow uint8 (>=0<=25) l/min False sensor.boiler_dhw_current_tap_water_flow sensor.boiler_dhw_curflow 5 9 1/10 52 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_intern_temperature sensor.boiler_dhw_storagetemp1 5 9 1/10 53 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.storagetemp2 storage extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_extern_temperature sensor.boiler_dhw_storagetemp2 5 9 1/10 54 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.activated activated boolean True switch.boiler_dhw_activated switch.boiler_dhw_activated 5 9 1 55 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.onetime one time charging boolean True switch.boiler_dhw_one_time_charging switch.boiler_dhw_onetime 5 9 1 56 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.disinfecting disinfecting boolean True switch.boiler_dhw_disinfecting switch.boiler_dhw_disinfecting 5 9 1 57 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.charging charging boolean False binary_sensor.boiler_dhw_charging binary_sensor.boiler_dhw_charging 5 9 1 58 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.recharging recharging boolean False binary_sensor.boiler_dhw_recharging binary_sensor.boiler_dhw_recharging 5 9 1 59 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.tempok temperature ok boolean False binary_sensor.boiler_dhw_temperature_ok binary_sensor.boiler_dhw_tempok 5 9 1 60 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.active active boolean False binary_sensor.boiler_dhw_active binary_sensor.boiler_dhw_active 5 9 1 61 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.3wayvalve 3-way valve active boolean False binary_sensor.boiler_dhw_3-way_valve_active binary_sensor.boiler_dhw_3wayvalve 5 9 1 62 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.mixertemp mixer temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_mixer_temperature sensor.boiler_dhw_mixertemp 5 9 1/10 63 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.cylmiddletemp cylinder middle temperature (TS3) uint16 (>=0<=3199) C False sensor.boiler_dhw_cylinder_middle_temperature_(TS3) sensor.boiler_dhw_cylmiddletemp 5 9 1/10 64 1
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.starts starts uint24 (>=0<=16777214) False sensor.boiler_dhw_starts sensor.boiler_dhw_starts 5 9 1 65 2
Greenstar HIU, Logamax kompakt WS170 boiler 219 dhw.workm active time time (>=0<=16777214) minutes False sensor.boiler_dhw_active_time sensor.boiler_dhw_workm 5 9 1 67 2
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 reset reset cmd [-|maintenance|error|history|message] True sensor.boiler_reset sensor.boiler_reset 5 0 1 0 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 heatingoff force heating off boolean True switch.boiler_force_heating_off switch.boiler_heatingoff 5 0 1 1 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 heatingactive heating active boolean False binary_sensor.boiler_heating_active binary_sensor.boiler_heatingactive 5 0 1 2 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 tapwateractive tapwater active boolean False binary_sensor.boiler_tapwater_active binary_sensor.boiler_tapwateractive 5 0 1 3 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 selflowtemp selected flow temperature uint8 (>=0<=90) C True number.boiler_selected_flow_temperature number.boiler_selflowtemp 5 0 1 4 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.boiler_heating_pump_modulation sensor.boiler_heatingpumpmod 5 0 1 5 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 outdoortemp outside temperature int16 (>=-3199<=3199) C False sensor.boiler_outside_temperature sensor.boiler_outdoortemp 5 0 1/10 6 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 curflowtemp current flow temperature uint16 (>=0<=3199) C False sensor.boiler_current_flow_temperature sensor.boiler_curflowtemp 5 0 1/10 7 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 rettemp return temperature uint16 (>=0<=3199) C False sensor.boiler_return_temperature sensor.boiler_rettemp 5 0 1/10 8 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 switchtemp mixing switch temperature uint16 (>=0<=3199) C False sensor.boiler_mixing_switch_temperature sensor.boiler_switchtemp 5 0 1/10 9 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 syspress system pressure uint8 (>=0<=25) bar False sensor.boiler_system_pressure sensor.boiler_syspress 5 0 1/10 10 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 boiltemp actual boiler temperature uint16 (>=0<=3199) C False sensor.boiler_actual_boiler_temperature sensor.boiler_boiltemp 5 0 1/10 11 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 headertemp low loss header uint16 (>=0<=3199) C False sensor.boiler_low_loss_header sensor.boiler_headertemp 5 0 1/10 12 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 exhausttemp exhaust temperature uint16 (>=0<=3199) C False sensor.boiler_exhaust_temperature sensor.boiler_exhausttemp 5 0 1/10 244 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 burngas gas boolean False binary_sensor.boiler_gas binary_sensor.boiler_burngas 5 0 1 245 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 burngas2 gas stage 2 boolean False binary_sensor.boiler_gas_stage_2 binary_sensor.boiler_burngas2 5 0 1 246 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 flamecurr flame current uint16 (>=0<=3199) µA False sensor.boiler_flame_current sensor.boiler_flamecurr 5 0 1/10 247 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 fanwork fan boolean False binary_sensor.boiler_fan binary_sensor.boiler_fanwork 5 0 1 248 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 ignwork ignition boolean False binary_sensor.boiler_ignition binary_sensor.boiler_ignwork 5 0 1 249 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 oilpreheat oil preheating boolean False binary_sensor.boiler_oil_preheating binary_sensor.boiler_oilpreheat 5 0 1 250 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 burnminpower burner min power uint8 (>=0<=100) % True number.boiler_burner_min_power number.boiler_burnminpower 5 0 1 251 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 burnmaxpower burner max power uint8 (>=0<=254) % True number.boiler_burner_max_power number.boiler_burnmaxpower 5 0 1 252 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 burnminperiod burner min period uint8 (>=0<=120) minutes True number.boiler_burner_min_period number.boiler_burnminperiod 5 0 1 253 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 absburnpow burner current power (absolute) uint8 (>=0<=100) % False sensor.boiler_burner_current_power_(absolute) sensor.boiler_absburnpow 5 0 1 254 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 heatblock heating block uint16 (>=0<=3199) C False sensor.boiler_heating_block sensor.boiler_heatblock 5 0 1/10 255 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 boilhyston hysteresis on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_on_temperature number.boiler_boilhyston 5 0 1 256 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 boilhystoff hysteresis off temperature int8 (>=0<=20) C True number.boiler_hysteresis_off_temperature number.boiler_boilhystoff 5 0 1 257 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 boil2hyston hysteresis stage 2 on temperature int8 (>=-20<=0) C True number.boiler_hysteresis_stage_2_on_temperature number.boiler_boil2hyston 5 0 1 258 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 boil2hystoff hysteresis stage 2 off temperature int8 (>=0<=20) C True number.boiler_hysteresis_stage_2_off_temperature number.boiler_boil2hystoff 5 0 1 259 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 curveon heatingcurve on boolean True switch.boiler_heatingcurve_on switch.boiler_curveon 5 0 1 260 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 curvebase heatingcurve base uint8 (>=20<=90) C True number.boiler_heatingcurve_base number.boiler_curvebase 5 0 1 261 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 curveend heatingcurve end uint8 (>=20<=90) C True number.boiler_heatingcurve_end number.boiler_curveend 5 0 1 262 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 summertemp summer temperature uint8 (>=0<=45) C True number.boiler_summer_temperature number.boiler_summertemp 5 0 1 263 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 nofrostmode nofrost mode boolean True switch.boiler_nofrost_mode switch.boiler_nofrostmode 5 0 1 264 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 nofrosttemp nofrost temperature uint8 (>=0<=10) C True number.boiler_nofrost_temperature number.boiler_nofrosttemp 5 0 1 265 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 heatingactivated heating activated boolean True switch.boiler_heating_activated switch.boiler_heatingactivated 5 0 1 13 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 heatingtemp heating temperature uint8 (>=0<=90) C True number.boiler_heating_temperature number.boiler_heatingtemp 5 0 1 14 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 heatingpump heating pump boolean False binary_sensor.boiler_heating_pump binary_sensor.boiler_heatingpump 5 0 1 15 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 pumpmodmax boiler pump max power uint8 (>=0<=100) % True number.boiler_boiler_pump_max_power number.boiler_pumpmodmax 5 0 1 16 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 pumpmodmin boiler pump min power uint8 (>=0<=100) % True number.boiler_boiler_pump_min_power number.boiler_pumpmodmin 5 0 1 17 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 pumpmode boiler pump mode enum [proportional|deltaP-1|deltaP-2|deltaP-3|deltaP-4] True select.boiler_boiler_pump_mode select.boiler_pumpmode 5 0 1 18 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 pumpcharacter boiler pump characteristic enum [proportional|150mbar|200mbar|250mbar|300mbar|350mbar|400mbar] True select.boiler_boiler_pump_characteristic select.boiler_pumpcharacter 5 0 1 19 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 pumpdelay pump delay uint8 (>=0<=60) minutes True number.boiler_pump_delay number.boiler_pumpdelay 5 0 1 20 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 pumpontemp pump logic temperature uint8 (>=0<=60) C True number.boiler_pump_logic_temperature number.boiler_pumpontemp 5 0 1 21 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 selburnpow burner selected max power uint8 (>=0<=254) % True number.boiler_burner_selected_max_power number.boiler_selburnpow 5 0 1 22 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 curburnpow burner current power uint8 (>=0<=100) % False sensor.boiler_burner_current_power sensor.boiler_curburnpow 5 0 1 23 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 burnstarts burner starts uint24 (>=0<=16777214) False sensor.boiler_burner_starts sensor.boiler_burnstarts 5 0 1 24 2
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 burnworkmin total burner operating time time (>=0<=16777214) minutes False sensor.boiler_total_burner_operating_time sensor.boiler_burnworkmin 5 0 1 26 2
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 burn2workmin burner stage 2 operating time time (>=0<=16777214) minutes False sensor.boiler_burner_stage_2_operating_time sensor.boiler_burn2workmin 5 0 1 28 2
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 heatworkmin total heat operating time time (>=0<=16777214) minutes False sensor.boiler_total_heat_operating_time sensor.boiler_heatworkmin 5 0 1 30 2
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 heatstarts burner starts heating uint24 (>=0<=16777214) False sensor.boiler_burner_starts_heating sensor.boiler_heatstarts 5 0 1 32 2
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 ubauptime total UBA operating time time (>=0<=16777214) minutes False sensor.boiler_total_UBA_operating_time sensor.boiler_ubauptime 5 0 1 34 2
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 lastcode last error code string False sensor.boiler_last_error_code sensor.boiler_lastcode 5 0 1 36 28
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 servicecode service code string False sensor.boiler_service_code sensor.boiler_servicecode 5 0 1 64 2
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 servicecodenumber service code number uint16 (>=0<=31999) False sensor.boiler_service_code_number sensor.boiler_servicecodenumber 5 0 1 66 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 maintenancemessage maintenance message string False sensor.boiler_maintenance_message sensor.boiler_maintenancemessage 5 0 1 67 2
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 maintenance maintenance scheduled enum [off|time|date|manual] True select.boiler_maintenance_scheduled select.boiler_maintenance 5 0 1 69 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 maintenancetime time to next maintenance uint16 (>=0<=31999) hours True number.boiler_time_to_next_maintenance number.boiler_maintenancetime 5 0 1 70 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 maintenancedate next maintenance date string True sensor.boiler_next_maintenance_date sensor.boiler_maintenancedate 5 0 1 71 6
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 emergencyops emergency operation boolean True switch.boiler_emergency_operation switch.boiler_emergencyops 5 0 1 77 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 emergencytemp emergency temperature uint8 (>=15<=70) C True number.boiler_emergency_temperature number.boiler_emergencytemp 5 0 1 78 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 pc0flow Flow PC0 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC0 sensor.boiler_pc0flow 5 0 1 79 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 pc1flow Flow PC1 int16 (>=-31999<=31999) l/h False sensor.boiler_Flow_PC1 sensor.boiler_pc1flow 5 0 1 80 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 pc1on PC1 boolean False binary_sensor.boiler_PC1 binary_sensor.boiler_pc1on 5 0 1 81 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 pc1rate PC1 rate uint8 (>=0<=100) % False sensor.boiler_PC1_rate sensor.boiler_pc1rate 5 0 1 82 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 meterheat meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_meter_heating sensor.boiler_meterheat 5 0 1/10 95 2
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.meter meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_meter sensor.boiler_dhw_meter 5 9 1/10 2 2
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 gasmeterheat gas meter heating uint24 (>=0<=1677721) kWh False sensor.boiler_gas_meter_heating sensor.boiler_gasmeterheat 5 0 1/10 266 2
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.gasmeter gas meter uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_gas_meter sensor.boiler_dhw_gasmeter 5 9 1/10 69 2
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 nrgheat2 energy heating 2 uint24 (>=0<=1677721) kWh False sensor.boiler_energy_heating_2 sensor.boiler_nrgheat2 5 0 1/10 268 2
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.nrg2 energy 2 uint24 (>=0<=1677721) kWh False sensor.boiler_dhw_energy_2 sensor.boiler_dhw_nrg2 5 9 1/10 71 2
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.tapactivated turn on/off boolean True switch.boiler_dhw_turn_on/off switch.boiler_dhw_tapactivated 5 9 1 28 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.settemp set temperature uint8 (>=0<=254) C False sensor.boiler_dhw_set_temperature sensor.boiler_dhw_settemp 5 9 1 29 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_temperature number.boiler_dhw_seltemp 5 9 1 30 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.seltemplow selected lower temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_lower_temperature number.boiler_dhw_seltemplow 5 9 1 31 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.tempecoplus selected eco+ temperature uint8 (>=0<=254) C True number.boiler_dhw_selected_eco+_temperature number.boiler_dhw_tempecoplus 5 9 1 32 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.seltempoff selected temperature for off uint8 (>=0<=254) C False sensor.boiler_dhw_selected_temperature_for_off sensor.boiler_dhw_seltempoff 5 9 1 33 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.seltempsingle single charge temperature uint8 (>=0<=254) C True number.boiler_dhw_single_charge_temperature number.boiler_dhw_seltempsingle 5 9 1 34 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.solartemp solar boiler temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_solar_boiler_temperature sensor.boiler_dhw_solartemp 5 9 1/10 35 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.type type enum [off|flow|buffered flow|buffer|layered buffer] False sensor.boiler_dhw_type sensor.boiler_dhw_type 5 9 1 36 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.comfort comfort enum [hot|eco|intelligent] True select.boiler_dhw_comfort select.boiler_dhw_comfort 5 9 1 37 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.comfort1 comfort mode enum [high comfort|eco] True select.boiler_dhw_comfort_mode select.boiler_dhw_comfort1 5 9 1 38 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.flowtempoffset flow temperature offset uint8 (>=0<=100) C True number.boiler_dhw_flow_temperature_offset number.boiler_dhw_flowtempoffset 5 9 1 39 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.chargeoptimization charge optimization boolean True switch.boiler_dhw_charge_optimization switch.boiler_dhw_chargeoptimization 5 9 1 40 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.maxpower max power uint8 (>=0<=254) % True number.boiler_dhw_max_power number.boiler_dhw_maxpower 5 9 1 41 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.maxtemp maximum temperature uint8 (>=0<=80) C True number.boiler_dhw_maximum_temperature number.boiler_dhw_maxtemp 5 9 1 42 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.circpump circulation pump available boolean True switch.boiler_dhw_circulation_pump_available switch.boiler_dhw_circpump 5 9 1 43 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.chargetype charging type enum [chargepump|3-way valve] False sensor.boiler_dhw_charging_type sensor.boiler_dhw_chargetype 5 9 1 44 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_on_temperature number.boiler_dhw_hyston 5 9 1 45 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.boiler_dhw_hysteresis_off_temperature number.boiler_dhw_hystoff 5 9 1 46 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.disinfectiontemp disinfection temperature uint8 (>=60<=80) C True number.boiler_dhw_disinfection_temperature number.boiler_dhw_disinfectiontemp 5 9 1 47 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.boiler_dhw_circulation_pump_mode select.boiler_dhw_circmode 5 9 1 48 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.circ circulation active boolean True switch.boiler_dhw_circulation_active switch.boiler_dhw_circ 5 9 1 49 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.curtemp current intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_intern_temperature sensor.boiler_dhw_curtemp 5 9 1/10 50 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_current_extern_temperature sensor.boiler_dhw_curtemp2 5 9 1/10 51 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.curflow current tap water flow uint8 (>=0<=25) l/min False sensor.boiler_dhw_current_tap_water_flow sensor.boiler_dhw_curflow 5 9 1/10 52 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_intern_temperature sensor.boiler_dhw_storagetemp1 5 9 1/10 53 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.storagetemp2 storage extern temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_storage_extern_temperature sensor.boiler_dhw_storagetemp2 5 9 1/10 54 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.activated activated boolean True switch.boiler_dhw_activated switch.boiler_dhw_activated 5 9 1 55 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.onetime one time charging boolean True switch.boiler_dhw_one_time_charging switch.boiler_dhw_onetime 5 9 1 56 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.disinfecting disinfecting boolean True switch.boiler_dhw_disinfecting switch.boiler_dhw_disinfecting 5 9 1 57 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.charging charging boolean False binary_sensor.boiler_dhw_charging binary_sensor.boiler_dhw_charging 5 9 1 58 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.recharging recharging boolean False binary_sensor.boiler_dhw_recharging binary_sensor.boiler_dhw_recharging 5 9 1 59 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.tempok temperature ok boolean False binary_sensor.boiler_dhw_temperature_ok binary_sensor.boiler_dhw_tempok 5 9 1 60 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.active active boolean False binary_sensor.boiler_dhw_active binary_sensor.boiler_dhw_active 5 9 1 61 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.3wayvalve 3-way valve active boolean False binary_sensor.boiler_dhw_3-way_valve_active binary_sensor.boiler_dhw_3wayvalve 5 9 1 62 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.mixertemp mixer temperature uint16 (>=0<=3199) C False sensor.boiler_dhw_mixer_temperature sensor.boiler_dhw_mixertemp 5 9 1/10 63 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.cylmiddletemp cylinder middle temperature (TS3) uint16 (>=0<=3199) C False sensor.boiler_dhw_cylinder_middle_temperature_(TS3) sensor.boiler_dhw_cylmiddletemp 5 9 1/10 64 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.starts starts uint24 (>=0<=16777214) False sensor.boiler_dhw_starts sensor.boiler_dhw_starts 5 9 1 65 2
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.workm active time time (>=0<=16777214) minutes False sensor.boiler_dhw_active_time sensor.boiler_dhw_workm 5 9 1 67 2
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 nompower nominal Power uint8 (>=0<=254) kW True number.boiler_nominal_Power number.boiler_nompower 5 0 1 270 1
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 nrgtotal total energy uint24 (>=0<=167772) kWh False sensor.boiler_total_energy sensor.boiler_nrgtotal 5 0 1/100 83 2
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 nrgheat energy heating uint24 (>=0<=10000000) kWh True number.boiler_energy_heating number.boiler_nrgheat 5 0 1/100 85 2
Logamax Plus GB122, Condense 2300, Junkers Cerapur GC2200W boiler 234 dhw.nrg energy uint24 (>=0<=10000000) kWh True number.boiler_dhw_energy number.boiler_dhw_nrg 5 9 1/100 0 2
Logamatic TC100, Moduline Easy thermostat 202 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
Logamatic TC100, Moduline Easy thermostat 202 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
Logamatic TC100, Moduline Easy thermostat 202 datetime date/time string False sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
Logamatic TC100, Moduline Easy thermostat 202 hc1.seltemp selected room temperature int16 (>=-319<=319) C False sensor.thermostat_hc1_selected_room_temperature sensor.thermostat_hc1_seltemp 6 1 1/100 0 1
Logamatic TC100, Moduline Easy thermostat 202 hc1.currtemp current room temperature int16 (>=-319<=319) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/100 1 1
Logamatic TC100, Moduline Easy thermostat 202 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
EasyControl, CT200 thermostat 203 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
EasyControl, CT200 thermostat 203 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
EasyControl, CT200 thermostat 203 datetime date/time string False sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
EasyControl, CT200 thermostat 203 hc1.seltemp selected room temperature int16 (>=-319<=319) C False sensor.thermostat_hc1_selected_room_temperature sensor.thermostat_hc1_seltemp 6 1 1/100 0 1
EasyControl, CT200 thermostat 203 hc1.currtemp current room temperature int16 (>=-319<=319) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/100 1 1
EasyControl, CT200 thermostat 203 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
UI800, BC400 thermostat 4 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
UI800, BC400 thermostat 4 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
UI800, BC400 thermostat 4 datetime date/time string True sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
UI800, BC400 thermostat 4 intoffset internal temperature offset int8 (>=-12<=12) C True number.thermostat_internal_temperature_offset number.thermostat_intoffset 6 0 1/10 46 1
UI800, BC400 thermostat 4 floordry floor drying enum [off|start|heat|hold|cool|end] False sensor.thermostat_floor_drying sensor.thermostat_floordry 6 0 1 47 1
UI800, BC400 thermostat 4 dampedoutdoortemp damped outdoor temperature int16 (>=-3199<=3199) C False sensor.thermostat_damped_outdoor_temperature sensor.thermostat_dampedoutdoortemp 6 0 1/10 48 1
UI800, BC400 thermostat 4 floordrytemp floor drying temperature uint8 (>=0<=254) C False sensor.thermostat_floor_drying_temperature sensor.thermostat_floordrytemp 6 0 1 49 1
UI800, BC400 thermostat 4 building building type enum [light|medium|heavy] True select.thermostat_building_type select.thermostat_building 6 0 1 50 1
UI800, BC400 thermostat 4 minexttemp minimal external temperature int8 (>=-126<=126) C True number.thermostat_minimal_external_temperature number.thermostat_minexttemp 6 0 1 51 1
UI800, BC400 thermostat 4 damping damping outdoor temperature boolean True switch.thermostat_damping_outdoor_temperature switch.thermostat_damping 6 0 1 52 1
UI800, BC400 thermostat 4 solar solar boolean True switch.thermostat_solar switch.thermostat_solar 6 0 1 53 1
UI800, BC400 thermostat 4 hybridstrategy hybrid control strategy enum [co2 optimized|cost optimized|outside temp switched|co2 cost mix] True select.thermostat_hybrid_control_strategy select.thermostat_hybridstrategy 6 0 1 54 1
UI800, BC400 thermostat 4 switchovertemp outside switchover temperature int8 (>=-20<=20) C True number.thermostat_outside_switchover_temperature number.thermostat_switchovertemp 6 0 1 55 1
UI800, BC400 thermostat 4 energycostratio energy cost ratio uint8 (>=0<=20) True number.thermostat_energy_cost_ratio number.thermostat_energycostratio 6 0 1/10 56 1
UI800, BC400 thermostat 4 fossilefactor fossile energy factor uint8 (>=0<=5) True number.thermostat_fossile_energy_factor number.thermostat_fossilefactor 6 0 1/10 57 1
UI800, BC400 thermostat 4 electricfactor electric energy factor uint8 (>=0<=5) True number.thermostat_electric_energy_factor number.thermostat_electricfactor 6 0 1/10 58 1
UI800, BC400 thermostat 4 delayboiler delay boiler support uint8 (>=5<=120) minutes True number.thermostat_delay_boiler_support number.thermostat_delayboiler 6 0 1 59 1
UI800, BC400 thermostat 4 tempdiffboiler temp diff boiler support uint8 (>=1<=99) C True number.thermostat_temp_diff_boiler_support number.thermostat_tempdiffboiler 6 0 1 60 1
UI800, BC400 thermostat 4 pvenabledhw enable raise dhw boolean True switch.thermostat_enable_raise_dhw switch.thermostat_pvenabledhw 6 0 1 61 1
UI800, BC400 thermostat 4 pvraiseheat raise heating with PV int8 (>=0<=5) K True number.thermostat_raise_heating_with_PV number.thermostat_pvraiseheat 6 0 1 62 1
UI800, BC400 thermostat 4 pvlowercool lower cooling with PV int8 (>=-5<=0) K True number.thermostat_lower_cooling_with_PV number.thermostat_pvlowercool 6 0 1 63 1
UI800, BC400 thermostat 4 absent absent boolean True switch.thermostat_absent switch.thermostat_absent 6 0 1 64 1
UI800, BC400 thermostat 4 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/2 0 1
UI800, BC400 thermostat 4 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
UI800, BC400 thermostat 4 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
UI800, BC400 thermostat 4 hc1.mode operating mode enum [off|manual|auto] True select.thermostat_hc1_operating_mode select.thermostat_hc1_mode 6 1 1 3 1
UI800, BC400 thermostat 4 hc1.modetype mode type enum [eco|comfort] False sensor.thermostat_hc1_mode_type sensor.thermostat_hc1_modetype 6 1 1 4 1
UI800, BC400 thermostat 4 hc1.ecotemp eco temperature uint8 (>=0<=127) C True number.thermostat_hc1_eco_temperature number.thermostat_hc1_ecotemp 6 1 1/2 5 1
UI800, BC400 thermostat 4 hc1.manualtemp manual temperature uint8 (>=0<=127) C True number.thermostat_hc1_manual_temperature number.thermostat_hc1_manualtemp 6 1 1/2 6 1
UI800, BC400 thermostat 4 hc1.comforttemp comfort temperature uint8 (>=0<=127) C True number.thermostat_hc1_comfort_temperature number.thermostat_hc1_comforttemp 6 1 1/2 7 1
UI800, BC400 thermostat 4 hc1.summertemp summer temperature uint8 (>=10<=30) C True number.thermostat_hc1_summer_temperature number.thermostat_hc1_summertemp 6 1 1 8 1
UI800, BC400 thermostat 4 hc1.designtemp design temperature uint8 (>=0<=254) C True number.thermostat_hc1_design_temperature number.thermostat_hc1_designtemp 6 1 1 9 1
UI800, BC400 thermostat 4 hc1.offsettemp offset temperature int8 (>=-126<=126) C True number.thermostat_hc1_offset_temperature number.thermostat_hc1_offsettemp 6 1 1 10 1
UI800, BC400 thermostat 4 hc1.minflowtemp min flow temperature uint8 (>=0<=254) C True number.thermostat_hc1_min_flow_temperature number.thermostat_hc1_minflowtemp 6 1 1 11 1
UI800, BC400 thermostat 4 hc1.maxflowtemp max flow temperature uint8 (>=0<=254) C True number.thermostat_hc1_max_flow_temperature number.thermostat_hc1_maxflowtemp 6 1 1 12 1
UI800, BC400 thermostat 4 hc1.roominfluence room influence uint8 (>=0<=254) C True number.thermostat_hc1_room_influence number.thermostat_hc1_roominfluence 6 1 1 13 1
UI800, BC400 thermostat 4 hc1.roominflfactor room influence factor uint8 (>=0<=25) True number.thermostat_hc1_room_influence_factor number.thermostat_hc1_roominflfactor 6 1 1/10 14 1
UI800, BC400 thermostat 4 hc1.curroominfl current room influence int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_influence sensor.thermostat_hc1_curroominfl 6 1 1/10 15 1
UI800, BC400 thermostat 4 hc1.nofrostmode nofrost mode enum [room|outdoor|room outdoor] True select.thermostat_hc1_nofrost_mode select.thermostat_hc1_nofrostmode 6 1 1 16 1
UI800, BC400 thermostat 4 hc1.nofrosttemp nofrost temperature int8 (>=-126<=126) C True number.thermostat_hc1_nofrost_temperature number.thermostat_hc1_nofrosttemp 6 1 1 17 1
UI800, BC400 thermostat 4 hc1.targetflowtemp target flow temperature uint8 (>=0<=254) C False sensor.thermostat_hc1_target_flow_temperature sensor.thermostat_hc1_targetflowtemp 6 1 1 18 1
UI800, BC400 thermostat 4 hc1.heatingtype heating type enum [off|radiator|convector|floor] True select.thermostat_hc1_heating_type select.thermostat_hc1_heatingtype 6 1 1 19 1
UI800, BC400 thermostat 4 hc1.summersetmode set summer mode enum [summer|auto|winter] True select.thermostat_hc1_set_summer_mode select.thermostat_hc1_summersetmode 6 1 1 20 1
UI800, BC400 thermostat 4 hc1.hpoperatingmode heatpump operating mode enum [off|auto|heating|cooling] True select.thermostat_hc1_heatpump_operating_mode select.thermostat_hc1_hpoperatingmode 6 1 1 21 1
UI800, BC400 thermostat 4 hc1.summermode summer mode enum [winter|summer] False sensor.thermostat_hc1_summer_mode sensor.thermostat_hc1_summermode 6 1 1 22 1
UI800, BC400 thermostat 4 hc1.hpoperatingstate heatpump operating state enum [heating|off|cooling] False sensor.thermostat_hc1_heatpump_operating_state sensor.thermostat_hc1_hpoperatingstate 6 1 1 23 1
UI800, BC400 thermostat 4 hc1.vacationmode vacation mode boolean False binary_sensor.thermostat_hc1_vacation_mode binary_sensor.thermostat_hc1_vacationmode 6 1 1 24 1
UI800, BC400 thermostat 4 hc1.controlmode control mode enum [weather compensated|outside basepoint|n/a|room|power|constant] True select.thermostat_hc1_control_mode select.thermostat_hc1_controlmode 6 1 1 25 1
UI800, BC400 thermostat 4 hc1.program program enum [prog 1|prog 2] True select.thermostat_hc1_program select.thermostat_hc1_program 6 1 1 26 1
UI800, BC400 thermostat 4 hc1.tempautotemp temporary set temperature automode int8 (>=-1<=30) C True number.thermostat_hc1_temporary_set_temperature_automode number.thermostat_hc1_tempautotemp 6 1 1/2 27 1
UI800, BC400 thermostat 4 hc1.cooltemp cooling temperature int8 (>=-1<=30) C True number.thermostat_hc1_cooling_temperature number.thermostat_hc1_cooltemp 6 1 1/2 28 1
UI800, BC400 thermostat 4 hc1.fastheatup fast heatup uint8 (>=0<=100) % True number.thermostat_hc1_fast_heatup number.thermostat_hc1_fastheatup 6 1 1 29 1
UI800, BC400 thermostat 4 hc1.switchonoptimization switch-on optimization boolean True switch.thermostat_hc1_switch-on_optimization switch.thermostat_hc1_switchonoptimization 6 1 1 30 1
UI800, BC400 thermostat 4 hc1.reducemode reduce mode enum [outdoor|room|reduce] True select.thermostat_hc1_reduce_mode select.thermostat_hc1_reducemode 6 1 1 31 1
UI800, BC400 thermostat 4 hc1.noreducetemp no reduce below temperature int8 (>=-126<=126) C True number.thermostat_hc1_no_reduce_below_temperature number.thermostat_hc1_noreducetemp 6 1 1 32 1
UI800, BC400 thermostat 4 hc1.reducetemp off/reduce switch temperature int8 (>=-126<=126) C True number.thermostat_hc1_off/reduce_switch_temperature number.thermostat_hc1_reducetemp 6 1 1 33 1
UI800, BC400 thermostat 4 hc1.dhwprio dhw priority boolean True switch.thermostat_hc1_dhw_priority switch.thermostat_hc1_dhwprio 6 1 1 34 1
UI800, BC400 thermostat 4 hc1.hpcooling hp cooling boolean True switch.thermostat_hc1_hp_cooling switch.thermostat_hc1_hpcooling 6 1 1 35 1
UI800, BC400 thermostat 4 hc1.coolingon cooling on boolean False binary_sensor.thermostat_hc1_cooling_on binary_sensor.thermostat_hc1_coolingon 6 1 1 36 1
UI800, BC400 thermostat 4 hc1.hpmode HP Mode enum [heating|cooling|heating & cooling] True select.thermostat_hc1_HP_Mode select.thermostat_hc1_hpmode 6 1 1 37 1
UI800, BC400 thermostat 4 hc1.dewoffset dew point offset uint8 (>=2<=10) K True number.thermostat_hc1_dew_point_offset number.thermostat_hc1_dewoffset 6 1 1 38 1
UI800, BC400 thermostat 4 hc1.roomtempdiff room temp difference uint8 (>=0<=254) K True number.thermostat_hc1_room_temp_difference number.thermostat_hc1_roomtempdiff 6 1 1 39 1
UI800, BC400 thermostat 4 hc1.hpminflowtemp HP min. flow temp. uint8 (>=0<=254) C True number.thermostat_hc1_HP_min._flow_temp. number.thermostat_hc1_hpminflowtemp 6 1 1 40 1
UI800, BC400 thermostat 4 hc1.control control device enum [off|-|RC100|RC100H|-|RC120RF|RC220/RT800|single] True select.thermostat_hc1_control_device select.thermostat_hc1_control 6 1 1 41 1
UI800, BC400 thermostat 4 hc1.remotetemp room temperature from remote cmd [] (>=-1<=101) C True sensor.thermostat_hc1_room_temperature_from_remote sensor.thermostat_hc1_remotetemp 6 1 1/10 42 1
UI800, BC400 thermostat 4 hc1.remotehum room humidity from remote cmd [] (>=-1<=101) % True sensor.thermostat_hc1_room_humidity_from_remote sensor.thermostat_hc1_remotehum 6 1 1 43 1
UI800, BC400 thermostat 4 hc1.heatondelay heat-on delay uint8 (>=1<=48) hours True number.thermostat_hc1_heat-on_delay number.thermostat_hc1_heatondelay 6 1 1 44 1
UI800, BC400 thermostat 4 hc1.heatoffdelay heat-off delay uint8 (>=1<=48) hours True number.thermostat_hc1_heat-off_delay number.thermostat_hc1_heatoffdelay 6 1 1 45 1
UI800, BC400 thermostat 4 hc1.instantstart instant start uint8 (>=1<=10) K True number.thermostat_hc1_instant_start number.thermostat_hc1_instantstart 6 1 1 46 1
UI800, BC400 thermostat 4 hc1.boost boost mode boolean True switch.thermostat_hc1_boost_mode switch.thermostat_hc1_boost 6 1 1 47 1
UI800, BC400 thermostat 4 hc1.boosttime boost time uint8 (>=0<=254) hours True number.thermostat_hc1_boost_time number.thermostat_hc1_boosttime 6 1 1 48 1
UI800, BC400 thermostat 4 hc1.coolstart cooling starttemp uint8 (>=20<=35) C True number.thermostat_hc1_cooling_starttemp number.thermostat_hc1_coolstart 6 1 1 49 1
UI800, BC400 thermostat 4 hc1.coolondelay cooling on delay uint8 (>=1<=48) hours True number.thermostat_hc1_cooling_on_delay number.thermostat_hc1_coolondelay 6 1 1 50 1
UI800, BC400 thermostat 4 hc1.cooloffdelay cooling off delay uint8 (>=1<=48) hours True number.thermostat_hc1_cooling_off_delay number.thermostat_hc1_cooloffdelay 6 1 1 51 1
UI800, BC400 thermostat 4 hc1.switchprogmode switch program mode enum [level|absolute] True select.thermostat_hc1_switch_program_mode select.thermostat_hc1_switchprogmode 6 1 1 52 1
UI800, BC400 thermostat 4 hc1.redthreshold reduction threshold int8 (>=12<=22) C True number.thermostat_hc1_reduction_threshold number.thermostat_hc1_redthreshold 6 1 1/2 53 1
UI800, BC400 thermostat 4 hc1.solarinfl solar influence uint8 (>=-5<=4294967295) C True number.thermostat_hc1_solar_influence number.thermostat_hc1_solarinfl 6 1 1 54 1
UI800, BC400 thermostat 4 hc1.currsolarinfl curent solar influence uint8 (>=0<=25) C False sensor.thermostat_hc1_curent_solar_influence sensor.thermostat_hc1_currsolarinfl 6 1 1/10 55 1
UI800, BC400 thermostat 4 dhw.mode operating mode enum [off|eco+|eco|comfort|auto] True select.thermostat_dhw_operating_mode select.thermostat_dhw_mode 6 9 1 0 1
UI800, BC400 thermostat 4 dhw.settemp set temperature uint8 (>=0<=254) C True number.thermostat_dhw_set_temperature number.thermostat_dhw_settemp 6 9 1 1 1
UI800, BC400 thermostat 4 dhw.settemplow set low temperature uint8 (>=0<=254) C True number.thermostat_dhw_set_low_temperature number.thermostat_dhw_settemplow 6 9 1 2 1
UI800, BC400 thermostat 4 dhw.circmode circulation pump mode enum [off|on|auto|own prog] True select.thermostat_dhw_circulation_pump_mode select.thermostat_dhw_circmode 6 9 1 3 1
UI800, BC400 thermostat 4 dhw.chargeduration charge duration uint8 (>=0<=3810) minutes True number.thermostat_dhw_charge_duration number.thermostat_dhw_chargeduration 6 9 15 4 1
UI800, BC400 thermostat 4 dhw.charge charge boolean True switch.thermostat_dhw_charge switch.thermostat_dhw_charge 6 9 1 5 1
UI800, BC400 thermostat 4 dhw.extra extra boolean False binary_sensor.thermostat_dhw_extra binary_sensor.thermostat_dhw_extra 6 9 1 6 1
UI800, BC400 thermostat 4 dhw.disinfecting disinfecting boolean True switch.thermostat_dhw_disinfecting switch.thermostat_dhw_disinfecting 6 9 1 7 1
UI800, BC400 thermostat 4 dhw.disinfectday disinfection day enum [mo|tu|we|th|fr|sa|su|all] True select.thermostat_dhw_disinfection_day select.thermostat_dhw_disinfectday 6 9 1 8 1
UI800, BC400 thermostat 4 dhw.disinfecttime disinfection time uint8 (>=0<=1431) minutes True number.thermostat_dhw_disinfection_time number.thermostat_dhw_disinfecttime 6 9 15 9 1
UI800, BC400 thermostat 4 dhw.dailyheating daily heating boolean True switch.thermostat_dhw_daily_heating switch.thermostat_dhw_dailyheating 6 9 1 10 1
UI800, BC400 thermostat 4 dhw.dailyheattime daily heating time uint8 (>=0<=1431) minutes True number.thermostat_dhw_daily_heating_time number.thermostat_dhw_dailyheattime 6 9 15 11 1
CR11 thermostat 10 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
CR11 thermostat 10 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
CR11 thermostat 10 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/2 0 1
CR11 thermostat 10 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
CR11 thermostat 10 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
CR11 thermostat 10 hc1.mode operating mode enum [manual|auto] False sensor.thermostat_hc1_operating_mode sensor.thermostat_hc1_mode 6 1 1 3 1
CR11 thermostat 10 hc1.targetflowtemp target flow temperature uint8 (>=0<=254) C False sensor.thermostat_hc1_target_flow_temperature sensor.thermostat_hc1_targetflowtemp 6 1 1 18 1
CR11 thermostat 10 hc1.heatingtype heating type enum [off|radiator|convector|floor] True select.thermostat_hc1_heating_type select.thermostat_hc1_heatingtype 6 1 1 19 1
RC10 thermostat 65 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
RC10 thermostat 65 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
RC10 thermostat 65 datetime date/time string False sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
RC10 thermostat 65 minexttemp minimal external temperature int8 (>=-126<=126) C True number.thermostat_minimal_external_temperature number.thermostat_minexttemp 6 0 1 51 1
RC10 thermostat 65 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/2 0 1
RC10 thermostat 65 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
RC10 thermostat 65 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
RC10 thermostat 65 hc1.mode operating mode enum [night|day|auto] True select.thermostat_hc1_operating_mode select.thermostat_hc1_mode 6 1 1 3 1
RC10 thermostat 65 hc1.modetype mode type enum [night|day] False sensor.thermostat_hc1_mode_type sensor.thermostat_hc1_modetype 6 1 1 4 1
RC10 thermostat 65 hc1.daytemp day temperature uint8 (>=0<=127) C True number.thermostat_hc1_day_temperature number.thermostat_hc1_daytemp 6 1 1/2 56 1
RC10 thermostat 65 hc1.nighttemp night temperature uint8 (>=0<=127) C True number.thermostat_hc1_night_temperature number.thermostat_hc1_nighttemp 6 1 1/2 57 1
RC10 thermostat 65 hc1.program program enum [family|morning|evening|am|pm|midday|singles|seniors] True select.thermostat_hc1_program select.thermostat_hc1_program 6 1 1 26 1
RC10 thermostat 65 hc1.minflowtemp min flow temperature uint8 (>=0<=254) C True number.thermostat_hc1_min_flow_temperature number.thermostat_hc1_minflowtemp 6 1 1 11 1
RC10 thermostat 65 hc1.maxflowtemp max flow temperature uint8 (>=0<=254) C True number.thermostat_hc1_max_flow_temperature number.thermostat_hc1_maxflowtemp 6 1 1 12 1
RC10 thermostat 65 hc1.tempautotemp temporary set temperature automode uint8 (>=0<=127) C True number.thermostat_hc1_temporary_set_temperature_automode number.thermostat_hc1_tempautotemp 6 1 1/2 27 1
RC10 thermostat 65 hc1.heatingtype heating type enum [off|radiator|convector|floor] True select.thermostat_hc1_heating_type select.thermostat_hc1_heatingtype 6 1 1 19 1
RC10 thermostat 65 hc1.summertemp summer temperature uint8 (>=10<=30) C True number.thermostat_hc1_summer_temperature number.thermostat_hc1_summertemp 6 1 1 8 1
RC10 thermostat 65 hc1.summermode summer mode enum [winter|summer] False sensor.thermostat_hc1_summer_mode sensor.thermostat_hc1_summermode 6 1 1 22 1
RC30 thermostat 67 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
RC30 thermostat 67 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
RC30 thermostat 67 datetime date/time string False sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
RC30 thermostat 67 display display enum [internal temperature|internal setpoint|external temperature|burner temperature|dhw temperature|functioning mode|time|date|smoke temperature] True select.thermostat_display select.thermostat_display 6 0 1 65 1
RC30 thermostat 67 language language enum [german|dutch|french|italian] False sensor.thermostat_language sensor.thermostat_language 6 0 1 66 1
RC30 thermostat 67 clockoffset clock offset int8 (>=-126<=126) seconds True number.thermostat_clock_offset number.thermostat_clockoffset 6 0 1 67 1
RC30 thermostat 67 intoffset internal temperature offset int8 (>=-12<=12) C True number.thermostat_internal_temperature_offset number.thermostat_intoffset 6 0 1/10 46 1
RC30 thermostat 67 minexttemp minimal external temperature int8 (>=-126<=126) C True number.thermostat_minimal_external_temperature number.thermostat_minexttemp 6 0 1 51 1
RC30 thermostat 67 inttemp1 temperature sensor 1 int16 (>=-3199<=3199) C False sensor.thermostat_temperature_sensor_1 sensor.thermostat_inttemp1 6 0 1/10 68 1
RC30 thermostat 67 inttemp2 temperature sensor 2 int16 (>=-3199<=3199) C False sensor.thermostat_temperature_sensor_2 sensor.thermostat_inttemp2 6 0 1/10 69 1
RC30 thermostat 67 damping damping outdoor temperature boolean True switch.thermostat_damping_outdoor_temperature switch.thermostat_damping 6 0 1 52 1
RC30 thermostat 67 dampedoutdoortemp damped outdoor temperature int8 (>=-126<=126) C False sensor.thermostat_damped_outdoor_temperature sensor.thermostat_dampedoutdoortemp 6 0 1 48 1
RC30 thermostat 67 building building type enum [light|medium|heavy] True select.thermostat_building_type select.thermostat_building 6 0 1 50 1
RC30 thermostat 67 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/2 0 1
RC30 thermostat 67 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
RC30 thermostat 67 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
RC30 thermostat 67 hc1.mode operating mode enum [night|day|auto] True select.thermostat_hc1_operating_mode select.thermostat_hc1_mode 6 1 1 3 1
RC30 thermostat 67 hc1.modetype mode type enum [night|day] False sensor.thermostat_hc1_mode_type sensor.thermostat_hc1_modetype 6 1 1 4 1
RC30 thermostat 67 hc1.daytemp day temperature uint8 (>=10<=30) C True number.thermostat_hc1_day_temperature number.thermostat_hc1_daytemp 6 1 1/2 56 1
RC30 thermostat 67 hc1.nighttemp night temperature uint8 (>=10<=30) C True number.thermostat_hc1_night_temperature number.thermostat_hc1_nighttemp 6 1 1/2 57 1
RC30 thermostat 67 hc1.designtemp design temperature uint8 (>=30<=90) C True number.thermostat_hc1_design_temperature number.thermostat_hc1_designtemp 6 1 1 9 1
RC30 thermostat 67 hc1.offsettemp offset temperature int8 (>=-5<=5) C True number.thermostat_hc1_offset_temperature number.thermostat_hc1_offsettemp 6 1 1/2 10 1
RC30 thermostat 67 hc1.holidaytemp holiday temperature uint8 (>=5<=30) C True number.thermostat_hc1_holiday_temperature number.thermostat_hc1_holidaytemp 6 1 1/2 58 1
RC30 thermostat 67 hc1.targetflowtemp target flow temperature uint8 (>=0<=254) C False sensor.thermostat_hc1_target_flow_temperature sensor.thermostat_hc1_targetflowtemp 6 1 1 18 1
RC30 thermostat 67 hc1.summertemp summer temperature uint8 (>=9<=25) C True number.thermostat_hc1_summer_temperature number.thermostat_hc1_summertemp 6 1 1 8 1
RC30 thermostat 67 hc1.summermode summer mode enum [winter|summer] False sensor.thermostat_hc1_summer_mode sensor.thermostat_hc1_summermode 6 1 1 22 1
RC30 thermostat 67 hc1.holidaymode holiday mode boolean False binary_sensor.thermostat_hc1_holiday_mode binary_sensor.thermostat_hc1_holidaymode 6 1 1 59 1
RC30 thermostat 67 hc1.nofrosttemp nofrost temperature int8 (>=-20<=10) C True number.thermostat_hc1_nofrost_temperature number.thermostat_hc1_nofrosttemp 6 1 1 17 1
RC30 thermostat 67 hc1.nofrostmode nofrost mode enum [off|outdoor|room] True select.thermostat_hc1_nofrost_mode select.thermostat_hc1_nofrostmode 6 1 1 16 1
RC30 thermostat 67 hc1.roominfluence room influence uint8 (>=0<=10) C True number.thermostat_hc1_room_influence number.thermostat_hc1_roominfluence 6 1 1 13 1
RC30 thermostat 67 hc1.minflowtemp min flow temperature uint8 (>=5<=70) C True number.thermostat_hc1_min_flow_temperature number.thermostat_hc1_minflowtemp 6 1 1 11 1
RC30 thermostat 67 hc1.maxflowtemp max flow temperature uint8 (>=30<=90) C True number.thermostat_hc1_max_flow_temperature number.thermostat_hc1_maxflowtemp 6 1 1 12 1
RC30 thermostat 67 hc1.flowtempoffset flow temperature offset for mixer uint8 (>=0<=20) C True number.thermostat_hc1_flow_temperature_offset_for_mixer number.thermostat_hc1_flowtempoffset 6 1 1 60 1
RC30 thermostat 67 hc1.heatingtype heating type enum [off|radiator|convector|floor] True select.thermostat_hc1_heating_type select.thermostat_hc1_heatingtype 6 1 1 19 1
RC30 thermostat 67 hc1.reducemode reduce mode enum [nofrost|reduce|room|outdoor] True select.thermostat_hc1_reduce_mode select.thermostat_hc1_reducemode 6 1 1 31 1
RC30 thermostat 67 hc1.controlmode control mode enum [outdoor|room] True select.thermostat_hc1_control_mode select.thermostat_hc1_controlmode 6 1 1 25 1
RC30 thermostat 67 hc1.control control device enum [off|RC20|RC3x] True select.thermostat_hc1_control_device select.thermostat_hc1_control 6 1 1 41 1
RC30 thermostat 67 hc1.holidays holiday dates string True sensor.thermostat_hc1_holiday_dates sensor.thermostat_hc1_holidays 6 1 1 61 13
RC30 thermostat 67 hc1.vacations vacation dates string True sensor.thermostat_hc1_vacation_dates sensor.thermostat_hc1_vacations 6 1 1 74 13
RC30 thermostat 67 hc1.program program enum [own 1|family|morning|evening|am|pm|midday|singles|seniors|new|own 2] True select.thermostat_hc1_program select.thermostat_hc1_program 6 1 1 26 1
RC30 thermostat 67 hc1.pause pause time uint8 (>=0<=99) hours True number.thermostat_hc1_pause_time number.thermostat_hc1_pause 6 1 1 87 1
RC30 thermostat 67 hc1.party party time uint8 (>=0<=99) hours True number.thermostat_hc1_party_time number.thermostat_hc1_party 6 1 1 88 1
RC30 thermostat 67 hc1.tempautotemp temporary set temperature automode uint8 (>=0<=30) C True number.thermostat_hc1_temporary_set_temperature_automode number.thermostat_hc1_tempautotemp 6 1 1/2 27 1
RC30 thermostat 67 hc1.noreducetemp no reduce below temperature int8 (>=-31<=10) C True number.thermostat_hc1_no_reduce_below_temperature number.thermostat_hc1_noreducetemp 6 1 1 32 1
RC30 thermostat 67 hc1.reducetemp off/reduce switch temperature int8 (>=-20<=10) C True number.thermostat_hc1_off/reduce_switch_temperature number.thermostat_hc1_reducetemp 6 1 1 33 1
RC30 thermostat 67 hc1.vacreducetemp vacations off/reduce switch temperature int8 (>=-20<=10) C True number.thermostat_hc1_vacations_off/reduce_switch_temperature number.thermostat_hc1_vacreducetemp 6 1 1 89 1
RC30 thermostat 67 hc1.vacreducemode vacations reduce mode enum [nofrost|reduce|room|outdoor] True select.thermostat_hc1_vacations_reduce_mode select.thermostat_hc1_vacreducemode 6 1 1 90 1
RC30 thermostat 67 hc1.remotetemp room temperature from remote cmd [] (>=-1<=101) C True sensor.thermostat_hc1_room_temperature_from_remote sensor.thermostat_hc1_remotetemp 6 1 1/10 42 1
RC30 thermostat 67 hc1.dhwprio dhw priority boolean True switch.thermostat_hc1_dhw_priority switch.thermostat_hc1_dhwprio 6 1 1 34 1
RC30 thermostat 67 hc1.switchonoptimization switch-on optimization boolean True switch.thermostat_hc1_switch-on_optimization switch.thermostat_hc1_switchonoptimization 6 1 1 30 1
RC30 thermostat 67 hc1.switchtime1 own1 program switchtime string True sensor.thermostat_hc1_own1_program_switchtime sensor.thermostat_hc1_switchtime1 6 1 1 91 8
RC30 thermostat 67 hc1.switchtime2 own2 program switchtime string True sensor.thermostat_hc1_own2_program_switchtime sensor.thermostat_hc1_switchtime2 6 1 1 99 8
RC30 thermostat 67 dhw.mode operating mode enum [off|on|auto] True select.thermostat_dhw_operating_mode select.thermostat_dhw_mode 6 9 1 0 1
RC30 thermostat 67 dhw.circmode circulation pump mode enum [off|on|auto] True select.thermostat_dhw_circulation_pump_mode select.thermostat_dhw_circmode 6 9 1 3 1
RC30 thermostat 67 dhw.progmode program enum [std prog|own prog] True select.thermostat_dhw_program select.thermostat_dhw_progmode 6 9 1 12 1
RC30 thermostat 67 dhw.circprog circulation program enum [std prog|own prog] True select.thermostat_dhw_circulation_program select.thermostat_dhw_circprog 6 9 1 13 1
RC30 thermostat 67 dhw.disinfecting disinfecting boolean True switch.thermostat_dhw_disinfecting switch.thermostat_dhw_disinfecting 6 9 1 7 1
RC30 thermostat 67 dhw.disinfectday disinfection day enum [mo|tu|we|th|fr|sa|su|all] True select.thermostat_dhw_disinfection_day select.thermostat_dhw_disinfectday 6 9 1 8 1
RC30 thermostat 67 dhw.disinfecthour disinfection hour uint8 (>=0<=23) True number.thermostat_dhw_disinfection_hour number.thermostat_dhw_disinfecthour 6 9 1 14 1
RC30 thermostat 67 dhw.maxtemp maximum temperature uint8 (>=0<=254) C True number.thermostat_dhw_maximum_temperature number.thermostat_dhw_maxtemp 6 9 1 15 1
RC30 thermostat 67 dhw.onetimekey one time key function boolean True switch.thermostat_dhw_one_time_key_function switch.thermostat_dhw_onetimekey 6 9 1 16 1
RC30 thermostat 67 dhw.switchtime program switchtime string True sensor.thermostat_dhw_program_switchtime sensor.thermostat_dhw_switchtime 6 9 1 17 8
RC30 thermostat 67 dhw.circswitchtime circulation program switchtime string True sensor.thermostat_dhw_circulation_program_switchtime sensor.thermostat_dhw_circswitchtime 6 9 1 25 8
RC30 thermostat 67 dhw.holidays holiday dates string True sensor.thermostat_dhw_holiday_dates sensor.thermostat_dhw_holidays 6 9 1 33 13
RC30 thermostat 67 dhw.vacations vacation dates string True sensor.thermostat_dhw_vacation_dates sensor.thermostat_dhw_vacations 6 9 1 46 13
RC20, Moduline 300 thermostat 77 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
RC20, Moduline 300 thermostat 77 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
RC20, Moduline 300 thermostat 77 datetime date/time string False sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
RC20, Moduline 300 thermostat 77 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/2 0 1
RC20, Moduline 300 thermostat 77 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
RC20, Moduline 300 thermostat 77 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
RC20, Moduline 300 thermostat 77 hc1.mode operating mode enum [off|manual|auto] True select.thermostat_hc1_operating_mode select.thermostat_hc1_mode 6 1 1 3 1
RC20, Moduline 300 thermostat 77 hc1.manualtemp manual temperature uint8 (>=0<=127) C True number.thermostat_hc1_manual_temperature number.thermostat_hc1_manualtemp 6 1 1/2 6 1
RC20, Moduline 300 thermostat 77 hc1.offtemp temperature when mode is off uint8 (>=0<=127) C True number.thermostat_hc1_temperature_when_mode_is_off number.thermostat_hc1_offtemp 6 1 1/2 107 1
RC20, Moduline 300 thermostat 77 hc1.daytemp2 day temperature T2 uint8 (>=0<=127) C True number.thermostat_hc1_day_temperature_T2 number.thermostat_hc1_daytemp2 6 1 1/2 108 1
RC20, Moduline 300 thermostat 77 hc1.daytemp3 day temperature T3 uint8 (>=0<=127) C True number.thermostat_hc1_day_temperature_T3 number.thermostat_hc1_daytemp3 6 1 1/2 109 1
RC20, Moduline 300 thermostat 77 hc1.daytemp4 day temperature T4 uint8 (>=0<=127) C True number.thermostat_hc1_day_temperature_T4 number.thermostat_hc1_daytemp4 6 1 1/2 110 1
RC20, Moduline 300 thermostat 77 hc1.nighttemp night temperature T1 uint8 (>=0<=127) C True number.thermostat_hc1_night_temperature_T1 number.thermostat_hc1_nighttemp 6 1 1/2 57 1
RC20, Moduline 300 thermostat 77 hc1.switchtime program switchtime string True sensor.thermostat_hc1_program_switchtime sensor.thermostat_hc1_switchtime 6 1 1 111 8
Moduline 400 thermostat 78 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
Moduline 400 thermostat 78 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
Moduline 400 thermostat 78 datetime date/time string False sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
Moduline 400 thermostat 78 clockoffset clock offset int8 (>=-126<=126) seconds True number.thermostat_clock_offset number.thermostat_clockoffset 6 0 1 67 1
Moduline 400 thermostat 78 autodst automatic change daylight saving time boolean True switch.thermostat_automatic_change_daylight_saving_time switch.thermostat_autodst 6 0 1 70 1
Moduline 400 thermostat 78 language language enum [german|dutch] True select.thermostat_language select.thermostat_language 6 0 1 66 1
Moduline 400 thermostat 78 backlight key backlight boolean True switch.thermostat_key_backlight switch.thermostat_backlight 6 0 1 71 1
Moduline 400 thermostat 78 brightness screen brightness int8 (>=-15<=15) True number.thermostat_screen_brightness number.thermostat_brightness 6 0 1 72 1
Moduline 400 thermostat 78 mixingvalves mixing valves uint8 (>=0<=2) True number.thermostat_mixing_valves number.thermostat_mixingvalves 6 0 1 73 1
Moduline 400 thermostat 78 building building type enum [light|medium|heavy] True select.thermostat_building_type select.thermostat_building 6 0 1 50 1
Moduline 400 thermostat 78 heatingpid heating PID enum [fast|medium|slow] True select.thermostat_heating_PID select.thermostat_heatingpid 6 0 1 74 1
Moduline 400 thermostat 78 preheating preheating in the clock program boolean True switch.thermostat_preheating_in_the_clock_program switch.thermostat_preheating 6 0 1 75 1
Moduline 400 thermostat 78 intoffset internal temperature offset int8 (>=-12<=12) C True number.thermostat_internal_temperature_offset number.thermostat_intoffset 6 0 1/10 46 1
Moduline 400 thermostat 78 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/2 0 1
Moduline 400 thermostat 78 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
Moduline 400 thermostat 78 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
Moduline 400 thermostat 78 hc1.mode operating mode enum [off|manual|auto] True select.thermostat_hc1_operating_mode select.thermostat_hc1_mode 6 1 1 3 1
Moduline 400 thermostat 78 hc1.pause pause time uint8 (>=0<=254) hours True number.thermostat_hc1_pause_time number.thermostat_hc1_pause 6 1 1 87 1
Moduline 400 thermostat 78 hc1.party party time uint8 (>=0<=254) hours True number.thermostat_hc1_party_time number.thermostat_hc1_party 6 1 1 88 1
Moduline 400 thermostat 78 hc1.vacations1 vacation dates 1 string True sensor.thermostat_hc1_vacation_dates_1 sensor.thermostat_hc1_vacations1 6 1 1 119 11
Moduline 400 thermostat 78 hc1.vacations2 vacation dates 2 string True sensor.thermostat_hc1_vacation_dates_2 sensor.thermostat_hc1_vacations2 6 1 1 130 11
Moduline 400 thermostat 78 hc1.vacations3 vacation dates 3 string True sensor.thermostat_hc1_vacation_dates_3 sensor.thermostat_hc1_vacations3 6 1 1 141 11
Moduline 400 thermostat 78 hc1.vacations4 vacation dates 4 string True sensor.thermostat_hc1_vacation_dates_4 sensor.thermostat_hc1_vacations4 6 1 1 152 11
Moduline 400 thermostat 78 hc1.vacations5 vacation dates 5 string True sensor.thermostat_hc1_vacation_dates_5 sensor.thermostat_hc1_vacations5 6 1 1 163 11
Moduline 400 thermostat 78 hc1.vacations6 vacation dates 6 string True sensor.thermostat_hc1_vacation_dates_6 sensor.thermostat_hc1_vacations6 6 1 1 174 11
Moduline 400 thermostat 78 hc1.vacations7 vacation dates 7 string True sensor.thermostat_hc1_vacation_dates_7 sensor.thermostat_hc1_vacations7 6 1 1 185 11
Moduline 400 thermostat 78 hc1.program program enum [own 1|family|morning|evening|am|pm|midday|singles|seniors|new|own 2] True select.thermostat_hc1_program select.thermostat_hc1_program 6 1 1 26 1
Moduline 400 thermostat 78 hc1.switchtime1 own1 program switchtime string True sensor.thermostat_hc1_own1_program_switchtime sensor.thermostat_hc1_switchtime1 6 1 1 91 8
Moduline 400 thermostat 78 hc1.heatingtype heating type enum [off|radiator|convector|floor] True select.thermostat_hc1_heating_type select.thermostat_hc1_heatingtype 6 1 1 19 1
Moduline 400 thermostat 78 hc1.controlmode control mode enum [outdoor|room] True select.thermostat_hc1_control_mode select.thermostat_hc1_controlmode 6 1 1 25 1
Moduline 400 thermostat 78 hc1.holidaytemp holiday temperature uint8 (>=0<=127) C True number.thermostat_hc1_holiday_temperature number.thermostat_hc1_holidaytemp 6 1 1/2 58 1
Moduline 400 thermostat 78 hc1.nighttemp night temperature T1 uint8 (>=0<=127) C True number.thermostat_hc1_night_temperature_T1 number.thermostat_hc1_nighttemp 6 1 1/2 57 1
Moduline 400 thermostat 78 hc1.daytemp2 day temperature T2 uint8 (>=0<=127) C True number.thermostat_hc1_day_temperature_T2 number.thermostat_hc1_daytemp2 6 1 1/2 108 1
Moduline 400 thermostat 78 hc1.daytemp3 day temperature T3 uint8 (>=0<=127) C True number.thermostat_hc1_day_temperature_T3 number.thermostat_hc1_daytemp3 6 1 1/2 109 1
Moduline 400 thermostat 78 hc1.daytemp4 day temperature T4 uint8 (>=0<=127) C True number.thermostat_hc1_day_temperature_T4 number.thermostat_hc1_daytemp4 6 1 1/2 110 1
Moduline 400 thermostat 78 hc1.manualtemp manual temperature uint8 (>=0<=127) C True number.thermostat_hc1_manual_temperature number.thermostat_hc1_manualtemp 6 1 1/2 6 1
Moduline 400 thermostat 78 hc1.offtemp temperature when mode is off uint8 (>=0<=127) C True number.thermostat_hc1_temperature_when_mode_is_off number.thermostat_hc1_offtemp 6 1 1/2 107 1
Moduline 400 thermostat 78 dhw.mode operating mode enum [on|off|auto] True select.thermostat_dhw_operating_mode select.thermostat_dhw_mode 6 9 1 0 1
Moduline 400 thermostat 78 dhw.whenmodeoff when thermostat mode off boolean True switch.thermostat_dhw_when_thermostat_mode_off switch.thermostat_dhw_whenmodeoff 6 9 1 59 1
Moduline 400 thermostat 78 dhw.disinfecting disinfecting boolean True switch.thermostat_dhw_disinfecting switch.thermostat_dhw_disinfecting 6 9 1 7 1
Moduline 400 thermostat 78 dhw.disinfectday disinfection day enum [mo|tu|we|th|fr|sa|su|all] True select.thermostat_dhw_disinfection_day select.thermostat_dhw_disinfectday 6 9 1 8 1
Moduline 400 thermostat 78 dhw.disinfecthour disinfection hour uint8 (>=0<=23) True number.thermostat_dhw_disinfection_hour number.thermostat_dhw_disinfecthour 6 9 1 14 1
RC10, Moduline 100 thermostat 79 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
RC10, Moduline 100 thermostat 79 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
RC10, Moduline 100 thermostat 79 intoffset internal temperature offset int8 (>=-12<=12) C True number.thermostat_internal_temperature_offset number.thermostat_intoffset 6 0 1/10 46 1
RC10, Moduline 100 thermostat 79 heatingpid heating PID enum [fast|medium|slow] True select.thermostat_heating_PID select.thermostat_heatingpid 6 0 1 74 1
RC10, Moduline 100 thermostat 79 backlight key backlight boolean True switch.thermostat_key_backlight switch.thermostat_backlight 6 0 1 71 1
RC10, Moduline 100 thermostat 79 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/2 0 1
RC10, Moduline 100 thermostat 79 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
RC10, Moduline 100 thermostat 79 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
RC10, Moduline 100 thermostat 79 hc1.mode operating mode enum [nofrost|night|day] True select.thermostat_hc1_operating_mode select.thermostat_hc1_mode 6 1 1 3 1
RC10, Moduline 100 thermostat 79 hc1.daytemp day temperature uint8 (>=0<=127) C True number.thermostat_hc1_day_temperature number.thermostat_hc1_daytemp 6 1 1/2 56 1
RC10, Moduline 100 thermostat 79 hc1.nighttemp night temperature uint8 (>=0<=127) C True number.thermostat_hc1_night_temperature number.thermostat_hc1_nighttemp 6 1 1/2 57 1
RC10, Moduline 100 thermostat 79 hc1.reducehours duration for nighttemp uint8 (>=0<=254) hours True number.thermostat_hc1_duration_for_nighttemp number.thermostat_hc1_reducehours 6 1 1 196 1
RC10, Moduline 100 thermostat 79 hc1.reduceminutes remaining time for nightmode uint16 (>=0<=31999) minutes False sensor.thermostat_hc1_remaining_time_for_nightmode sensor.thermostat_hc1_reduceminutes 6 1 1 197 1
RC10, Moduline 100 thermostat 79 dhw.mode operating mode enum [on|off|auto] True select.thermostat_dhw_operating_mode select.thermostat_dhw_mode 6 9 1 0 1
Moduline 200 thermostat 80 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
Moduline 200 thermostat 80 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
Moduline 200 thermostat 80 intoffset internal temperature offset int8 (>=-12<=12) C True number.thermostat_internal_temperature_offset number.thermostat_intoffset 6 0 1/10 46 1
Moduline 200 thermostat 80 heatingpid heating PID enum [fast|medium|slow] True select.thermostat_heating_PID select.thermostat_heatingpid 6 0 1 74 1
Moduline 200 thermostat 80 backlight key backlight boolean True switch.thermostat_key_backlight switch.thermostat_backlight 6 0 1 71 1
Moduline 200 thermostat 80 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/2 0 1
Moduline 200 thermostat 80 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
Moduline 200 thermostat 80 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
Moduline 200 thermostat 80 hc1.mode operating mode enum [nofrost|night|day] True select.thermostat_hc1_operating_mode select.thermostat_hc1_mode 6 1 1 3 1
Moduline 200 thermostat 80 hc1.daytemp day temperature uint8 (>=0<=127) C True number.thermostat_hc1_day_temperature number.thermostat_hc1_daytemp 6 1 1/2 56 1
Moduline 200 thermostat 80 hc1.nighttemp night temperature uint8 (>=0<=127) C True number.thermostat_hc1_night_temperature number.thermostat_hc1_nighttemp 6 1 1/2 57 1
Moduline 200 thermostat 80 hc1.reducehours duration for nighttemp uint8 (>=0<=254) hours True number.thermostat_hc1_duration_for_nighttemp number.thermostat_hc1_reducehours 6 1 1 196 1
Moduline 200 thermostat 80 hc1.reduceminutes remaining time for nightmode uint16 (>=0<=31999) minutes False sensor.thermostat_hc1_remaining_time_for_nightmode sensor.thermostat_hc1_reduceminutes 6 1 1 197 1
Moduline 200 thermostat 80 dhw.mode operating mode enum [on|off|auto] True select.thermostat_dhw_operating_mode select.thermostat_dhw_mode 6 9 1 0 1
RC35 thermostat 86 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
RC35 thermostat 86 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
RC35 thermostat 86 datetime date/time string True sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
RC35 thermostat 86 intoffset internal temperature offset int8 (>=-5<=5) C True number.thermostat_internal_temperature_offset number.thermostat_intoffset 6 0 1/10 46 1
RC35 thermostat 86 minexttemp minimal external temperature int8 (>=-30<=0) C True number.thermostat_minimal_external_temperature number.thermostat_minexttemp 6 0 1 51 1
RC35 thermostat 86 inttemp1 temperature sensor 1 int16 (>=-3199<=3199) C False sensor.thermostat_temperature_sensor_1 sensor.thermostat_inttemp1 6 0 1/10 68 1
RC35 thermostat 86 inttemp2 temperature sensor 2 int16 (>=-3199<=3199) C False sensor.thermostat_temperature_sensor_2 sensor.thermostat_inttemp2 6 0 1/10 69 1
RC35 thermostat 86 damping damping outdoor temperature boolean True switch.thermostat_damping_outdoor_temperature switch.thermostat_damping 6 0 1 52 1
RC35 thermostat 86 dampedoutdoortemp damped outdoor temperature int8 (>=-126<=126) C False sensor.thermostat_damped_outdoor_temperature sensor.thermostat_dampedoutdoortemp 6 0 1 48 1
RC35 thermostat 86 building building type enum [light|medium|heavy] True select.thermostat_building_type select.thermostat_building 6 0 1 50 1
RC35 thermostat 86 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/2 0 1
RC35 thermostat 86 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
RC35 thermostat 86 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
RC35 thermostat 86 hc1.mode operating mode enum [night|day|auto] True select.thermostat_hc1_operating_mode select.thermostat_hc1_mode 6 1 1 3 1
RC35 thermostat 86 hc1.modetype mode type enum [night|day] False sensor.thermostat_hc1_mode_type sensor.thermostat_hc1_modetype 6 1 1 4 1
RC35 thermostat 86 hc1.daytemp day temperature uint8 (>=10<=30) C True number.thermostat_hc1_day_temperature number.thermostat_hc1_daytemp 6 1 1/2 56 1
RC35 thermostat 86 hc1.nighttemp night temperature uint8 (>=10<=30) C True number.thermostat_hc1_night_temperature number.thermostat_hc1_nighttemp 6 1 1/2 57 1
RC35 thermostat 86 hc1.designtemp design temperature uint8 (>=30<=90) C True number.thermostat_hc1_design_temperature number.thermostat_hc1_designtemp 6 1 1 9 1
RC35 thermostat 86 hc1.offsettemp offset temperature int8 (>=-5<=5) C True number.thermostat_hc1_offset_temperature number.thermostat_hc1_offsettemp 6 1 1/2 10 1
RC35 thermostat 86 hc1.holidaytemp holiday temperature uint8 (>=5<=30) C True number.thermostat_hc1_holiday_temperature number.thermostat_hc1_holidaytemp 6 1 1/2 58 1
RC35 thermostat 86 hc1.targetflowtemp target flow temperature uint8 (>=0<=254) C False sensor.thermostat_hc1_target_flow_temperature sensor.thermostat_hc1_targetflowtemp 6 1 1 18 1
RC35 thermostat 86 hc1.summertemp summer temperature uint8 (>=9<=25) C True number.thermostat_hc1_summer_temperature number.thermostat_hc1_summertemp 6 1 1 8 1
RC35 thermostat 86 hc1.summermode summer mode enum [winter|summer] False sensor.thermostat_hc1_summer_mode sensor.thermostat_hc1_summermode 6 1 1 22 1
RC35 thermostat 86 hc1.holidaymode holiday mode boolean False binary_sensor.thermostat_hc1_holiday_mode binary_sensor.thermostat_hc1_holidaymode 6 1 1 59 1
RC35 thermostat 86 hc1.nofrosttemp nofrost temperature int8 (>=-20<=10) C True number.thermostat_hc1_nofrost_temperature number.thermostat_hc1_nofrosttemp 6 1 1 17 1
RC35 thermostat 86 hc1.nofrostmode nofrost mode enum [off|outdoor|room] True select.thermostat_hc1_nofrost_mode select.thermostat_hc1_nofrostmode 6 1 1 16 1
RC35 thermostat 86 hc1.roominfluence room influence uint8 (>=0<=10) C True number.thermostat_hc1_room_influence number.thermostat_hc1_roominfluence 6 1 1 13 1
RC35 thermostat 86 hc1.minflowtemp min flow temperature uint8 (>=5<=70) C True number.thermostat_hc1_min_flow_temperature number.thermostat_hc1_minflowtemp 6 1 1 11 1
RC35 thermostat 86 hc1.maxflowtemp max flow temperature uint8 (>=30<=90) C True number.thermostat_hc1_max_flow_temperature number.thermostat_hc1_maxflowtemp 6 1 1 12 1
RC35 thermostat 86 hc1.flowtempoffset flow temperature offset for mixer uint8 (>=0<=20) C True number.thermostat_hc1_flow_temperature_offset_for_mixer number.thermostat_hc1_flowtempoffset 6 1 1 60 1
RC35 thermostat 86 hc1.heatingtype heating type enum [off|radiator|convector|floor] True select.thermostat_hc1_heating_type select.thermostat_hc1_heatingtype 6 1 1 19 1
RC35 thermostat 86 hc1.reducemode reduce mode enum [nofrost|reduce|room|outdoor] True select.thermostat_hc1_reduce_mode select.thermostat_hc1_reducemode 6 1 1 31 1
RC35 thermostat 86 hc1.controlmode control mode enum [outdoor|room] True select.thermostat_hc1_control_mode select.thermostat_hc1_controlmode 6 1 1 25 1
RC35 thermostat 86 hc1.control control device enum [off|RC20|RC3x] True select.thermostat_hc1_control_device select.thermostat_hc1_control 6 1 1 41 1
RC35 thermostat 86 hc1.holidays holiday dates string True sensor.thermostat_hc1_holiday_dates sensor.thermostat_hc1_holidays 6 1 1 61 13
RC35 thermostat 86 hc1.vacations vacation dates string True sensor.thermostat_hc1_vacation_dates sensor.thermostat_hc1_vacations 6 1 1 74 13
RC35 thermostat 86 hc1.program program enum [own 1|family|morning|evening|am|pm|midday|singles|seniors|new|own 2] True select.thermostat_hc1_program select.thermostat_hc1_program 6 1 1 26 1
RC35 thermostat 86 hc1.pause pause time uint8 (>=0<=99) hours True number.thermostat_hc1_pause_time number.thermostat_hc1_pause 6 1 1 87 1
RC35 thermostat 86 hc1.party party time uint8 (>=0<=99) hours True number.thermostat_hc1_party_time number.thermostat_hc1_party 6 1 1 88 1
RC35 thermostat 86 hc1.tempautotemp temporary set temperature automode uint8 (>=0<=30) C True number.thermostat_hc1_temporary_set_temperature_automode number.thermostat_hc1_tempautotemp 6 1 1/2 27 1
RC35 thermostat 86 hc1.noreducetemp no reduce below temperature int8 (>=-31<=10) C True number.thermostat_hc1_no_reduce_below_temperature number.thermostat_hc1_noreducetemp 6 1 1 32 1
RC35 thermostat 86 hc1.reducetemp off/reduce switch temperature int8 (>=-20<=10) C True number.thermostat_hc1_off/reduce_switch_temperature number.thermostat_hc1_reducetemp 6 1 1 33 1
RC35 thermostat 86 hc1.vacreducetemp vacations off/reduce switch temperature int8 (>=-20<=10) C True number.thermostat_hc1_vacations_off/reduce_switch_temperature number.thermostat_hc1_vacreducetemp 6 1 1 89 1
RC35 thermostat 86 hc1.vacreducemode vacations reduce mode enum [nofrost|reduce|room|outdoor] True select.thermostat_hc1_vacations_reduce_mode select.thermostat_hc1_vacreducemode 6 1 1 90 1
RC35 thermostat 86 hc1.remotetemp room temperature from remote cmd [] (>=-1<=101) C True sensor.thermostat_hc1_room_temperature_from_remote sensor.thermostat_hc1_remotetemp 6 1 1/10 42 1
RC35 thermostat 86 hc1.dhwprio dhw priority boolean True switch.thermostat_hc1_dhw_priority switch.thermostat_hc1_dhwprio 6 1 1 34 1
RC35 thermostat 86 hc1.switchonoptimization switch-on optimization boolean True switch.thermostat_hc1_switch-on_optimization switch.thermostat_hc1_switchonoptimization 6 1 1 30 1
RC35 thermostat 86 hc1.switchtime1 own1 program switchtime string True sensor.thermostat_hc1_own1_program_switchtime sensor.thermostat_hc1_switchtime1 6 1 1 91 8
RC35 thermostat 86 hc1.switchtime2 own2 program switchtime string True sensor.thermostat_hc1_own2_program_switchtime sensor.thermostat_hc1_switchtime2 6 1 1 99 8
RC35 thermostat 86 dhw.mode operating mode enum [off|on|auto] True select.thermostat_dhw_operating_mode select.thermostat_dhw_mode 6 9 1 0 1
RC35 thermostat 86 dhw.circmode circulation pump mode enum [off|on|auto] True select.thermostat_dhw_circulation_pump_mode select.thermostat_dhw_circmode 6 9 1 3 1
RC35 thermostat 86 dhw.progmode program enum [std prog|own prog] True select.thermostat_dhw_program select.thermostat_dhw_progmode 6 9 1 12 1
RC35 thermostat 86 dhw.circprog circulation program enum [std prog|own prog] True select.thermostat_dhw_circulation_program select.thermostat_dhw_circprog 6 9 1 13 1
RC35 thermostat 86 dhw.disinfecting disinfecting boolean True switch.thermostat_dhw_disinfecting switch.thermostat_dhw_disinfecting 6 9 1 7 1
RC35 thermostat 86 dhw.disinfectday disinfection day enum [mo|tu|we|th|fr|sa|su|all] True select.thermostat_dhw_disinfection_day select.thermostat_dhw_disinfectday 6 9 1 8 1
RC35 thermostat 86 dhw.disinfecthour disinfection hour uint8 (>=0<=23) True number.thermostat_dhw_disinfection_hour number.thermostat_dhw_disinfecthour 6 9 1 14 1
RC35 thermostat 86 dhw.maxtemp maximum temperature uint8 (>=60<=80) C True number.thermostat_dhw_maximum_temperature number.thermostat_dhw_maxtemp 6 9 1 15 1
RC35 thermostat 86 dhw.onetimekey one time key function boolean True switch.thermostat_dhw_one_time_key_function switch.thermostat_dhw_onetimekey 6 9 1 16 1
RC35 thermostat 86 dhw.switchtime program switchtime string True sensor.thermostat_dhw_program_switchtime sensor.thermostat_dhw_switchtime 6 9 1 17 8
RC35 thermostat 86 dhw.circswitchtime circulation program switchtime string True sensor.thermostat_dhw_circulation_program_switchtime sensor.thermostat_dhw_circswitchtime 6 9 1 25 8
RC35 thermostat 86 dhw.holidays holiday dates string True sensor.thermostat_dhw_holiday_dates sensor.thermostat_dhw_holidays 6 9 1 33 13
RC35 thermostat 86 dhw.vacations vacation dates string True sensor.thermostat_dhw_vacation_dates sensor.thermostat_dhw_vacations 6 9 1 46 13
RC10, Moduline 100 thermostat 90 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
RC10, Moduline 100 thermostat 90 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
RC10, Moduline 100 thermostat 90 datetime date/time string False sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
RC10, Moduline 100 thermostat 90 minexttemp minimal external temperature int8 (>=-126<=126) C True number.thermostat_minimal_external_temperature number.thermostat_minexttemp 6 0 1 51 1
RC10, Moduline 100 thermostat 90 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/2 0 1
RC10, Moduline 100 thermostat 90 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
RC10, Moduline 100 thermostat 90 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
RC10, Moduline 100 thermostat 90 hc1.mode operating mode enum [night|day|auto] True select.thermostat_hc1_operating_mode select.thermostat_hc1_mode 6 1 1 3 1
RC10, Moduline 100 thermostat 90 hc1.modetype mode type enum [night|day] False sensor.thermostat_hc1_mode_type sensor.thermostat_hc1_modetype 6 1 1 4 1
RC10, Moduline 100 thermostat 90 hc1.daytemp day temperature uint8 (>=0<=127) C True number.thermostat_hc1_day_temperature number.thermostat_hc1_daytemp 6 1 1/2 56 1
RC10, Moduline 100 thermostat 90 hc1.nighttemp night temperature uint8 (>=0<=127) C True number.thermostat_hc1_night_temperature number.thermostat_hc1_nighttemp 6 1 1/2 57 1
RC10, Moduline 100 thermostat 90 hc1.program program enum [family|morning|evening|am|pm|midday|singles|seniors] True select.thermostat_hc1_program select.thermostat_hc1_program 6 1 1 26 1
RC10, Moduline 100 thermostat 90 hc1.minflowtemp min flow temperature uint8 (>=0<=254) C True number.thermostat_hc1_min_flow_temperature number.thermostat_hc1_minflowtemp 6 1 1 11 1
RC10, Moduline 100 thermostat 90 hc1.maxflowtemp max flow temperature uint8 (>=0<=254) C True number.thermostat_hc1_max_flow_temperature number.thermostat_hc1_maxflowtemp 6 1 1 12 1
RC10, Moduline 100 thermostat 90 hc1.tempautotemp temporary set temperature automode uint8 (>=0<=127) C True number.thermostat_hc1_temporary_set_temperature_automode number.thermostat_hc1_tempautotemp 6 1 1/2 27 1
RC10, Moduline 100 thermostat 90 hc1.heatingtype heating type enum [off|radiator|convector|floor] True select.thermostat_hc1_heating_type select.thermostat_hc1_heatingtype 6 1 1 19 1
RC10, Moduline 100 thermostat 90 hc1.summertemp summer temperature uint8 (>=10<=30) C True number.thermostat_hc1_summer_temperature number.thermostat_hc1_summertemp 6 1 1 8 1
RC10, Moduline 100 thermostat 90 hc1.summermode summer mode enum [winter|summer] False sensor.thermostat_hc1_summer_mode sensor.thermostat_hc1_summermode 6 1 1 22 1
RC20RF thermostat 93 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
RC20RF thermostat 93 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
RC20RF thermostat 93 datetime date/time string False sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
RC20RF thermostat 93 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/2 0 1
RC20RF thermostat 93 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
RC20RF thermostat 93 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
RC20RF thermostat 93 hc1.mode operating mode enum [off|manual|auto] True select.thermostat_hc1_operating_mode select.thermostat_hc1_mode 6 1 1 3 1
RC20RF thermostat 93 hc1.manualtemp manual temperature uint8 (>=0<=127) C True number.thermostat_hc1_manual_temperature number.thermostat_hc1_manualtemp 6 1 1/2 6 1
RC20RF thermostat 93 hc1.offtemp temperature when mode is off uint8 (>=0<=127) C True number.thermostat_hc1_temperature_when_mode_is_off number.thermostat_hc1_offtemp 6 1 1/2 107 1
RC20RF thermostat 93 hc1.daytemp2 day temperature T2 uint8 (>=0<=127) C True number.thermostat_hc1_day_temperature_T2 number.thermostat_hc1_daytemp2 6 1 1/2 108 1
RC20RF thermostat 93 hc1.daytemp3 day temperature T3 uint8 (>=0<=127) C True number.thermostat_hc1_day_temperature_T3 number.thermostat_hc1_daytemp3 6 1 1/2 109 1
RC20RF thermostat 93 hc1.daytemp4 day temperature T4 uint8 (>=0<=127) C True number.thermostat_hc1_day_temperature_T4 number.thermostat_hc1_daytemp4 6 1 1/2 110 1
RC20RF thermostat 93 hc1.nighttemp night temperature T1 uint8 (>=0<=127) C True number.thermostat_hc1_night_temperature_T1 number.thermostat_hc1_nighttemp 6 1 1/2 57 1
RC20RF thermostat 93 hc1.switchtime program switchtime string True sensor.thermostat_hc1_program_switchtime sensor.thermostat_hc1_switchtime 6 1 1 111 8
RFM20 Remote thermostat 94 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
RFM20 Remote thermostat 94 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
RFM20 Remote thermostat 94 datetime date/time string False sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
RFM20 Remote thermostat 94 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/2 0 1
RFM20 Remote thermostat 94 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
RFM20 Remote thermostat 94 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
RC25 thermostat 151 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
RC25 thermostat 151 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
RC25 thermostat 151 datetime date/time string False sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
RC25 thermostat 151 minexttemp minimal external temperature int8 (>=-126<=126) C True number.thermostat_minimal_external_temperature number.thermostat_minexttemp 6 0 1 51 1
RC25 thermostat 151 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/2 0 1
RC25 thermostat 151 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
RC25 thermostat 151 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
RC25 thermostat 151 hc1.mode operating mode enum [night|day|auto] True select.thermostat_hc1_operating_mode select.thermostat_hc1_mode 6 1 1 3 1
RC25 thermostat 151 hc1.modetype mode type enum [night|day] False sensor.thermostat_hc1_mode_type sensor.thermostat_hc1_modetype 6 1 1 4 1
RC25 thermostat 151 hc1.daytemp day temperature uint8 (>=0<=127) C True number.thermostat_hc1_day_temperature number.thermostat_hc1_daytemp 6 1 1/2 56 1
RC25 thermostat 151 hc1.nighttemp night temperature uint8 (>=0<=127) C True number.thermostat_hc1_night_temperature number.thermostat_hc1_nighttemp 6 1 1/2 57 1
RC25 thermostat 151 hc1.program program enum [family|morning|evening|am|pm|midday|singles|seniors] True select.thermostat_hc1_program select.thermostat_hc1_program 6 1 1 26 1
RC25 thermostat 151 hc1.minflowtemp min flow temperature uint8 (>=0<=254) C True number.thermostat_hc1_min_flow_temperature number.thermostat_hc1_minflowtemp 6 1 1 11 1
RC25 thermostat 151 hc1.maxflowtemp max flow temperature uint8 (>=0<=254) C True number.thermostat_hc1_max_flow_temperature number.thermostat_hc1_maxflowtemp 6 1 1 12 1
RC25 thermostat 151 hc1.tempautotemp temporary set temperature automode uint8 (>=0<=127) C True number.thermostat_hc1_temporary_set_temperature_automode number.thermostat_hc1_tempautotemp 6 1 1/2 27 1
RC25 thermostat 151 hc1.heatingtype heating type enum [off|radiator|convector|floor] True select.thermostat_hc1_heating_type select.thermostat_hc1_heatingtype 6 1 1 19 1
RC25 thermostat 151 hc1.summertemp summer temperature uint8 (>=9<=25) C True number.thermostat_hc1_summer_temperature number.thermostat_hc1_summertemp 6 1 1 8 1
RC25 thermostat 151 hc1.summermode summer mode enum [winter|summer] False sensor.thermostat_hc1_summer_mode sensor.thermostat_hc1_summermode 6 1 1 22 1
RC200, CW100, CR120, CR50 thermostat 157 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
RC200, CW100, CR120, CR50 thermostat 157 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
RC200, CW100, CR120, CR50 thermostat 157 datetime date/time string True sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
RC200, CW100, CR120, CR50 thermostat 157 intoffset internal temperature offset int8 (>=-12<=12) C True number.thermostat_internal_temperature_offset number.thermostat_intoffset 6 0 1/10 46 1
RC200, CW100, CR120, CR50 thermostat 157 floordry floor drying enum [off|start|heat|hold|cool|end] False sensor.thermostat_floor_drying sensor.thermostat_floordry 6 0 1 47 1
RC200, CW100, CR120, CR50 thermostat 157 dampedoutdoortemp damped outdoor temperature int16 (>=-3199<=3199) C False sensor.thermostat_damped_outdoor_temperature sensor.thermostat_dampedoutdoortemp 6 0 1/10 48 1
RC200, CW100, CR120, CR50 thermostat 157 floordrytemp floor drying temperature uint8 (>=0<=254) C False sensor.thermostat_floor_drying_temperature sensor.thermostat_floordrytemp 6 0 1 49 1
RC200, CW100, CR120, CR50 thermostat 157 building building type enum [light|medium|heavy] True select.thermostat_building_type select.thermostat_building 6 0 1 50 1
RC200, CW100, CR120, CR50 thermostat 157 minexttemp minimal external temperature int8 (>=-126<=126) C True number.thermostat_minimal_external_temperature number.thermostat_minexttemp 6 0 1 51 1
RC200, CW100, CR120, CR50 thermostat 157 damping damping outdoor temperature boolean True switch.thermostat_damping_outdoor_temperature switch.thermostat_damping 6 0 1 52 1
RC200, CW100, CR120, CR50 thermostat 157 solar solar boolean True switch.thermostat_solar switch.thermostat_solar 6 0 1 53 1
RC200, CW100, CR120, CR50 thermostat 157 vacations vacation dates string True sensor.thermostat_vacation_dates sensor.thermostat_vacations 6 0 1 76 13
RC200, CW100, CR120, CR50 thermostat 157 hybridstrategy hybrid control strategy enum [co2 optimized|cost optimized|outside temp switched|co2 cost mix] True select.thermostat_hybrid_control_strategy select.thermostat_hybridstrategy 6 0 1 54 1
RC200, CW100, CR120, CR50 thermostat 157 switchovertemp outside switchover temperature int8 (>=-20<=20) C True number.thermostat_outside_switchover_temperature number.thermostat_switchovertemp 6 0 1 55 1
RC200, CW100, CR120, CR50 thermostat 157 energycostratio energy cost ratio uint8 (>=0<=20) True number.thermostat_energy_cost_ratio number.thermostat_energycostratio 6 0 1/10 56 1
RC200, CW100, CR120, CR50 thermostat 157 fossilefactor fossile energy factor uint8 (>=0<=5) True number.thermostat_fossile_energy_factor number.thermostat_fossilefactor 6 0 1/10 57 1
RC200, CW100, CR120, CR50 thermostat 157 electricfactor electric energy factor uint8 (>=0<=5) True number.thermostat_electric_energy_factor number.thermostat_electricfactor 6 0 1/10 58 1
RC200, CW100, CR120, CR50 thermostat 157 delayboiler delay boiler support uint8 (>=5<=120) minutes True number.thermostat_delay_boiler_support number.thermostat_delayboiler 6 0 1 59 1
RC200, CW100, CR120, CR50 thermostat 157 tempdiffboiler temp diff boiler support uint8 (>=1<=99) C True number.thermostat_temp_diff_boiler_support number.thermostat_tempdiffboiler 6 0 1 60 1
RC200, CW100, CR120, CR50 thermostat 157 pvenabledhw enable raise dhw boolean True switch.thermostat_enable_raise_dhw switch.thermostat_pvenabledhw 6 0 1 61 1
RC200, CW100, CR120, CR50 thermostat 157 pvraiseheat raise heating with PV int8 (>=0<=5) K True number.thermostat_raise_heating_with_PV number.thermostat_pvraiseheat 6 0 1 62 1
RC200, CW100, CR120, CR50 thermostat 157 pvlowercool lower cooling with PV int8 (>=-5<=0) K True number.thermostat_lower_cooling_with_PV number.thermostat_pvlowercool 6 0 1 63 1
RC200, CW100, CR120, CR50 thermostat 157 absent absent boolean True switch.thermostat_absent switch.thermostat_absent 6 0 1 64 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/2 0 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.mode operating mode enum [manual|auto] True select.thermostat_hc1_operating_mode select.thermostat_hc1_mode 6 1 1 3 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.modetype mode type enum [eco|comfort] False sensor.thermostat_hc1_mode_type sensor.thermostat_hc1_modetype 6 1 1 4 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.ecotemp eco temperature uint8 (>=0<=127) C True number.thermostat_hc1_eco_temperature number.thermostat_hc1_ecotemp 6 1 1/2 5 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.manualtemp manual temperature uint8 (>=0<=127) C True number.thermostat_hc1_manual_temperature number.thermostat_hc1_manualtemp 6 1 1/2 6 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.comforttemp comfort temperature uint8 (>=0<=127) C True number.thermostat_hc1_comfort_temperature number.thermostat_hc1_comforttemp 6 1 1/2 7 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.summertemp summer temperature uint8 (>=10<=30) C True number.thermostat_hc1_summer_temperature number.thermostat_hc1_summertemp 6 1 1 8 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.designtemp design temperature uint8 (>=0<=254) C True number.thermostat_hc1_design_temperature number.thermostat_hc1_designtemp 6 1 1 9 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.offsettemp offset temperature int8 (>=-126<=126) C True number.thermostat_hc1_offset_temperature number.thermostat_hc1_offsettemp 6 1 1 10 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.minflowtemp min flow temperature uint8 (>=0<=254) C True number.thermostat_hc1_min_flow_temperature number.thermostat_hc1_minflowtemp 6 1 1 11 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.maxflowtemp max flow temperature uint8 (>=0<=254) C True number.thermostat_hc1_max_flow_temperature number.thermostat_hc1_maxflowtemp 6 1 1 12 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.roominfluence room influence uint8 (>=0<=254) C True number.thermostat_hc1_room_influence number.thermostat_hc1_roominfluence 6 1 1 13 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.roominflfactor room influence factor uint8 (>=0<=25) True number.thermostat_hc1_room_influence_factor number.thermostat_hc1_roominflfactor 6 1 1/10 14 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.curroominfl current room influence int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_influence sensor.thermostat_hc1_curroominfl 6 1 1/10 15 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.nofrostmode nofrost mode enum [room|outdoor|room outdoor] True select.thermostat_hc1_nofrost_mode select.thermostat_hc1_nofrostmode 6 1 1 16 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.nofrosttemp nofrost temperature int8 (>=-126<=126) C True number.thermostat_hc1_nofrost_temperature number.thermostat_hc1_nofrosttemp 6 1 1 17 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.targetflowtemp target flow temperature uint8 (>=0<=254) C False sensor.thermostat_hc1_target_flow_temperature sensor.thermostat_hc1_targetflowtemp 6 1 1 18 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.heatingtype heating type enum [off|radiator|convector|floor] True select.thermostat_hc1_heating_type select.thermostat_hc1_heatingtype 6 1 1 19 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.summersetmode set summer mode enum [summer|auto|winter] True select.thermostat_hc1_set_summer_mode select.thermostat_hc1_summersetmode 6 1 1 20 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.hpoperatingmode heatpump operating mode enum [off|auto|heating|cooling] True select.thermostat_hc1_heatpump_operating_mode select.thermostat_hc1_hpoperatingmode 6 1 1 21 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.summermode summer mode enum [winter|summer] False sensor.thermostat_hc1_summer_mode sensor.thermostat_hc1_summermode 6 1 1 22 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.hpoperatingstate heatpump operating state enum [heating|off|cooling] False sensor.thermostat_hc1_heatpump_operating_state sensor.thermostat_hc1_hpoperatingstate 6 1 1 23 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.vacationmode vacation mode boolean False binary_sensor.thermostat_hc1_vacation_mode binary_sensor.thermostat_hc1_vacationmode 6 1 1 24 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.controlmode control mode enum [optimized|simple|n/a|room|power] True select.thermostat_hc1_control_mode select.thermostat_hc1_controlmode 6 1 1 25 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.program program enum [prog 1|prog 2] True select.thermostat_hc1_program select.thermostat_hc1_program 6 1 1 26 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.tempautotemp temporary set temperature automode int8 (>=-1<=30) C True number.thermostat_hc1_temporary_set_temperature_automode number.thermostat_hc1_tempautotemp 6 1 1/2 27 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.cooltemp cooling temperature int8 (>=-1<=30) C True number.thermostat_hc1_cooling_temperature number.thermostat_hc1_cooltemp 6 1 1/2 28 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.fastheatup fast heatup uint8 (>=0<=100) % True number.thermostat_hc1_fast_heatup number.thermostat_hc1_fastheatup 6 1 1 29 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.switchonoptimization switch-on optimization boolean True switch.thermostat_hc1_switch-on_optimization switch.thermostat_hc1_switchonoptimization 6 1 1 30 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.reducemode reduce mode enum [outdoor|room|reduce] True select.thermostat_hc1_reduce_mode select.thermostat_hc1_reducemode 6 1 1 31 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.noreducetemp no reduce below temperature int8 (>=-126<=126) C True number.thermostat_hc1_no_reduce_below_temperature number.thermostat_hc1_noreducetemp 6 1 1 32 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.reducetemp off/reduce switch temperature int8 (>=-126<=126) C True number.thermostat_hc1_off/reduce_switch_temperature number.thermostat_hc1_reducetemp 6 1 1 33 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.dhwprio dhw priority boolean True switch.thermostat_hc1_dhw_priority switch.thermostat_hc1_dhwprio 6 1 1 34 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.hpcooling hp cooling boolean True switch.thermostat_hc1_hp_cooling switch.thermostat_hc1_hpcooling 6 1 1 35 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.coolingon cooling on boolean False binary_sensor.thermostat_hc1_cooling_on binary_sensor.thermostat_hc1_coolingon 6 1 1 36 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.hpmode HP Mode enum [heating|cooling|heating & cooling] True select.thermostat_hc1_HP_Mode select.thermostat_hc1_hpmode 6 1 1 37 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.dewoffset dew point offset uint8 (>=2<=10) K True number.thermostat_hc1_dew_point_offset number.thermostat_hc1_dewoffset 6 1 1 38 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.roomtempdiff room temp difference uint8 (>=0<=254) K True number.thermostat_hc1_room_temp_difference number.thermostat_hc1_roomtempdiff 6 1 1 39 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.hpminflowtemp HP min. flow temp. uint8 (>=0<=254) C True number.thermostat_hc1_HP_min._flow_temp. number.thermostat_hc1_hpminflowtemp 6 1 1 40 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.control control device enum [RC310|RC200|RC100|RC100H|TC100] True select.thermostat_hc1_control_device select.thermostat_hc1_control 6 1 1 41 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.heatondelay heat-on delay uint8 (>=1<=48) hours True number.thermostat_hc1_heat-on_delay number.thermostat_hc1_heatondelay 6 1 1 44 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.heatoffdelay heat-off delay uint8 (>=1<=48) hours True number.thermostat_hc1_heat-off_delay number.thermostat_hc1_heatoffdelay 6 1 1 45 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.instantstart instant start uint8 (>=1<=10) K True number.thermostat_hc1_instant_start number.thermostat_hc1_instantstart 6 1 1 46 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.boost boost mode boolean True switch.thermostat_hc1_boost_mode switch.thermostat_hc1_boost 6 1 1 47 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.boosttime boost time uint8 (>=0<=254) hours True number.thermostat_hc1_boost_time number.thermostat_hc1_boosttime 6 1 1 48 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.coolstart cooling starttemp uint8 (>=20<=35) C True number.thermostat_hc1_cooling_starttemp number.thermostat_hc1_coolstart 6 1 1 49 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.coolondelay cooling on delay uint8 (>=1<=48) hours True number.thermostat_hc1_cooling_on_delay number.thermostat_hc1_coolondelay 6 1 1 50 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.cooloffdelay cooling off delay uint8 (>=1<=48) hours True number.thermostat_hc1_cooling_off_delay number.thermostat_hc1_cooloffdelay 6 1 1 51 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.switchprogmode switch program mode enum [level|absolute] True select.thermostat_hc1_switch_program_mode select.thermostat_hc1_switchprogmode 6 1 1 52 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.redthreshold reduction threshold int8 (>=12<=22) C True number.thermostat_hc1_reduction_threshold number.thermostat_hc1_redthreshold 6 1 1/2 53 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.solarinfl solar influence uint8 (>=-5<=4294967295) C True number.thermostat_hc1_solar_influence number.thermostat_hc1_solarinfl 6 1 1 54 1
RC200, CW100, CR120, CR50 thermostat 157 hc1.currsolarinfl curent solar influence uint8 (>=0<=25) C False sensor.thermostat_hc1_curent_solar_influence sensor.thermostat_hc1_currsolarinfl 6 1 1/10 55 1
RC200, CW100, CR120, CR50 thermostat 157 dhw.mode operating mode enum [off|on|auto] True select.thermostat_dhw_operating_mode select.thermostat_dhw_mode 6 9 1 0 1
RC200, CW100, CR120, CR50 thermostat 157 dhw.settemp set temperature uint8 (>=0<=254) C True number.thermostat_dhw_set_temperature number.thermostat_dhw_settemp 6 9 1 1 1
RC200, CW100, CR120, CR50 thermostat 157 dhw.settemplow set low temperature uint8 (>=0<=254) C True number.thermostat_dhw_set_low_temperature number.thermostat_dhw_settemplow 6 9 1 2 1
RC200, CW100, CR120, CR50 thermostat 157 dhw.circmode circulation pump mode enum [off|on|auto|own prog] True select.thermostat_dhw_circulation_pump_mode select.thermostat_dhw_circmode 6 9 1 3 1
RC200, CW100, CR120, CR50 thermostat 157 dhw.chargeduration charge duration uint8 (>=0<=3810) minutes True number.thermostat_dhw_charge_duration number.thermostat_dhw_chargeduration 6 9 15 4 1
RC200, CW100, CR120, CR50 thermostat 157 dhw.charge charge boolean True switch.thermostat_dhw_charge switch.thermostat_dhw_charge 6 9 1 5 1
RC200, CW100, CR120, CR50 thermostat 157 dhw.extra extra boolean False binary_sensor.thermostat_dhw_extra binary_sensor.thermostat_dhw_extra 6 9 1 6 1
RC200, CW100, CR120, CR50 thermostat 157 dhw.disinfecting disinfecting boolean True switch.thermostat_dhw_disinfecting switch.thermostat_dhw_disinfecting 6 9 1 7 1
RC200, CW100, CR120, CR50 thermostat 157 dhw.disinfectday disinfection day enum [mo|tu|we|th|fr|sa|su|all] True select.thermostat_dhw_disinfection_day select.thermostat_dhw_disinfectday 6 9 1 8 1
RC200, CW100, CR120, CR50 thermostat 157 dhw.disinfecttime disinfection time uint8 (>=0<=1431) minutes True number.thermostat_dhw_disinfection_time number.thermostat_dhw_disinfecttime 6 9 15 9 1
RC200, CW100, CR120, CR50 thermostat 157 dhw.dailyheating daily heating boolean True switch.thermostat_dhw_daily_heating switch.thermostat_dhw_dailyheating 6 9 1 10 1
RC200, CW100, CR120, CR50 thermostat 157 dhw.dailyheattime daily heating time uint8 (>=0<=1431) minutes True number.thermostat_dhw_daily_heating_time number.thermostat_dhw_dailyheattime 6 9 15 11 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 datetime date/time string True sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 intoffset internal temperature offset int8 (>=-12<=12) C True number.thermostat_internal_temperature_offset number.thermostat_intoffset 6 0 1/10 46 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 floordry floor drying enum [off|start|heat|hold|cool|end] False sensor.thermostat_floor_drying sensor.thermostat_floordry 6 0 1 47 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 dampedoutdoortemp damped outdoor temperature int16 (>=-3199<=3199) C False sensor.thermostat_damped_outdoor_temperature sensor.thermostat_dampedoutdoortemp 6 0 1/10 48 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 floordrytemp floor drying temperature uint8 (>=0<=254) C False sensor.thermostat_floor_drying_temperature sensor.thermostat_floordrytemp 6 0 1 49 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 building building type enum [light|medium|heavy] True select.thermostat_building_type select.thermostat_building 6 0 1 50 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 minexttemp minimal external temperature int8 (>=-126<=126) C True number.thermostat_minimal_external_temperature number.thermostat_minexttemp 6 0 1 51 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 damping damping outdoor temperature boolean True switch.thermostat_damping_outdoor_temperature switch.thermostat_damping 6 0 1 52 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 solar solar boolean True switch.thermostat_solar switch.thermostat_solar 6 0 1 53 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hybridstrategy hybrid control strategy enum [co2 optimized|cost optimized|outside temp switched|co2 cost mix] True select.thermostat_hybrid_control_strategy select.thermostat_hybridstrategy 6 0 1 54 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 switchovertemp outside switchover temperature int8 (>=-20<=20) C True number.thermostat_outside_switchover_temperature number.thermostat_switchovertemp 6 0 1 55 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 energycostratio energy cost ratio uint8 (>=0<=20) True number.thermostat_energy_cost_ratio number.thermostat_energycostratio 6 0 1/10 56 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 fossilefactor fossile energy factor uint8 (>=0<=5) True number.thermostat_fossile_energy_factor number.thermostat_fossilefactor 6 0 1/10 57 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 electricfactor electric energy factor uint8 (>=0<=5) True number.thermostat_electric_energy_factor number.thermostat_electricfactor 6 0 1/10 58 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 delayboiler delay boiler support uint8 (>=5<=120) minutes True number.thermostat_delay_boiler_support number.thermostat_delayboiler 6 0 1 59 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 tempdiffboiler temp diff boiler support uint8 (>=1<=99) C True number.thermostat_temp_diff_boiler_support number.thermostat_tempdiffboiler 6 0 1 60 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 pvenabledhw enable raise dhw boolean True switch.thermostat_enable_raise_dhw switch.thermostat_pvenabledhw 6 0 1 61 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 pvraiseheat raise heating with PV int8 (>=0<=5) K True number.thermostat_raise_heating_with_PV number.thermostat_pvraiseheat 6 0 1 62 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 pvlowercool lower cooling with PV int8 (>=-5<=0) K True number.thermostat_lower_cooling_with_PV number.thermostat_pvlowercool 6 0 1 63 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 absent absent boolean True switch.thermostat_absent switch.thermostat_absent 6 0 1 64 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/2 0 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.mode operating mode enum [manual|auto] True select.thermostat_hc1_operating_mode select.thermostat_hc1_mode 6 1 1 3 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.modetype mode type enum [eco|comfort] False sensor.thermostat_hc1_mode_type sensor.thermostat_hc1_modetype 6 1 1 4 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.ecotemp eco temperature uint8 (>=0<=127) C True number.thermostat_hc1_eco_temperature number.thermostat_hc1_ecotemp 6 1 1/2 5 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.manualtemp manual temperature uint8 (>=0<=127) C True number.thermostat_hc1_manual_temperature number.thermostat_hc1_manualtemp 6 1 1/2 6 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.comforttemp comfort temperature uint8 (>=0<=127) C True number.thermostat_hc1_comfort_temperature number.thermostat_hc1_comforttemp 6 1 1/2 7 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.summertemp summer temperature uint8 (>=10<=30) C True number.thermostat_hc1_summer_temperature number.thermostat_hc1_summertemp 6 1 1 8 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.designtemp design temperature uint8 (>=0<=254) C True number.thermostat_hc1_design_temperature number.thermostat_hc1_designtemp 6 1 1 9 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.offsettemp offset temperature int8 (>=-126<=126) C True number.thermostat_hc1_offset_temperature number.thermostat_hc1_offsettemp 6 1 1 10 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.minflowtemp min flow temperature uint8 (>=0<=254) C True number.thermostat_hc1_min_flow_temperature number.thermostat_hc1_minflowtemp 6 1 1 11 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.maxflowtemp max flow temperature uint8 (>=0<=254) C True number.thermostat_hc1_max_flow_temperature number.thermostat_hc1_maxflowtemp 6 1 1 12 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.roominfluence room influence uint8 (>=0<=254) C True number.thermostat_hc1_room_influence number.thermostat_hc1_roominfluence 6 1 1 13 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.roominflfactor room influence factor uint8 (>=0<=25) True number.thermostat_hc1_room_influence_factor number.thermostat_hc1_roominflfactor 6 1 1/10 14 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.curroominfl current room influence int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_influence sensor.thermostat_hc1_curroominfl 6 1 1/10 15 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.nofrostmode nofrost mode enum [room|outdoor|room outdoor] True select.thermostat_hc1_nofrost_mode select.thermostat_hc1_nofrostmode 6 1 1 16 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.nofrosttemp nofrost temperature int8 (>=-126<=126) C True number.thermostat_hc1_nofrost_temperature number.thermostat_hc1_nofrosttemp 6 1 1 17 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.targetflowtemp target flow temperature uint8 (>=0<=254) C False sensor.thermostat_hc1_target_flow_temperature sensor.thermostat_hc1_targetflowtemp 6 1 1 18 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.heatingtype heating type enum [off|radiator|convector|floor] True select.thermostat_hc1_heating_type select.thermostat_hc1_heatingtype 6 1 1 19 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.summersetmode set summer mode enum [summer|auto|winter] True select.thermostat_hc1_set_summer_mode select.thermostat_hc1_summersetmode 6 1 1 20 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.hpoperatingmode heatpump operating mode enum [off|auto|heating|cooling] True select.thermostat_hc1_heatpump_operating_mode select.thermostat_hc1_hpoperatingmode 6 1 1 21 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.summermode summer mode enum [winter|summer] False sensor.thermostat_hc1_summer_mode sensor.thermostat_hc1_summermode 6 1 1 22 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.hpoperatingstate heatpump operating state enum [heating|off|cooling] False sensor.thermostat_hc1_heatpump_operating_state sensor.thermostat_hc1_hpoperatingstate 6 1 1 23 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.vacationmode vacation mode boolean False binary_sensor.thermostat_hc1_vacation_mode binary_sensor.thermostat_hc1_vacationmode 6 1 1 24 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.controlmode control mode enum [weather compensated|outside basepoint|n/a|room|power|constant] True select.thermostat_hc1_control_mode select.thermostat_hc1_controlmode 6 1 1 25 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.program program enum [prog 1|prog 2] True select.thermostat_hc1_program select.thermostat_hc1_program 6 1 1 26 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.tempautotemp temporary set temperature automode int8 (>=-1<=30) C True number.thermostat_hc1_temporary_set_temperature_automode number.thermostat_hc1_tempautotemp 6 1 1/2 27 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.cooltemp cooling temperature int8 (>=-1<=30) C True number.thermostat_hc1_cooling_temperature number.thermostat_hc1_cooltemp 6 1 1/2 28 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.fastheatup fast heatup uint8 (>=0<=100) % True number.thermostat_hc1_fast_heatup number.thermostat_hc1_fastheatup 6 1 1 29 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.switchonoptimization switch-on optimization boolean True switch.thermostat_hc1_switch-on_optimization switch.thermostat_hc1_switchonoptimization 6 1 1 30 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.reducemode reduce mode enum [outdoor|room|reduce] True select.thermostat_hc1_reduce_mode select.thermostat_hc1_reducemode 6 1 1 31 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.noreducetemp no reduce below temperature int8 (>=-126<=126) C True number.thermostat_hc1_no_reduce_below_temperature number.thermostat_hc1_noreducetemp 6 1 1 32 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.reducetemp off/reduce switch temperature int8 (>=-126<=126) C True number.thermostat_hc1_off/reduce_switch_temperature number.thermostat_hc1_reducetemp 6 1 1 33 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.dhwprio dhw priority boolean True switch.thermostat_hc1_dhw_priority switch.thermostat_hc1_dhwprio 6 1 1 34 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.hpcooling hp cooling boolean True switch.thermostat_hc1_hp_cooling switch.thermostat_hc1_hpcooling 6 1 1 35 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.coolingon cooling on boolean False binary_sensor.thermostat_hc1_cooling_on binary_sensor.thermostat_hc1_coolingon 6 1 1 36 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.hpmode HP Mode enum [heating|cooling|heating & cooling] True select.thermostat_hc1_HP_Mode select.thermostat_hc1_hpmode 6 1 1 37 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.dewoffset dew point offset uint8 (>=2<=10) K True number.thermostat_hc1_dew_point_offset number.thermostat_hc1_dewoffset 6 1 1 38 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.roomtempdiff room temp difference uint8 (>=0<=254) K True number.thermostat_hc1_room_temp_difference number.thermostat_hc1_roomtempdiff 6 1 1 39 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.hpminflowtemp HP min. flow temp. uint8 (>=0<=254) C True number.thermostat_hc1_HP_min._flow_temp. number.thermostat_hc1_hpminflowtemp 6 1 1 40 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.control control device enum [RC310|RC200|RC100|RC100H|TC100] True select.thermostat_hc1_control_device select.thermostat_hc1_control 6 1 1 41 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.remotetemp room temperature from remote cmd [] (>=-1<=101) C True sensor.thermostat_hc1_room_temperature_from_remote sensor.thermostat_hc1_remotetemp 6 1 1/10 42 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.remotehum room humidity from remote cmd [] (>=-1<=101) % True sensor.thermostat_hc1_room_humidity_from_remote sensor.thermostat_hc1_remotehum 6 1 1 43 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.heatondelay heat-on delay uint8 (>=1<=48) hours True number.thermostat_hc1_heat-on_delay number.thermostat_hc1_heatondelay 6 1 1 44 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.heatoffdelay heat-off delay uint8 (>=1<=48) hours True number.thermostat_hc1_heat-off_delay number.thermostat_hc1_heatoffdelay 6 1 1 45 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.instantstart instant start uint8 (>=1<=10) K True number.thermostat_hc1_instant_start number.thermostat_hc1_instantstart 6 1 1 46 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.boost boost mode boolean True switch.thermostat_hc1_boost_mode switch.thermostat_hc1_boost 6 1 1 47 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.boosttime boost time uint8 (>=0<=254) hours True number.thermostat_hc1_boost_time number.thermostat_hc1_boosttime 6 1 1 48 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.coolstart cooling starttemp uint8 (>=20<=35) C True number.thermostat_hc1_cooling_starttemp number.thermostat_hc1_coolstart 6 1 1 49 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.coolondelay cooling on delay uint8 (>=1<=48) hours True number.thermostat_hc1_cooling_on_delay number.thermostat_hc1_coolondelay 6 1 1 50 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.cooloffdelay cooling off delay uint8 (>=1<=48) hours True number.thermostat_hc1_cooling_off_delay number.thermostat_hc1_cooloffdelay 6 1 1 51 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.switchprogmode switch program mode enum [level|absolute] True select.thermostat_hc1_switch_program_mode select.thermostat_hc1_switchprogmode 6 1 1 52 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.redthreshold reduction threshold int8 (>=12<=22) C True number.thermostat_hc1_reduction_threshold number.thermostat_hc1_redthreshold 6 1 1/2 53 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.solarinfl solar influence uint8 (>=-5<=4294967295) C True number.thermostat_hc1_solar_influence number.thermostat_hc1_solarinfl 6 1 1 54 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 hc1.currsolarinfl curent solar influence uint8 (>=0<=25) C False sensor.thermostat_hc1_curent_solar_influence sensor.thermostat_hc1_currsolarinfl 6 1 1/10 55 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 dhw.mode operating mode enum [off|normal|comfort|auto|own prog] True select.thermostat_dhw_operating_mode select.thermostat_dhw_mode 6 9 1 0 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 dhw.settemp set temperature uint8 (>=0<=254) C True number.thermostat_dhw_set_temperature number.thermostat_dhw_settemp 6 9 1 1 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 dhw.settemplow set low temperature uint8 (>=0<=254) C True number.thermostat_dhw_set_low_temperature number.thermostat_dhw_settemplow 6 9 1 2 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 dhw.circmode circulation pump mode enum [off|on|auto|own prog] True select.thermostat_dhw_circulation_pump_mode select.thermostat_dhw_circmode 6 9 1 3 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 dhw.chargeduration charge duration uint8 (>=0<=3810) minutes True number.thermostat_dhw_charge_duration number.thermostat_dhw_chargeduration 6 9 15 4 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 dhw.charge charge boolean True switch.thermostat_dhw_charge switch.thermostat_dhw_charge 6 9 1 5 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 dhw.extra extra boolean False binary_sensor.thermostat_dhw_extra binary_sensor.thermostat_dhw_extra 6 9 1 6 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 dhw.disinfecting disinfecting boolean True switch.thermostat_dhw_disinfecting switch.thermostat_dhw_disinfecting 6 9 1 7 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 dhw.disinfectday disinfection day enum [mo|tu|we|th|fr|sa|su|all] True select.thermostat_dhw_disinfection_day select.thermostat_dhw_disinfectday 6 9 1 8 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 dhw.disinfecttime disinfection time uint8 (>=0<=1431) minutes True number.thermostat_dhw_disinfection_time number.thermostat_dhw_disinfecttime 6 9 15 9 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 dhw.dailyheating daily heating boolean True switch.thermostat_dhw_daily_heating switch.thermostat_dhw_dailyheating 6 9 1 10 1
RC3*0, Moduline 3000/1010H, CW400, Sense II, HPC410 thermostat 158 dhw.dailyheattime daily heating time uint8 (>=0<=1431) minutes True number.thermostat_dhw_daily_heating_time number.thermostat_dhw_dailyheattime 6 9 15 11 1
RC100, CR10, Moduline 1000/1010 thermostat 165 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
RC100, CR10, Moduline 1000/1010 thermostat 165 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
RC100, CR10, Moduline 1000/1010 thermostat 165 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/2 0 1
RC100, CR10, Moduline 1000/1010 thermostat 165 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
RC100, CR10, Moduline 1000/1010 thermostat 165 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
RC100, CR10, Moduline 1000/1010 thermostat 165 hc1.mode operating mode enum [manual|auto] False sensor.thermostat_hc1_operating_mode sensor.thermostat_hc1_mode 6 1 1 3 1
RC100, CR10, Moduline 1000/1010 thermostat 165 hc1.targetflowtemp target flow temperature uint8 (>=0<=254) C False sensor.thermostat_hc1_target_flow_temperature sensor.thermostat_hc1_targetflowtemp 6 1 1 18 1
RC100, CR10, Moduline 1000/1010 thermostat 165 hc1.heatingtype heating type enum [off|radiator|convector|floor] True select.thermostat_hc1_heating_type select.thermostat_hc1_heatingtype 6 1 1 19 1
Rego 2000/3000 thermostat 172 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
Rego 2000/3000 thermostat 172 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
Rego 2000/3000 thermostat 172 datetime date/time string True sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
Rego 2000/3000 thermostat 172 intoffset internal temperature offset int8 (>=-12<=12) C True number.thermostat_internal_temperature_offset number.thermostat_intoffset 6 0 1/10 46 1
Rego 2000/3000 thermostat 172 floordry floor drying enum [off|start|heat|hold|cool|end] False sensor.thermostat_floor_drying sensor.thermostat_floordry 6 0 1 47 1
Rego 2000/3000 thermostat 172 dampedoutdoortemp damped outdoor temperature int16 (>=-3199<=3199) C False sensor.thermostat_damped_outdoor_temperature sensor.thermostat_dampedoutdoortemp 6 0 1/10 48 1
Rego 2000/3000 thermostat 172 floordrytemp floor drying temperature uint8 (>=0<=254) C False sensor.thermostat_floor_drying_temperature sensor.thermostat_floordrytemp 6 0 1 49 1
Rego 2000/3000 thermostat 172 building building type enum [light|medium|heavy] True select.thermostat_building_type select.thermostat_building 6 0 1 50 1
Rego 2000/3000 thermostat 172 minexttemp minimal external temperature int8 (>=-126<=126) C True number.thermostat_minimal_external_temperature number.thermostat_minexttemp 6 0 1 51 1
Rego 2000/3000 thermostat 172 damping damping outdoor temperature boolean True switch.thermostat_damping_outdoor_temperature switch.thermostat_damping 6 0 1 52 1
Rego 2000/3000 thermostat 172 solar solar boolean True switch.thermostat_solar switch.thermostat_solar 6 0 1 53 1
Rego 2000/3000 thermostat 172 vacations vacation dates string True sensor.thermostat_vacation_dates sensor.thermostat_vacations 6 0 1 76 13
Rego 2000/3000 thermostat 172 hybridstrategy hybrid control strategy enum [co2 optimized|cost optimized|outside temp switched|co2 cost mix] True select.thermostat_hybrid_control_strategy select.thermostat_hybridstrategy 6 0 1 54 1
Rego 2000/3000 thermostat 172 switchovertemp outside switchover temperature int8 (>=-20<=20) C True number.thermostat_outside_switchover_temperature number.thermostat_switchovertemp 6 0 1 55 1
Rego 2000/3000 thermostat 172 energycostratio energy cost ratio uint8 (>=0<=20) True number.thermostat_energy_cost_ratio number.thermostat_energycostratio 6 0 1/10 56 1
Rego 2000/3000 thermostat 172 fossilefactor fossile energy factor uint8 (>=0<=5) True number.thermostat_fossile_energy_factor number.thermostat_fossilefactor 6 0 1/10 57 1
Rego 2000/3000 thermostat 172 electricfactor electric energy factor uint8 (>=0<=5) True number.thermostat_electric_energy_factor number.thermostat_electricfactor 6 0 1/10 58 1
Rego 2000/3000 thermostat 172 delayboiler delay boiler support uint8 (>=5<=120) minutes True number.thermostat_delay_boiler_support number.thermostat_delayboiler 6 0 1 59 1
Rego 2000/3000 thermostat 172 tempdiffboiler temp diff boiler support uint8 (>=1<=99) C True number.thermostat_temp_diff_boiler_support number.thermostat_tempdiffboiler 6 0 1 60 1
Rego 2000/3000 thermostat 172 pvenabledhw enable raise dhw boolean True switch.thermostat_enable_raise_dhw switch.thermostat_pvenabledhw 6 0 1 61 1
Rego 2000/3000 thermostat 172 pvraiseheat raise heating with PV int8 (>=0<=5) K True number.thermostat_raise_heating_with_PV number.thermostat_pvraiseheat 6 0 1 62 1
Rego 2000/3000 thermostat 172 pvlowercool lower cooling with PV int8 (>=-5<=0) K True number.thermostat_lower_cooling_with_PV number.thermostat_pvlowercool 6 0 1 63 1
Rego 2000/3000 thermostat 172 absent absent boolean True switch.thermostat_absent switch.thermostat_absent 6 0 1 64 1
Rego 2000/3000 thermostat 172 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/2 0 1
Rego 2000/3000 thermostat 172 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
Rego 2000/3000 thermostat 172 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
Rego 2000/3000 thermostat 172 hc1.mode operating mode enum [manual|auto] True select.thermostat_hc1_operating_mode select.thermostat_hc1_mode 6 1 1 3 1
Rego 2000/3000 thermostat 172 hc1.modetype mode type enum [eco|comfort] False sensor.thermostat_hc1_mode_type sensor.thermostat_hc1_modetype 6 1 1 4 1
Rego 2000/3000 thermostat 172 hc1.ecotemp eco temperature uint8 (>=0<=127) C True number.thermostat_hc1_eco_temperature number.thermostat_hc1_ecotemp 6 1 1/2 5 1
Rego 2000/3000 thermostat 172 hc1.manualtemp manual temperature uint8 (>=0<=127) C True number.thermostat_hc1_manual_temperature number.thermostat_hc1_manualtemp 6 1 1/2 6 1
Rego 2000/3000 thermostat 172 hc1.comforttemp comfort temperature uint8 (>=0<=127) C True number.thermostat_hc1_comfort_temperature number.thermostat_hc1_comforttemp 6 1 1/2 7 1
Rego 2000/3000 thermostat 172 hc1.summertemp summer temperature uint8 (>=10<=30) C True number.thermostat_hc1_summer_temperature number.thermostat_hc1_summertemp 6 1 1 8 1
Rego 2000/3000 thermostat 172 hc1.designtemp design temperature uint8 (>=0<=254) C True number.thermostat_hc1_design_temperature number.thermostat_hc1_designtemp 6 1 1 9 1
Rego 2000/3000 thermostat 172 hc1.offsettemp offset temperature int8 (>=-126<=126) C True number.thermostat_hc1_offset_temperature number.thermostat_hc1_offsettemp 6 1 1 10 1
Rego 2000/3000 thermostat 172 hc1.minflowtemp min flow temperature uint8 (>=0<=254) C True number.thermostat_hc1_min_flow_temperature number.thermostat_hc1_minflowtemp 6 1 1 11 1
Rego 2000/3000 thermostat 172 hc1.maxflowtemp max flow temperature uint8 (>=0<=254) C True number.thermostat_hc1_max_flow_temperature number.thermostat_hc1_maxflowtemp 6 1 1 12 1
Rego 2000/3000 thermostat 172 hc1.roominfluence room influence uint8 (>=0<=254) C True number.thermostat_hc1_room_influence number.thermostat_hc1_roominfluence 6 1 1 13 1
Rego 2000/3000 thermostat 172 hc1.roominflfactor room influence factor uint8 (>=0<=25) True number.thermostat_hc1_room_influence_factor number.thermostat_hc1_roominflfactor 6 1 1/10 14 1
Rego 2000/3000 thermostat 172 hc1.curroominfl current room influence int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_influence sensor.thermostat_hc1_curroominfl 6 1 1/10 15 1
Rego 2000/3000 thermostat 172 hc1.nofrostmode nofrost mode enum [room|outdoor|room outdoor] True select.thermostat_hc1_nofrost_mode select.thermostat_hc1_nofrostmode 6 1 1 16 1
Rego 2000/3000 thermostat 172 hc1.nofrosttemp nofrost temperature int8 (>=-126<=126) C True number.thermostat_hc1_nofrost_temperature number.thermostat_hc1_nofrosttemp 6 1 1 17 1
Rego 2000/3000 thermostat 172 hc1.targetflowtemp target flow temperature uint8 (>=0<=254) C False sensor.thermostat_hc1_target_flow_temperature sensor.thermostat_hc1_targetflowtemp 6 1 1 18 1
Rego 2000/3000 thermostat 172 hc1.heatingtype heating type enum [off|radiator|convector|floor] True select.thermostat_hc1_heating_type select.thermostat_hc1_heatingtype 6 1 1 19 1
Rego 2000/3000 thermostat 172 hc1.summersetmode set summer mode enum [summer|auto|winter] True select.thermostat_hc1_set_summer_mode select.thermostat_hc1_summersetmode 6 1 1 20 1
Rego 2000/3000 thermostat 172 hc1.hpoperatingmode heatpump operating mode enum [off|auto|heating|cooling] True select.thermostat_hc1_heatpump_operating_mode select.thermostat_hc1_hpoperatingmode 6 1 1 21 1
Rego 2000/3000 thermostat 172 hc1.summermode summer mode enum [winter|summer] False sensor.thermostat_hc1_summer_mode sensor.thermostat_hc1_summermode 6 1 1 22 1
Rego 2000/3000 thermostat 172 hc1.hpoperatingstate heatpump operating state enum [heating|off|cooling] False sensor.thermostat_hc1_heatpump_operating_state sensor.thermostat_hc1_hpoperatingstate 6 1 1 23 1
Rego 2000/3000 thermostat 172 hc1.vacationmode vacation mode boolean False binary_sensor.thermostat_hc1_vacation_mode binary_sensor.thermostat_hc1_vacationmode 6 1 1 24 1
Rego 2000/3000 thermostat 172 hc1.controlmode control mode enum [weather compensated|outside basepoint|n/a|room|power|constant] True select.thermostat_hc1_control_mode select.thermostat_hc1_controlmode 6 1 1 25 1
Rego 2000/3000 thermostat 172 hc1.program program enum [prog 1|prog 2] True select.thermostat_hc1_program select.thermostat_hc1_program 6 1 1 26 1
Rego 2000/3000 thermostat 172 hc1.tempautotemp temporary set temperature automode int8 (>=-1<=30) C True number.thermostat_hc1_temporary_set_temperature_automode number.thermostat_hc1_tempautotemp 6 1 1/2 27 1
Rego 2000/3000 thermostat 172 hc1.cooltemp cooling temperature int8 (>=-1<=30) C True number.thermostat_hc1_cooling_temperature number.thermostat_hc1_cooltemp 6 1 1/2 28 1
Rego 2000/3000 thermostat 172 hc1.fastheatup fast heatup uint8 (>=0<=100) % True number.thermostat_hc1_fast_heatup number.thermostat_hc1_fastheatup 6 1 1 29 1
Rego 2000/3000 thermostat 172 hc1.switchonoptimization switch-on optimization boolean True switch.thermostat_hc1_switch-on_optimization switch.thermostat_hc1_switchonoptimization 6 1 1 30 1
Rego 2000/3000 thermostat 172 hc1.reducemode reduce mode enum [outdoor|room|reduce] True select.thermostat_hc1_reduce_mode select.thermostat_hc1_reducemode 6 1 1 31 1
Rego 2000/3000 thermostat 172 hc1.noreducetemp no reduce below temperature int8 (>=-126<=126) C True number.thermostat_hc1_no_reduce_below_temperature number.thermostat_hc1_noreducetemp 6 1 1 32 1
Rego 2000/3000 thermostat 172 hc1.reducetemp off/reduce switch temperature int8 (>=-126<=126) C True number.thermostat_hc1_off/reduce_switch_temperature number.thermostat_hc1_reducetemp 6 1 1 33 1
Rego 2000/3000 thermostat 172 hc1.dhwprio dhw priority boolean True switch.thermostat_hc1_dhw_priority switch.thermostat_hc1_dhwprio 6 1 1 34 1
Rego 2000/3000 thermostat 172 hc1.hpcooling hp cooling boolean True switch.thermostat_hc1_hp_cooling switch.thermostat_hc1_hpcooling 6 1 1 35 1
Rego 2000/3000 thermostat 172 hc1.coolingon cooling on boolean False binary_sensor.thermostat_hc1_cooling_on binary_sensor.thermostat_hc1_coolingon 6 1 1 36 1
Rego 2000/3000 thermostat 172 hc1.hpmode HP Mode enum [heating|cooling|heating & cooling] True select.thermostat_hc1_HP_Mode select.thermostat_hc1_hpmode 6 1 1 37 1
Rego 2000/3000 thermostat 172 hc1.dewoffset dew point offset uint8 (>=2<=10) K True number.thermostat_hc1_dew_point_offset number.thermostat_hc1_dewoffset 6 1 1 38 1
Rego 2000/3000 thermostat 172 hc1.roomtempdiff room temp difference uint8 (>=0<=254) K True number.thermostat_hc1_room_temp_difference number.thermostat_hc1_roomtempdiff 6 1 1 39 1
Rego 2000/3000 thermostat 172 hc1.hpminflowtemp HP min. flow temp. uint8 (>=0<=254) C True number.thermostat_hc1_HP_min._flow_temp. number.thermostat_hc1_hpminflowtemp 6 1 1 40 1
Rego 2000/3000 thermostat 172 hc1.control control device enum [RC310|RC200|RC100|RC100H|TC100] True select.thermostat_hc1_control_device select.thermostat_hc1_control 6 1 1 41 1
Rego 2000/3000 thermostat 172 hc1.remotetemp room temperature from remote cmd [] (>=-1<=101) C True sensor.thermostat_hc1_room_temperature_from_remote sensor.thermostat_hc1_remotetemp 6 1 1/10 42 1
Rego 2000/3000 thermostat 172 hc1.remotehum room humidity from remote cmd [] (>=-1<=101) % True sensor.thermostat_hc1_room_humidity_from_remote sensor.thermostat_hc1_remotehum 6 1 1 43 1
Rego 2000/3000 thermostat 172 hc1.heatondelay heat-on delay uint8 (>=1<=48) hours True number.thermostat_hc1_heat-on_delay number.thermostat_hc1_heatondelay 6 1 1 44 1
Rego 2000/3000 thermostat 172 hc1.heatoffdelay heat-off delay uint8 (>=1<=48) hours True number.thermostat_hc1_heat-off_delay number.thermostat_hc1_heatoffdelay 6 1 1 45 1
Rego 2000/3000 thermostat 172 hc1.instantstart instant start uint8 (>=1<=10) K True number.thermostat_hc1_instant_start number.thermostat_hc1_instantstart 6 1 1 46 1
Rego 2000/3000 thermostat 172 hc1.boost boost mode boolean True switch.thermostat_hc1_boost_mode switch.thermostat_hc1_boost 6 1 1 47 1
Rego 2000/3000 thermostat 172 hc1.boosttime boost time uint8 (>=0<=254) hours True number.thermostat_hc1_boost_time number.thermostat_hc1_boosttime 6 1 1 48 1
Rego 2000/3000 thermostat 172 hc1.coolstart cooling starttemp uint8 (>=20<=35) C True number.thermostat_hc1_cooling_starttemp number.thermostat_hc1_coolstart 6 1 1 49 1
Rego 2000/3000 thermostat 172 hc1.coolondelay cooling on delay uint8 (>=1<=48) hours True number.thermostat_hc1_cooling_on_delay number.thermostat_hc1_coolondelay 6 1 1 50 1
Rego 2000/3000 thermostat 172 hc1.cooloffdelay cooling off delay uint8 (>=1<=48) hours True number.thermostat_hc1_cooling_off_delay number.thermostat_hc1_cooloffdelay 6 1 1 51 1
Rego 2000/3000 thermostat 172 hc1.switchprogmode switch program mode enum [level|absolute] True select.thermostat_hc1_switch_program_mode select.thermostat_hc1_switchprogmode 6 1 1 52 1
Rego 2000/3000 thermostat 172 hc1.redthreshold reduction threshold int8 (>=12<=22) C True number.thermostat_hc1_reduction_threshold number.thermostat_hc1_redthreshold 6 1 1/2 53 1
Rego 2000/3000 thermostat 172 hc1.solarinfl solar influence uint8 (>=-5<=4294967295) C True number.thermostat_hc1_solar_influence number.thermostat_hc1_solarinfl 6 1 1 54 1
Rego 2000/3000 thermostat 172 hc1.currsolarinfl curent solar influence uint8 (>=0<=25) C False sensor.thermostat_hc1_curent_solar_influence sensor.thermostat_hc1_currsolarinfl 6 1 1/10 55 1
Rego 2000/3000 thermostat 172 dhw.mode operating mode enum [normal|comfort|eco+] True select.thermostat_dhw_operating_mode select.thermostat_dhw_mode 6 9 1 0 1
Rego 2000/3000 thermostat 172 dhw.settemp set temperature uint8 (>=0<=254) C True number.thermostat_dhw_set_temperature number.thermostat_dhw_settemp 6 9 1 1 1
Rego 2000/3000 thermostat 172 dhw.settemplow set low temperature uint8 (>=0<=254) C True number.thermostat_dhw_set_low_temperature number.thermostat_dhw_settemplow 6 9 1 2 1
Rego 2000/3000 thermostat 172 dhw.circmode circulation pump mode enum [off|on|auto|own prog] True select.thermostat_dhw_circulation_pump_mode select.thermostat_dhw_circmode 6 9 1 3 1
Rego 2000/3000 thermostat 172 dhw.chargeduration charge duration uint8 (>=0<=3810) minutes True number.thermostat_dhw_charge_duration number.thermostat_dhw_chargeduration 6 9 15 4 1
Rego 2000/3000 thermostat 172 dhw.charge charge boolean True switch.thermostat_dhw_charge switch.thermostat_dhw_charge 6 9 1 5 1
Rego 2000/3000 thermostat 172 dhw.extra extra boolean False binary_sensor.thermostat_dhw_extra binary_sensor.thermostat_dhw_extra 6 9 1 6 1
Rego 2000/3000 thermostat 172 dhw.disinfecting disinfecting boolean True switch.thermostat_dhw_disinfecting switch.thermostat_dhw_disinfecting 6 9 1 7 1
Rego 2000/3000 thermostat 172 dhw.disinfectday disinfection day enum [mo|tu|we|th|fr|sa|su|all] True select.thermostat_dhw_disinfection_day select.thermostat_dhw_disinfectday 6 9 1 8 1
Rego 2000/3000 thermostat 172 dhw.disinfecttime disinfection time uint8 (>=0<=1431) minutes True number.thermostat_dhw_disinfection_time number.thermostat_dhw_disinfecttime 6 9 15 9 1
Rego 2000/3000 thermostat 172 dhw.dailyheating daily heating boolean True switch.thermostat_dhw_daily_heating switch.thermostat_dhw_dailyheating 6 9 1 10 1
Rego 2000/3000 thermostat 172 dhw.dailyheattime daily heating time uint8 (>=0<=1431) minutes True number.thermostat_dhw_daily_heating_time number.thermostat_dhw_dailyheattime 6 9 15 11 1
Comfort RF thermostat 215 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
Comfort RF thermostat 215 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
Comfort RF thermostat 215 datetime date/time string False sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
Comfort RF thermostat 215 hc1.seltemp selected room temperature int16 (>=-15999<=15999) C False sensor.thermostat_hc1_selected_room_temperature sensor.thermostat_hc1_seltemp 6 1 1/2 0 1
Comfort RF thermostat 215 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
Comfort RF thermostat 215 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
Comfort RF thermostat 215 hc1.mode operating mode enum [auto|off] False sensor.thermostat_hc1_operating_mode sensor.thermostat_hc1_mode 6 1 1 3 1
Comfort RF thermostat 215 hc1.modetype mode type enum [off|on] False sensor.thermostat_hc1_mode_type sensor.thermostat_hc1_modetype 6 1 1 4 1
Comfort RF thermostat 215 hc1.targetflowtemp target flow temperature uint8 (>=0<=254) C False sensor.thermostat_hc1_target_flow_temperature sensor.thermostat_hc1_targetflowtemp 6 1 1 18 1
CRF200S thermostat 216 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
CRF200S thermostat 216 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
CRF200S thermostat 216 datetime date/time string False sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
CRF200S thermostat 216 hc1.seltemp selected room temperature int16 (>=-15999<=15999) C False sensor.thermostat_hc1_selected_room_temperature sensor.thermostat_hc1_seltemp 6 1 1/2 0 1
CRF200S thermostat 216 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
CRF200S thermostat 216 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
CRF200S thermostat 216 hc1.mode operating mode enum [auto|off] False sensor.thermostat_hc1_operating_mode sensor.thermostat_hc1_mode 6 1 1 3 1
CRF200S thermostat 216 hc1.modetype mode type enum [off|on] False sensor.thermostat_hc1_mode_type sensor.thermostat_hc1_modetype 6 1 1 4 1
CRF200S thermostat 216 hc1.targetflowtemp target flow temperature uint8 (>=0<=254) C False sensor.thermostat_hc1_target_flow_temperature sensor.thermostat_hc1_targetflowtemp 6 1 1 18 1
Comfort+2RF thermostat 246 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
Comfort+2RF thermostat 246 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
Comfort+2RF thermostat 246 datetime date/time string False sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
Comfort+2RF thermostat 246 hc1.seltemp selected room temperature int16 (>=-15999<=15999) C False sensor.thermostat_hc1_selected_room_temperature sensor.thermostat_hc1_seltemp 6 1 1/2 0 1
Comfort+2RF thermostat 246 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
Comfort+2RF thermostat 246 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
Comfort+2RF thermostat 246 hc1.mode operating mode enum [auto|off] False sensor.thermostat_hc1_operating_mode sensor.thermostat_hc1_mode 6 1 1 3 1
Comfort+2RF thermostat 246 hc1.modetype mode type enum [off|on] False sensor.thermostat_hc1_mode_type sensor.thermostat_hc1_modetype 6 1 1 4 1
Comfort+2RF thermostat 246 hc1.targetflowtemp target flow temperature uint8 (>=0<=254) C False sensor.thermostat_hc1_target_flow_temperature sensor.thermostat_hc1_targetflowtemp 6 1 1 18 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
Rego 3000, UI800, Logamatic BC400 thermostat 253 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
Rego 3000, UI800, Logamatic BC400 thermostat 253 datetime date/time string True sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
Rego 3000, UI800, Logamatic BC400 thermostat 253 intoffset internal temperature offset int8 (>=-12<=12) C True number.thermostat_internal_temperature_offset number.thermostat_intoffset 6 0 1/10 46 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 floordry floor drying enum [off|start|heat|hold|cool|end] False sensor.thermostat_floor_drying sensor.thermostat_floordry 6 0 1 47 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 dampedoutdoortemp damped outdoor temperature int16 (>=-3199<=3199) C False sensor.thermostat_damped_outdoor_temperature sensor.thermostat_dampedoutdoortemp 6 0 1/10 48 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 floordrytemp floor drying temperature uint8 (>=0<=254) C False sensor.thermostat_floor_drying_temperature sensor.thermostat_floordrytemp 6 0 1 49 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 building building type enum [light|medium|heavy] True select.thermostat_building_type select.thermostat_building 6 0 1 50 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 minexttemp minimal external temperature int8 (>=-126<=126) C True number.thermostat_minimal_external_temperature number.thermostat_minexttemp 6 0 1 51 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 damping damping outdoor temperature boolean True switch.thermostat_damping_outdoor_temperature switch.thermostat_damping 6 0 1 52 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 solar solar boolean True switch.thermostat_solar switch.thermostat_solar 6 0 1 53 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hybridstrategy hybrid control strategy enum [co2 optimized|cost optimized|outside temp switched|co2 cost mix] True select.thermostat_hybrid_control_strategy select.thermostat_hybridstrategy 6 0 1 54 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 switchovertemp outside switchover temperature int8 (>=-20<=20) C True number.thermostat_outside_switchover_temperature number.thermostat_switchovertemp 6 0 1 55 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 energycostratio energy cost ratio uint8 (>=0<=20) True number.thermostat_energy_cost_ratio number.thermostat_energycostratio 6 0 1/10 56 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 fossilefactor fossile energy factor uint8 (>=0<=5) True number.thermostat_fossile_energy_factor number.thermostat_fossilefactor 6 0 1/10 57 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 electricfactor electric energy factor uint8 (>=0<=5) True number.thermostat_electric_energy_factor number.thermostat_electricfactor 6 0 1/10 58 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 delayboiler delay boiler support uint8 (>=5<=120) minutes True number.thermostat_delay_boiler_support number.thermostat_delayboiler 6 0 1 59 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 tempdiffboiler temp diff boiler support uint8 (>=1<=99) C True number.thermostat_temp_diff_boiler_support number.thermostat_tempdiffboiler 6 0 1 60 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 pvenabledhw enable raise dhw boolean True switch.thermostat_enable_raise_dhw switch.thermostat_pvenabledhw 6 0 1 61 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 pvraiseheat raise heating with PV int8 (>=0<=5) K True number.thermostat_raise_heating_with_PV number.thermostat_pvraiseheat 6 0 1 62 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 pvlowercool lower cooling with PV int8 (>=-5<=0) K True number.thermostat_lower_cooling_with_PV number.thermostat_pvlowercool 6 0 1 63 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 absent absent boolean True switch.thermostat_absent switch.thermostat_absent 6 0 1 64 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/2 0 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.mode operating mode enum [off|manual|auto] True select.thermostat_hc1_operating_mode select.thermostat_hc1_mode 6 1 1 3 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.modetype mode type enum [eco|comfort] False sensor.thermostat_hc1_mode_type sensor.thermostat_hc1_modetype 6 1 1 4 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.ecotemp eco temperature uint8 (>=0<=127) C True number.thermostat_hc1_eco_temperature number.thermostat_hc1_ecotemp 6 1 1/2 5 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.manualtemp manual temperature uint8 (>=0<=127) C True number.thermostat_hc1_manual_temperature number.thermostat_hc1_manualtemp 6 1 1/2 6 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.comforttemp comfort temperature uint8 (>=0<=127) C True number.thermostat_hc1_comfort_temperature number.thermostat_hc1_comforttemp 6 1 1/2 7 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.summertemp summer temperature uint8 (>=10<=30) C True number.thermostat_hc1_summer_temperature number.thermostat_hc1_summertemp 6 1 1 8 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.designtemp design temperature uint8 (>=0<=254) C True number.thermostat_hc1_design_temperature number.thermostat_hc1_designtemp 6 1 1 9 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.offsettemp offset temperature int8 (>=-126<=126) C True number.thermostat_hc1_offset_temperature number.thermostat_hc1_offsettemp 6 1 1 10 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.minflowtemp min flow temperature uint8 (>=0<=254) C True number.thermostat_hc1_min_flow_temperature number.thermostat_hc1_minflowtemp 6 1 1 11 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.maxflowtemp max flow temperature uint8 (>=0<=254) C True number.thermostat_hc1_max_flow_temperature number.thermostat_hc1_maxflowtemp 6 1 1 12 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.roominfluence room influence uint8 (>=0<=254) C True number.thermostat_hc1_room_influence number.thermostat_hc1_roominfluence 6 1 1 13 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.roominflfactor room influence factor uint8 (>=0<=25) True number.thermostat_hc1_room_influence_factor number.thermostat_hc1_roominflfactor 6 1 1/10 14 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.curroominfl current room influence int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_influence sensor.thermostat_hc1_curroominfl 6 1 1/10 15 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.nofrostmode nofrost mode enum [room|outdoor|room outdoor] True select.thermostat_hc1_nofrost_mode select.thermostat_hc1_nofrostmode 6 1 1 16 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.nofrosttemp nofrost temperature int8 (>=-126<=126) C True number.thermostat_hc1_nofrost_temperature number.thermostat_hc1_nofrosttemp 6 1 1 17 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.targetflowtemp target flow temperature uint8 (>=0<=254) C False sensor.thermostat_hc1_target_flow_temperature sensor.thermostat_hc1_targetflowtemp 6 1 1 18 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.heatingtype heating type enum [off|radiator|convector|floor] True select.thermostat_hc1_heating_type select.thermostat_hc1_heatingtype 6 1 1 19 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.summersetmode set summer mode enum [summer|auto|winter] True select.thermostat_hc1_set_summer_mode select.thermostat_hc1_summersetmode 6 1 1 20 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.hpoperatingmode heatpump operating mode enum [off|auto|heating|cooling] True select.thermostat_hc1_heatpump_operating_mode select.thermostat_hc1_hpoperatingmode 6 1 1 21 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.summermode summer mode enum [winter|summer] False sensor.thermostat_hc1_summer_mode sensor.thermostat_hc1_summermode 6 1 1 22 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.hpoperatingstate heatpump operating state enum [heating|off|cooling] False sensor.thermostat_hc1_heatpump_operating_state sensor.thermostat_hc1_hpoperatingstate 6 1 1 23 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.vacationmode vacation mode boolean False binary_sensor.thermostat_hc1_vacation_mode binary_sensor.thermostat_hc1_vacationmode 6 1 1 24 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.controlmode control mode enum [weather compensated|outside basepoint|n/a|room|power|constant] True select.thermostat_hc1_control_mode select.thermostat_hc1_controlmode 6 1 1 25 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.program program enum [prog 1|prog 2] True select.thermostat_hc1_program select.thermostat_hc1_program 6 1 1 26 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.tempautotemp temporary set temperature automode int8 (>=-1<=30) C True number.thermostat_hc1_temporary_set_temperature_automode number.thermostat_hc1_tempautotemp 6 1 1/2 27 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.cooltemp cooling temperature int8 (>=-1<=30) C True number.thermostat_hc1_cooling_temperature number.thermostat_hc1_cooltemp 6 1 1/2 28 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.fastheatup fast heatup uint8 (>=0<=100) % True number.thermostat_hc1_fast_heatup number.thermostat_hc1_fastheatup 6 1 1 29 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.switchonoptimization switch-on optimization boolean True switch.thermostat_hc1_switch-on_optimization switch.thermostat_hc1_switchonoptimization 6 1 1 30 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.reducemode reduce mode enum [outdoor|room|reduce] True select.thermostat_hc1_reduce_mode select.thermostat_hc1_reducemode 6 1 1 31 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.noreducetemp no reduce below temperature int8 (>=-126<=126) C True number.thermostat_hc1_no_reduce_below_temperature number.thermostat_hc1_noreducetemp 6 1 1 32 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.reducetemp off/reduce switch temperature int8 (>=-126<=126) C True number.thermostat_hc1_off/reduce_switch_temperature number.thermostat_hc1_reducetemp 6 1 1 33 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.dhwprio dhw priority boolean True switch.thermostat_hc1_dhw_priority switch.thermostat_hc1_dhwprio 6 1 1 34 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.hpcooling hp cooling boolean True switch.thermostat_hc1_hp_cooling switch.thermostat_hc1_hpcooling 6 1 1 35 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.coolingon cooling on boolean False binary_sensor.thermostat_hc1_cooling_on binary_sensor.thermostat_hc1_coolingon 6 1 1 36 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.hpmode HP Mode enum [heating|cooling|heating & cooling] True select.thermostat_hc1_HP_Mode select.thermostat_hc1_hpmode 6 1 1 37 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.dewoffset dew point offset uint8 (>=2<=10) K True number.thermostat_hc1_dew_point_offset number.thermostat_hc1_dewoffset 6 1 1 38 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.roomtempdiff room temp difference uint8 (>=0<=254) K True number.thermostat_hc1_room_temp_difference number.thermostat_hc1_roomtempdiff 6 1 1 39 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.hpminflowtemp HP min. flow temp. uint8 (>=0<=254) C True number.thermostat_hc1_HP_min._flow_temp. number.thermostat_hc1_hpminflowtemp 6 1 1 40 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.control control device enum [off|-|RC100|RC100H|-|RC120RF|RC220/RT800|single] True select.thermostat_hc1_control_device select.thermostat_hc1_control 6 1 1 41 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.remotetemp room temperature from remote cmd [] (>=-1<=101) C True sensor.thermostat_hc1_room_temperature_from_remote sensor.thermostat_hc1_remotetemp 6 1 1/10 42 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.remotehum room humidity from remote cmd [] (>=-1<=101) % True sensor.thermostat_hc1_room_humidity_from_remote sensor.thermostat_hc1_remotehum 6 1 1 43 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.heatondelay heat-on delay uint8 (>=1<=48) hours True number.thermostat_hc1_heat-on_delay number.thermostat_hc1_heatondelay 6 1 1 44 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.heatoffdelay heat-off delay uint8 (>=1<=48) hours True number.thermostat_hc1_heat-off_delay number.thermostat_hc1_heatoffdelay 6 1 1 45 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.instantstart instant start uint8 (>=1<=10) K True number.thermostat_hc1_instant_start number.thermostat_hc1_instantstart 6 1 1 46 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.boost boost mode boolean True switch.thermostat_hc1_boost_mode switch.thermostat_hc1_boost 6 1 1 47 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.boosttime boost time uint8 (>=0<=254) hours True number.thermostat_hc1_boost_time number.thermostat_hc1_boosttime 6 1 1 48 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.coolstart cooling starttemp uint8 (>=20<=35) C True number.thermostat_hc1_cooling_starttemp number.thermostat_hc1_coolstart 6 1 1 49 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.coolondelay cooling on delay uint8 (>=1<=48) hours True number.thermostat_hc1_cooling_on_delay number.thermostat_hc1_coolondelay 6 1 1 50 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.cooloffdelay cooling off delay uint8 (>=1<=48) hours True number.thermostat_hc1_cooling_off_delay number.thermostat_hc1_cooloffdelay 6 1 1 51 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.switchprogmode switch program mode enum [level|absolute] True select.thermostat_hc1_switch_program_mode select.thermostat_hc1_switchprogmode 6 1 1 52 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.redthreshold reduction threshold int8 (>=12<=22) C True number.thermostat_hc1_reduction_threshold number.thermostat_hc1_redthreshold 6 1 1/2 53 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.solarinfl solar influence uint8 (>=-5<=4294967295) C True number.thermostat_hc1_solar_influence number.thermostat_hc1_solarinfl 6 1 1 54 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 hc1.currsolarinfl curent solar influence uint8 (>=0<=25) C False sensor.thermostat_hc1_curent_solar_influence sensor.thermostat_hc1_currsolarinfl 6 1 1/10 55 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 dhw.mode operating mode enum [off|eco+|eco|comfort|auto] True select.thermostat_dhw_operating_mode select.thermostat_dhw_mode 6 9 1 0 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 dhw.settemp set temperature uint8 (>=0<=254) C True number.thermostat_dhw_set_temperature number.thermostat_dhw_settemp 6 9 1 1 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 dhw.settemplow set low temperature uint8 (>=0<=254) C True number.thermostat_dhw_set_low_temperature number.thermostat_dhw_settemplow 6 9 1 2 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 dhw.circmode circulation pump mode enum [off|on|auto|own prog] True select.thermostat_dhw_circulation_pump_mode select.thermostat_dhw_circmode 6 9 1 3 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 dhw.chargeduration charge duration uint8 (>=0<=3810) minutes True number.thermostat_dhw_charge_duration number.thermostat_dhw_chargeduration 6 9 15 4 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 dhw.charge charge boolean True switch.thermostat_dhw_charge switch.thermostat_dhw_charge 6 9 1 5 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 dhw.extra extra boolean False binary_sensor.thermostat_dhw_extra binary_sensor.thermostat_dhw_extra 6 9 1 6 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 dhw.disinfecting disinfecting boolean True switch.thermostat_dhw_disinfecting switch.thermostat_dhw_disinfecting 6 9 1 7 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 dhw.disinfectday disinfection day enum [mo|tu|we|th|fr|sa|su|all] True select.thermostat_dhw_disinfection_day select.thermostat_dhw_disinfectday 6 9 1 8 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 dhw.disinfecttime disinfection time uint8 (>=0<=1431) minutes True number.thermostat_dhw_disinfection_time number.thermostat_dhw_disinfecttime 6 9 15 9 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 dhw.dailyheating daily heating boolean True switch.thermostat_dhw_daily_heating switch.thermostat_dhw_dailyheating 6 9 1 10 1
Rego 3000, UI800, Logamatic BC400 thermostat 253 dhw.dailyheattime daily heating time uint8 (>=0<=1431) minutes True number.thermostat_dhw_daily_heating_time number.thermostat_dhw_dailyheattime 6 9 15 11 1
ES72, RC20 thermostat 66 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
ES72, RC20 thermostat 66 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
ES72, RC20 thermostat 66 datetime date/time string False sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
ES72, RC20 thermostat 66 minexttemp minimal external temperature int8 (>=-126<=126) C True number.thermostat_minimal_external_temperature number.thermostat_minexttemp 6 0 1 51 1
ES72, RC20 thermostat 66 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/2 0 1
ES72, RC20 thermostat 66 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
ES72, RC20 thermostat 66 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
ES72, RC20 thermostat 66 hc1.mode operating mode enum [night|day|auto] True select.thermostat_hc1_operating_mode select.thermostat_hc1_mode 6 1 1 3 1
ES72, RC20 thermostat 66 hc1.modetype mode type enum [night|day] False sensor.thermostat_hc1_mode_type sensor.thermostat_hc1_modetype 6 1 1 4 1
ES72, RC20 thermostat 66 hc1.daytemp day temperature uint8 (>=0<=127) C True number.thermostat_hc1_day_temperature number.thermostat_hc1_daytemp 6 1 1/2 56 1
ES72, RC20 thermostat 66 hc1.nighttemp night temperature uint8 (>=0<=127) C True number.thermostat_hc1_night_temperature number.thermostat_hc1_nighttemp 6 1 1/2 57 1
ES72, RC20 thermostat 66 hc1.program program enum [family|morning|evening|am|pm|midday|singles|seniors] True select.thermostat_hc1_program select.thermostat_hc1_program 6 1 1 26 1
ES72, RC20 thermostat 66 hc1.minflowtemp min flow temperature uint8 (>=0<=254) C True number.thermostat_hc1_min_flow_temperature number.thermostat_hc1_minflowtemp 6 1 1 11 1
ES72, RC20 thermostat 66 hc1.maxflowtemp max flow temperature uint8 (>=0<=254) C True number.thermostat_hc1_max_flow_temperature number.thermostat_hc1_maxflowtemp 6 1 1 12 1
ES72, RC20 thermostat 66 hc1.tempautotemp temporary set temperature automode uint8 (>=0<=127) C True number.thermostat_hc1_temporary_set_temperature_automode number.thermostat_hc1_tempautotemp 6 1 1/2 27 1
ES72, RC20 thermostat 66 hc1.heatingtype heating type enum [off|radiator|convector|floor] True select.thermostat_hc1_heating_type select.thermostat_hc1_heatingtype 6 1 1 19 1
ES72, RC20 thermostat 66 hc1.summertemp summer temperature uint8 (>=10<=30) C True number.thermostat_hc1_summer_temperature number.thermostat_hc1_summertemp 6 1 1 8 1
ES72, RC20 thermostat 66 hc1.summermode summer mode enum [winter|summer] False sensor.thermostat_hc1_summer_mode sensor.thermostat_hc1_summermode 6 1 1 22 1
ES73 thermostat 76 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
ES73 thermostat 76 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
ES73 thermostat 76 datetime date/time string False sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
ES73 thermostat 76 display display enum [internal temperature|internal setpoint|external temperature|burner temperature|dhw temperature|functioning mode|time|date|smoke temperature] True select.thermostat_display select.thermostat_display 6 0 1 65 1
ES73 thermostat 76 language language enum [german|dutch|french|italian] False sensor.thermostat_language sensor.thermostat_language 6 0 1 66 1
ES73 thermostat 76 clockoffset clock offset int8 (>=-126<=126) seconds True number.thermostat_clock_offset number.thermostat_clockoffset 6 0 1 67 1
ES73 thermostat 76 intoffset internal temperature offset int8 (>=-12<=12) C True number.thermostat_internal_temperature_offset number.thermostat_intoffset 6 0 1/10 46 1
ES73 thermostat 76 minexttemp minimal external temperature int8 (>=-126<=126) C True number.thermostat_minimal_external_temperature number.thermostat_minexttemp 6 0 1 51 1
ES73 thermostat 76 inttemp1 temperature sensor 1 int16 (>=-3199<=3199) C False sensor.thermostat_temperature_sensor_1 sensor.thermostat_inttemp1 6 0 1/10 68 1
ES73 thermostat 76 inttemp2 temperature sensor 2 int16 (>=-3199<=3199) C False sensor.thermostat_temperature_sensor_2 sensor.thermostat_inttemp2 6 0 1/10 69 1
ES73 thermostat 76 damping damping outdoor temperature boolean True switch.thermostat_damping_outdoor_temperature switch.thermostat_damping 6 0 1 52 1
ES73 thermostat 76 dampedoutdoortemp damped outdoor temperature int8 (>=-126<=126) C False sensor.thermostat_damped_outdoor_temperature sensor.thermostat_dampedoutdoortemp 6 0 1 48 1
ES73 thermostat 76 building building type enum [light|medium|heavy] True select.thermostat_building_type select.thermostat_building 6 0 1 50 1
ES73 thermostat 76 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/2 0 1
ES73 thermostat 76 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
ES73 thermostat 76 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
ES73 thermostat 76 hc1.mode operating mode enum [night|day|auto] True select.thermostat_hc1_operating_mode select.thermostat_hc1_mode 6 1 1 3 1
ES73 thermostat 76 hc1.modetype mode type enum [night|day] False sensor.thermostat_hc1_mode_type sensor.thermostat_hc1_modetype 6 1 1 4 1
ES73 thermostat 76 hc1.daytemp day temperature uint8 (>=10<=30) C True number.thermostat_hc1_day_temperature number.thermostat_hc1_daytemp 6 1 1/2 56 1
ES73 thermostat 76 hc1.nighttemp night temperature uint8 (>=10<=30) C True number.thermostat_hc1_night_temperature number.thermostat_hc1_nighttemp 6 1 1/2 57 1
ES73 thermostat 76 hc1.designtemp design temperature uint8 (>=30<=90) C True number.thermostat_hc1_design_temperature number.thermostat_hc1_designtemp 6 1 1 9 1
ES73 thermostat 76 hc1.offsettemp offset temperature int8 (>=-5<=5) C True number.thermostat_hc1_offset_temperature number.thermostat_hc1_offsettemp 6 1 1/2 10 1
ES73 thermostat 76 hc1.holidaytemp holiday temperature uint8 (>=5<=30) C True number.thermostat_hc1_holiday_temperature number.thermostat_hc1_holidaytemp 6 1 1/2 58 1
ES73 thermostat 76 hc1.targetflowtemp target flow temperature uint8 (>=0<=254) C False sensor.thermostat_hc1_target_flow_temperature sensor.thermostat_hc1_targetflowtemp 6 1 1 18 1
ES73 thermostat 76 hc1.summertemp summer temperature uint8 (>=9<=25) C True number.thermostat_hc1_summer_temperature number.thermostat_hc1_summertemp 6 1 1 8 1
ES73 thermostat 76 hc1.summermode summer mode enum [winter|summer] False sensor.thermostat_hc1_summer_mode sensor.thermostat_hc1_summermode 6 1 1 22 1
ES73 thermostat 76 hc1.holidaymode holiday mode boolean False binary_sensor.thermostat_hc1_holiday_mode binary_sensor.thermostat_hc1_holidaymode 6 1 1 59 1
ES73 thermostat 76 hc1.nofrosttemp nofrost temperature int8 (>=-20<=10) C True number.thermostat_hc1_nofrost_temperature number.thermostat_hc1_nofrosttemp 6 1 1 17 1
ES73 thermostat 76 hc1.nofrostmode nofrost mode enum [off|outdoor|room] True select.thermostat_hc1_nofrost_mode select.thermostat_hc1_nofrostmode 6 1 1 16 1
ES73 thermostat 76 hc1.roominfluence room influence uint8 (>=0<=10) C True number.thermostat_hc1_room_influence number.thermostat_hc1_roominfluence 6 1 1 13 1
ES73 thermostat 76 hc1.minflowtemp min flow temperature uint8 (>=5<=70) C True number.thermostat_hc1_min_flow_temperature number.thermostat_hc1_minflowtemp 6 1 1 11 1
ES73 thermostat 76 hc1.maxflowtemp max flow temperature uint8 (>=30<=90) C True number.thermostat_hc1_max_flow_temperature number.thermostat_hc1_maxflowtemp 6 1 1 12 1
ES73 thermostat 76 hc1.flowtempoffset flow temperature offset for mixer uint8 (>=0<=20) C True number.thermostat_hc1_flow_temperature_offset_for_mixer number.thermostat_hc1_flowtempoffset 6 1 1 60 1
ES73 thermostat 76 hc1.heatingtype heating type enum [off|radiator|convector|floor] True select.thermostat_hc1_heating_type select.thermostat_hc1_heatingtype 6 1 1 19 1
ES73 thermostat 76 hc1.reducemode reduce mode enum [nofrost|reduce|room|outdoor] True select.thermostat_hc1_reduce_mode select.thermostat_hc1_reducemode 6 1 1 31 1
ES73 thermostat 76 hc1.controlmode control mode enum [outdoor|room] True select.thermostat_hc1_control_mode select.thermostat_hc1_controlmode 6 1 1 25 1
ES73 thermostat 76 hc1.control control device enum [off|RC20|RC3x] True select.thermostat_hc1_control_device select.thermostat_hc1_control 6 1 1 41 1
ES73 thermostat 76 hc1.holidays holiday dates string True sensor.thermostat_hc1_holiday_dates sensor.thermostat_hc1_holidays 6 1 1 61 13
ES73 thermostat 76 hc1.vacations vacation dates string True sensor.thermostat_hc1_vacation_dates sensor.thermostat_hc1_vacations 6 1 1 74 13
ES73 thermostat 76 hc1.program program enum [own 1|family|morning|evening|am|pm|midday|singles|seniors|new|own 2] True select.thermostat_hc1_program select.thermostat_hc1_program 6 1 1 26 1
ES73 thermostat 76 hc1.pause pause time uint8 (>=0<=99) hours True number.thermostat_hc1_pause_time number.thermostat_hc1_pause 6 1 1 87 1
ES73 thermostat 76 hc1.party party time uint8 (>=0<=99) hours True number.thermostat_hc1_party_time number.thermostat_hc1_party 6 1 1 88 1
ES73 thermostat 76 hc1.tempautotemp temporary set temperature automode uint8 (>=0<=30) C True number.thermostat_hc1_temporary_set_temperature_automode number.thermostat_hc1_tempautotemp 6 1 1/2 27 1
ES73 thermostat 76 hc1.noreducetemp no reduce below temperature int8 (>=-31<=10) C True number.thermostat_hc1_no_reduce_below_temperature number.thermostat_hc1_noreducetemp 6 1 1 32 1
ES73 thermostat 76 hc1.reducetemp off/reduce switch temperature int8 (>=-20<=10) C True number.thermostat_hc1_off/reduce_switch_temperature number.thermostat_hc1_reducetemp 6 1 1 33 1
ES73 thermostat 76 hc1.vacreducetemp vacations off/reduce switch temperature int8 (>=-20<=10) C True number.thermostat_hc1_vacations_off/reduce_switch_temperature number.thermostat_hc1_vacreducetemp 6 1 1 89 1
ES73 thermostat 76 hc1.vacreducemode vacations reduce mode enum [nofrost|reduce|room|outdoor] True select.thermostat_hc1_vacations_reduce_mode select.thermostat_hc1_vacreducemode 6 1 1 90 1
ES73 thermostat 76 hc1.remotetemp room temperature from remote cmd [] (>=-1<=101) C True sensor.thermostat_hc1_room_temperature_from_remote sensor.thermostat_hc1_remotetemp 6 1 1/10 42 1
ES73 thermostat 76 hc1.dhwprio dhw priority boolean True switch.thermostat_hc1_dhw_priority switch.thermostat_hc1_dhwprio 6 1 1 34 1
ES73 thermostat 76 hc1.switchonoptimization switch-on optimization boolean True switch.thermostat_hc1_switch-on_optimization switch.thermostat_hc1_switchonoptimization 6 1 1 30 1
ES73 thermostat 76 hc1.switchtime1 own1 program switchtime string True sensor.thermostat_hc1_own1_program_switchtime sensor.thermostat_hc1_switchtime1 6 1 1 91 8
ES73 thermostat 76 hc1.switchtime2 own2 program switchtime string True sensor.thermostat_hc1_own2_program_switchtime sensor.thermostat_hc1_switchtime2 6 1 1 99 8
ES73 thermostat 76 dhw.mode operating mode enum [off|on|auto] True select.thermostat_dhw_operating_mode select.thermostat_dhw_mode 6 9 1 0 1
ES73 thermostat 76 dhw.circmode circulation pump mode enum [off|on|auto] True select.thermostat_dhw_circulation_pump_mode select.thermostat_dhw_circmode 6 9 1 3 1
ES73 thermostat 76 dhw.progmode program enum [std prog|own prog] True select.thermostat_dhw_program select.thermostat_dhw_progmode 6 9 1 12 1
ES73 thermostat 76 dhw.circprog circulation program enum [std prog|own prog] True select.thermostat_dhw_circulation_program select.thermostat_dhw_circprog 6 9 1 13 1
ES73 thermostat 76 dhw.disinfecting disinfecting boolean True switch.thermostat_dhw_disinfecting switch.thermostat_dhw_disinfecting 6 9 1 7 1
ES73 thermostat 76 dhw.disinfectday disinfection day enum [mo|tu|we|th|fr|sa|su|all] True select.thermostat_dhw_disinfection_day select.thermostat_dhw_disinfectday 6 9 1 8 1
ES73 thermostat 76 dhw.disinfecthour disinfection hour uint8 (>=0<=23) True number.thermostat_dhw_disinfection_hour number.thermostat_dhw_disinfecthour 6 9 1 14 1
ES73 thermostat 76 dhw.maxtemp maximum temperature uint8 (>=0<=254) C True number.thermostat_dhw_maximum_temperature number.thermostat_dhw_maxtemp 6 9 1 15 1
ES73 thermostat 76 dhw.onetimekey one time key function boolean True switch.thermostat_dhw_one_time_key_function switch.thermostat_dhw_onetimekey 6 9 1 16 1
ES73 thermostat 76 dhw.switchtime program switchtime string True sensor.thermostat_dhw_program_switchtime sensor.thermostat_dhw_switchtime 6 9 1 17 8
ES73 thermostat 76 dhw.circswitchtime circulation program switchtime string True sensor.thermostat_dhw_circulation_program_switchtime sensor.thermostat_dhw_circswitchtime 6 9 1 25 8
ES73 thermostat 76 dhw.holidays holiday dates string True sensor.thermostat_dhw_holiday_dates sensor.thermostat_dhw_holidays 6 9 1 33 13
ES73 thermostat 76 dhw.vacations vacation dates string True sensor.thermostat_dhw_vacation_dates sensor.thermostat_dhw_vacations 6 9 1 46 13
ES72, RC20 thermostat 113 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
ES72, RC20 thermostat 113 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
ES72, RC20 thermostat 113 datetime date/time string False sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
ES72, RC20 thermostat 113 minexttemp minimal external temperature int8 (>=-126<=126) C True number.thermostat_minimal_external_temperature number.thermostat_minexttemp 6 0 1 51 1
ES72, RC20 thermostat 113 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/2 0 1
ES72, RC20 thermostat 113 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
ES72, RC20 thermostat 113 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
ES72, RC20 thermostat 113 hc1.mode operating mode enum [night|day|auto] True select.thermostat_hc1_operating_mode select.thermostat_hc1_mode 6 1 1 3 1
ES72, RC20 thermostat 113 hc1.modetype mode type enum [night|day] False sensor.thermostat_hc1_mode_type sensor.thermostat_hc1_modetype 6 1 1 4 1
ES72, RC20 thermostat 113 hc1.daytemp day temperature uint8 (>=0<=127) C True number.thermostat_hc1_day_temperature number.thermostat_hc1_daytemp 6 1 1/2 56 1
ES72, RC20 thermostat 113 hc1.nighttemp night temperature uint8 (>=0<=127) C True number.thermostat_hc1_night_temperature number.thermostat_hc1_nighttemp 6 1 1/2 57 1
ES72, RC20 thermostat 113 hc1.program program enum [family|morning|evening|am|pm|midday|singles|seniors] True select.thermostat_hc1_program select.thermostat_hc1_program 6 1 1 26 1
ES72, RC20 thermostat 113 hc1.minflowtemp min flow temperature uint8 (>=0<=254) C True number.thermostat_hc1_min_flow_temperature number.thermostat_hc1_minflowtemp 6 1 1 11 1
ES72, RC20 thermostat 113 hc1.maxflowtemp max flow temperature uint8 (>=0<=254) C True number.thermostat_hc1_max_flow_temperature number.thermostat_hc1_maxflowtemp 6 1 1 12 1
ES72, RC20 thermostat 113 hc1.tempautotemp temporary set temperature automode uint8 (>=0<=127) C True number.thermostat_hc1_temporary_set_temperature_automode number.thermostat_hc1_tempautotemp 6 1 1/2 27 1
ES72, RC20 thermostat 113 hc1.heatingtype heating type enum [off|radiator|convector|floor] True select.thermostat_hc1_heating_type select.thermostat_hc1_heatingtype 6 1 1 19 1
ES72, RC20 thermostat 113 hc1.summertemp summer temperature uint8 (>=10<=30) C True number.thermostat_hc1_summer_temperature number.thermostat_hc1_summertemp 6 1 1 8 1
ES72, RC20 thermostat 113 hc1.summermode summer mode enum [winter|summer] False sensor.thermostat_hc1_summer_mode sensor.thermostat_hc1_summermode 6 1 1 22 1
ES79 thermostat 156 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
ES79 thermostat 156 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
ES79 thermostat 156 datetime date/time string True sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
ES79 thermostat 156 intoffset internal temperature offset int8 (>=-5<=5) C True number.thermostat_internal_temperature_offset number.thermostat_intoffset 6 0 1/10 46 1
ES79 thermostat 156 minexttemp minimal external temperature int8 (>=-30<=0) C True number.thermostat_minimal_external_temperature number.thermostat_minexttemp 6 0 1 51 1
ES79 thermostat 156 inttemp1 temperature sensor 1 int16 (>=-3199<=3199) C False sensor.thermostat_temperature_sensor_1 sensor.thermostat_inttemp1 6 0 1/10 68 1
ES79 thermostat 156 inttemp2 temperature sensor 2 int16 (>=-3199<=3199) C False sensor.thermostat_temperature_sensor_2 sensor.thermostat_inttemp2 6 0 1/10 69 1
ES79 thermostat 156 damping damping outdoor temperature boolean True switch.thermostat_damping_outdoor_temperature switch.thermostat_damping 6 0 1 52 1
ES79 thermostat 156 dampedoutdoortemp damped outdoor temperature int8 (>=-126<=126) C False sensor.thermostat_damped_outdoor_temperature sensor.thermostat_dampedoutdoortemp 6 0 1 48 1
ES79 thermostat 156 building building type enum [light|medium|heavy] True select.thermostat_building_type select.thermostat_building 6 0 1 50 1
ES79 thermostat 156 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/2 0 1
ES79 thermostat 156 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
ES79 thermostat 156 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
ES79 thermostat 156 hc1.mode operating mode enum [night|day|auto] True select.thermostat_hc1_operating_mode select.thermostat_hc1_mode 6 1 1 3 1
ES79 thermostat 156 hc1.modetype mode type enum [night|day] False sensor.thermostat_hc1_mode_type sensor.thermostat_hc1_modetype 6 1 1 4 1
ES79 thermostat 156 hc1.daytemp day temperature uint8 (>=10<=30) C True number.thermostat_hc1_day_temperature number.thermostat_hc1_daytemp 6 1 1/2 56 1
ES79 thermostat 156 hc1.nighttemp night temperature uint8 (>=10<=30) C True number.thermostat_hc1_night_temperature number.thermostat_hc1_nighttemp 6 1 1/2 57 1
ES79 thermostat 156 hc1.designtemp design temperature uint8 (>=30<=90) C True number.thermostat_hc1_design_temperature number.thermostat_hc1_designtemp 6 1 1 9 1
ES79 thermostat 156 hc1.offsettemp offset temperature int8 (>=-5<=5) C True number.thermostat_hc1_offset_temperature number.thermostat_hc1_offsettemp 6 1 1/2 10 1
ES79 thermostat 156 hc1.holidaytemp holiday temperature uint8 (>=5<=30) C True number.thermostat_hc1_holiday_temperature number.thermostat_hc1_holidaytemp 6 1 1/2 58 1
ES79 thermostat 156 hc1.targetflowtemp target flow temperature uint8 (>=0<=254) C False sensor.thermostat_hc1_target_flow_temperature sensor.thermostat_hc1_targetflowtemp 6 1 1 18 1
ES79 thermostat 156 hc1.summertemp summer temperature uint8 (>=9<=25) C True number.thermostat_hc1_summer_temperature number.thermostat_hc1_summertemp 6 1 1 8 1
ES79 thermostat 156 hc1.summermode summer mode enum [winter|summer] False sensor.thermostat_hc1_summer_mode sensor.thermostat_hc1_summermode 6 1 1 22 1
ES79 thermostat 156 hc1.holidaymode holiday mode boolean False binary_sensor.thermostat_hc1_holiday_mode binary_sensor.thermostat_hc1_holidaymode 6 1 1 59 1
ES79 thermostat 156 hc1.nofrosttemp nofrost temperature int8 (>=-20<=10) C True number.thermostat_hc1_nofrost_temperature number.thermostat_hc1_nofrosttemp 6 1 1 17 1
ES79 thermostat 156 hc1.nofrostmode nofrost mode enum [off|outdoor|room] True select.thermostat_hc1_nofrost_mode select.thermostat_hc1_nofrostmode 6 1 1 16 1
ES79 thermostat 156 hc1.roominfluence room influence uint8 (>=0<=10) C True number.thermostat_hc1_room_influence number.thermostat_hc1_roominfluence 6 1 1 13 1
ES79 thermostat 156 hc1.minflowtemp min flow temperature uint8 (>=5<=70) C True number.thermostat_hc1_min_flow_temperature number.thermostat_hc1_minflowtemp 6 1 1 11 1
ES79 thermostat 156 hc1.maxflowtemp max flow temperature uint8 (>=30<=90) C True number.thermostat_hc1_max_flow_temperature number.thermostat_hc1_maxflowtemp 6 1 1 12 1
ES79 thermostat 156 hc1.flowtempoffset flow temperature offset for mixer uint8 (>=0<=20) C True number.thermostat_hc1_flow_temperature_offset_for_mixer number.thermostat_hc1_flowtempoffset 6 1 1 60 1
ES79 thermostat 156 hc1.heatingtype heating type enum [off|radiator|convector|floor] True select.thermostat_hc1_heating_type select.thermostat_hc1_heatingtype 6 1 1 19 1
ES79 thermostat 156 hc1.reducemode reduce mode enum [nofrost|reduce|room|outdoor] True select.thermostat_hc1_reduce_mode select.thermostat_hc1_reducemode 6 1 1 31 1
ES79 thermostat 156 hc1.controlmode control mode enum [outdoor|room] True select.thermostat_hc1_control_mode select.thermostat_hc1_controlmode 6 1 1 25 1
ES79 thermostat 156 hc1.control control device enum [off|RC20|RC3x] True select.thermostat_hc1_control_device select.thermostat_hc1_control 6 1 1 41 1
ES79 thermostat 156 hc1.holidays holiday dates string True sensor.thermostat_hc1_holiday_dates sensor.thermostat_hc1_holidays 6 1 1 61 13
ES79 thermostat 156 hc1.vacations vacation dates string True sensor.thermostat_hc1_vacation_dates sensor.thermostat_hc1_vacations 6 1 1 74 13
ES79 thermostat 156 hc1.program program enum [own 1|family|morning|evening|am|pm|midday|singles|seniors|new|own 2] True select.thermostat_hc1_program select.thermostat_hc1_program 6 1 1 26 1
ES79 thermostat 156 hc1.pause pause time uint8 (>=0<=99) hours True number.thermostat_hc1_pause_time number.thermostat_hc1_pause 6 1 1 87 1
ES79 thermostat 156 hc1.party party time uint8 (>=0<=99) hours True number.thermostat_hc1_party_time number.thermostat_hc1_party 6 1 1 88 1
ES79 thermostat 156 hc1.tempautotemp temporary set temperature automode uint8 (>=0<=30) C True number.thermostat_hc1_temporary_set_temperature_automode number.thermostat_hc1_tempautotemp 6 1 1/2 27 1
ES79 thermostat 156 hc1.noreducetemp no reduce below temperature int8 (>=-31<=10) C True number.thermostat_hc1_no_reduce_below_temperature number.thermostat_hc1_noreducetemp 6 1 1 32 1
ES79 thermostat 156 hc1.reducetemp off/reduce switch temperature int8 (>=-20<=10) C True number.thermostat_hc1_off/reduce_switch_temperature number.thermostat_hc1_reducetemp 6 1 1 33 1
ES79 thermostat 156 hc1.vacreducetemp vacations off/reduce switch temperature int8 (>=-20<=10) C True number.thermostat_hc1_vacations_off/reduce_switch_temperature number.thermostat_hc1_vacreducetemp 6 1 1 89 1
ES79 thermostat 156 hc1.vacreducemode vacations reduce mode enum [nofrost|reduce|room|outdoor] True select.thermostat_hc1_vacations_reduce_mode select.thermostat_hc1_vacreducemode 6 1 1 90 1
ES79 thermostat 156 hc1.remotetemp room temperature from remote cmd [] (>=-1<=101) C True sensor.thermostat_hc1_room_temperature_from_remote sensor.thermostat_hc1_remotetemp 6 1 1/10 42 1
ES79 thermostat 156 hc1.dhwprio dhw priority boolean True switch.thermostat_hc1_dhw_priority switch.thermostat_hc1_dhwprio 6 1 1 34 1
ES79 thermostat 156 hc1.switchonoptimization switch-on optimization boolean True switch.thermostat_hc1_switch-on_optimization switch.thermostat_hc1_switchonoptimization 6 1 1 30 1
ES79 thermostat 156 hc1.switchtime1 own1 program switchtime string True sensor.thermostat_hc1_own1_program_switchtime sensor.thermostat_hc1_switchtime1 6 1 1 91 8
ES79 thermostat 156 hc1.switchtime2 own2 program switchtime string True sensor.thermostat_hc1_own2_program_switchtime sensor.thermostat_hc1_switchtime2 6 1 1 99 8
ES79 thermostat 156 dhw.mode operating mode enum [off|on|auto] True select.thermostat_dhw_operating_mode select.thermostat_dhw_mode 6 9 1 0 1
ES79 thermostat 156 dhw.circmode circulation pump mode enum [off|on|auto] True select.thermostat_dhw_circulation_pump_mode select.thermostat_dhw_circmode 6 9 1 3 1
ES79 thermostat 156 dhw.progmode program enum [std prog|own prog] True select.thermostat_dhw_program select.thermostat_dhw_progmode 6 9 1 12 1
ES79 thermostat 156 dhw.circprog circulation program enum [std prog|own prog] True select.thermostat_dhw_circulation_program select.thermostat_dhw_circprog 6 9 1 13 1
ES79 thermostat 156 dhw.disinfecting disinfecting boolean True switch.thermostat_dhw_disinfecting switch.thermostat_dhw_disinfecting 6 9 1 7 1
ES79 thermostat 156 dhw.disinfectday disinfection day enum [mo|tu|we|th|fr|sa|su|all] True select.thermostat_dhw_disinfection_day select.thermostat_dhw_disinfectday 6 9 1 8 1
ES79 thermostat 156 dhw.disinfecthour disinfection hour uint8 (>=0<=23) True number.thermostat_dhw_disinfection_hour number.thermostat_dhw_disinfecthour 6 9 1 14 1
ES79 thermostat 156 dhw.maxtemp maximum temperature uint8 (>=60<=80) C True number.thermostat_dhw_maximum_temperature number.thermostat_dhw_maxtemp 6 9 1 15 1
ES79 thermostat 156 dhw.onetimekey one time key function boolean True switch.thermostat_dhw_one_time_key_function switch.thermostat_dhw_onetimekey 6 9 1 16 1
ES79 thermostat 156 dhw.switchtime program switchtime string True sensor.thermostat_dhw_program_switchtime sensor.thermostat_dhw_switchtime 6 9 1 17 8
ES79 thermostat 156 dhw.circswitchtime circulation program switchtime string True sensor.thermostat_dhw_circulation_program_switchtime sensor.thermostat_dhw_circswitchtime 6 9 1 25 8
ES79 thermostat 156 dhw.holidays holiday dates string True sensor.thermostat_dhw_holiday_dates sensor.thermostat_dhw_holidays 6 9 1 33 13
ES79 thermostat 156 dhw.vacations vacation dates string True sensor.thermostat_dhw_vacation_dates sensor.thermostat_dhw_vacations 6 9 1 46 13
FW100 thermostat 105 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
FW100 thermostat 105 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
FW100 thermostat 105 datetime date/time string True sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
FW100 thermostat 105 hybridstrategy hybrid control strategy enum [co2 optimized|cost optimized|outside temp switched|co2 cost mix] True select.thermostat_hybrid_control_strategy select.thermostat_hybridstrategy 6 0 1 54 1
FW100 thermostat 105 switchovertemp outside switchover temperature int8 (>=-20<=20) C True number.thermostat_outside_switchover_temperature number.thermostat_switchovertemp 6 0 1 55 1
FW100 thermostat 105 energycostratio energy cost ratio uint8 (>=0<=20) True number.thermostat_energy_cost_ratio number.thermostat_energycostratio 6 0 1/10 56 1
FW100 thermostat 105 fossilefactor fossile energy factor uint8 (>=0<=5) True number.thermostat_fossile_energy_factor number.thermostat_fossilefactor 6 0 1/10 57 1
FW100 thermostat 105 electricfactor electric energy factor uint8 (>=0<=5) True number.thermostat_electric_energy_factor number.thermostat_electricfactor 6 0 1/10 58 1
FW100 thermostat 105 delayboiler delay boiler support uint8 (>=5<=120) minutes True number.thermostat_delay_boiler_support number.thermostat_delayboiler 6 0 1 59 1
FW100 thermostat 105 tempdiffboiler temp diff boiler support uint8 (>=1<=99) C True number.thermostat_temp_diff_boiler_support number.thermostat_tempdiffboiler 6 0 1 60 1
FW100 thermostat 105 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/10 0 1
FW100 thermostat 105 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
FW100 thermostat 105 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
FW100 thermostat 105 hc1.mode operating mode enum [nofrost|eco|heat|auto] True select.thermostat_hc1_operating_mode select.thermostat_hc1_mode 6 1 1 3 1
FW100 thermostat 105 hc1.modetype mode type enum [nofrost|eco|heat] False sensor.thermostat_hc1_mode_type sensor.thermostat_hc1_modetype 6 1 1 4 1
FW100 thermostat 105 hc1.heattemp heat temperature uint8 (>=0<=127) C True number.thermostat_hc1_heat_temperature number.thermostat_hc1_heattemp 6 1 1/2 198 1
FW100 thermostat 105 hc1.ecotemp eco temperature uint8 (>=0<=127) C True number.thermostat_hc1_eco_temperature number.thermostat_hc1_ecotemp 6 1 1/2 5 1
FW100 thermostat 105 hc1.nofrosttemp nofrost temperature int8 (>=-63<=63) C True number.thermostat_hc1_nofrost_temperature number.thermostat_hc1_nofrosttemp 6 1 1/2 17 1
FW100 thermostat 105 hc1.control control device enum [off|FB10|FB100] True select.thermostat_hc1_control_device select.thermostat_hc1_control 6 1 1 41 1
FW100 thermostat 105 hc1.program program enum [prog a|prog b|prog c|prog d|prog e|prog f] True select.thermostat_hc1_program select.thermostat_hc1_program 6 1 1 26 1
FW100 thermostat 105 hc1.remotetemp room temperature from remote cmd [] (>=-1<=101) C True sensor.thermostat_hc1_room_temperature_from_remote sensor.thermostat_hc1_remotetemp 6 1 1/10 42 1
FW100 thermostat 105 hc1.targetflowtemp target flow temperature uint8 (>=0<=254) C False sensor.thermostat_hc1_target_flow_temperature sensor.thermostat_hc1_targetflowtemp 6 1 1 18 1
FW100 thermostat 105 hc1.summertemp summer temperature uint8 (>=9<=25) C True number.thermostat_hc1_summer_temperature number.thermostat_hc1_summertemp 6 1 1/2 8 1
FW100 thermostat 105 hc1.roomsensor room sensor enum [extern|intern|auto] True select.thermostat_hc1_room_sensor select.thermostat_hc1_roomsensor 6 1 1 199 1
FW100 thermostat 105 hc1.holidaymode holiday mode enum [nofrost|eco|heat|auto] True select.thermostat_hc1_holiday_mode select.thermostat_hc1_holidaymode 6 1 1 59 1
FW100 thermostat 105 hc1.switchonoptimization switch-on optimization boolean True switch.thermostat_hc1_switch-on_optimization switch.thermostat_hc1_switchonoptimization 6 1 1 30 1
FW100 thermostat 105 hc1.heatup heatup enum [slow|medium|fast] True select.thermostat_hc1_heatup select.thermostat_hc1_heatup 6 1 1 200 1
FW100 thermostat 105 hc1.minflowtemp min flow temperature uint8 (>=5<=70) C True number.thermostat_hc1_min_flow_temperature number.thermostat_hc1_minflowtemp 6 1 1 11 1
FW100 thermostat 105 hc1.maxflowtemp max flow temperature uint8 (>=30<=90) C True number.thermostat_hc1_max_flow_temperature number.thermostat_hc1_maxflowtemp 6 1 1 12 1
FW100 thermostat 105 hc1.designtemp design temperature uint8 (>=30<=90) C True number.thermostat_hc1_design_temperature number.thermostat_hc1_designtemp 6 1 1 9 1
FW100 thermostat 105 hc1.roominfluence room influence enum [off|intern|extern|auto] True select.thermostat_hc1_room_influence select.thermostat_hc1_roominfluence 6 1 1 13 1
FW100 thermostat 105 hc1.roominflfactor room influence factor uint8 (>=0<=100) % True number.thermostat_hc1_room_influence_factor number.thermostat_hc1_roominflfactor 6 1 10 14 1
FW100 thermostat 105 hc1.heatingtype heating type enum [off|heatingcurve|radiator|convector|floor] True select.thermostat_hc1_heating_type select.thermostat_hc1_heatingtype 6 1 1 19 1
FW100 thermostat 105 hc1.controlmode control mode enum [off|unmixed|unmixed IPM|mixed IPM] True select.thermostat_hc1_control_mode select.thermostat_hc1_controlmode 6 1 1 25 1
FW100 thermostat 105 dhw.charge charge boolean True switch.thermostat_dhw_charge switch.thermostat_dhw_charge 6 9 1 5 1
FW200 thermostat 106 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
FW200 thermostat 106 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
FW200 thermostat 106 datetime date/time string True sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
FW200 thermostat 106 hybridstrategy hybrid control strategy enum [co2 optimized|cost optimized|outside temp switched|co2 cost mix] True select.thermostat_hybrid_control_strategy select.thermostat_hybridstrategy 6 0 1 54 1
FW200 thermostat 106 switchovertemp outside switchover temperature int8 (>=-20<=20) C True number.thermostat_outside_switchover_temperature number.thermostat_switchovertemp 6 0 1 55 1
FW200 thermostat 106 energycostratio energy cost ratio uint8 (>=0<=20) True number.thermostat_energy_cost_ratio number.thermostat_energycostratio 6 0 1/10 56 1
FW200 thermostat 106 fossilefactor fossile energy factor uint8 (>=0<=5) True number.thermostat_fossile_energy_factor number.thermostat_fossilefactor 6 0 1/10 57 1
FW200 thermostat 106 electricfactor electric energy factor uint8 (>=0<=5) True number.thermostat_electric_energy_factor number.thermostat_electricfactor 6 0 1/10 58 1
FW200 thermostat 106 delayboiler delay boiler support uint8 (>=5<=120) minutes True number.thermostat_delay_boiler_support number.thermostat_delayboiler 6 0 1 59 1
FW200 thermostat 106 tempdiffboiler temp diff boiler support uint8 (>=1<=99) C True number.thermostat_temp_diff_boiler_support number.thermostat_tempdiffboiler 6 0 1 60 1
FW200 thermostat 106 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/10 0 1
FW200 thermostat 106 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
FW200 thermostat 106 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
FW200 thermostat 106 hc1.mode operating mode enum [nofrost|eco|heat|auto] True select.thermostat_hc1_operating_mode select.thermostat_hc1_mode 6 1 1 3 1
FW200 thermostat 106 hc1.modetype mode type enum [nofrost|eco|heat] False sensor.thermostat_hc1_mode_type sensor.thermostat_hc1_modetype 6 1 1 4 1
FW200 thermostat 106 hc1.heattemp heat temperature uint8 (>=0<=127) C True number.thermostat_hc1_heat_temperature number.thermostat_hc1_heattemp 6 1 1/2 198 1
FW200 thermostat 106 hc1.ecotemp eco temperature uint8 (>=0<=127) C True number.thermostat_hc1_eco_temperature number.thermostat_hc1_ecotemp 6 1 1/2 5 1
FW200 thermostat 106 hc1.nofrosttemp nofrost temperature int8 (>=-63<=63) C True number.thermostat_hc1_nofrost_temperature number.thermostat_hc1_nofrosttemp 6 1 1/2 17 1
FW200 thermostat 106 hc1.control control device enum [off|FB10|FB100] True select.thermostat_hc1_control_device select.thermostat_hc1_control 6 1 1 41 1
FW200 thermostat 106 hc1.program program enum [prog a|prog b|prog c|prog d|prog e|prog f] True select.thermostat_hc1_program select.thermostat_hc1_program 6 1 1 26 1
FW200 thermostat 106 hc1.remotetemp room temperature from remote cmd [] (>=-1<=101) C True sensor.thermostat_hc1_room_temperature_from_remote sensor.thermostat_hc1_remotetemp 6 1 1/10 42 1
FW200 thermostat 106 hc1.targetflowtemp target flow temperature uint8 (>=0<=254) C False sensor.thermostat_hc1_target_flow_temperature sensor.thermostat_hc1_targetflowtemp 6 1 1 18 1
FW200 thermostat 106 hc1.summertemp summer temperature uint8 (>=9<=25) C True number.thermostat_hc1_summer_temperature number.thermostat_hc1_summertemp 6 1 1/2 8 1
FW200 thermostat 106 hc1.roomsensor room sensor enum [extern|intern|auto] True select.thermostat_hc1_room_sensor select.thermostat_hc1_roomsensor 6 1 1 199 1
FW200 thermostat 106 hc1.holidaymode holiday mode enum [nofrost|eco|heat|auto] True select.thermostat_hc1_holiday_mode select.thermostat_hc1_holidaymode 6 1 1 59 1
FW200 thermostat 106 hc1.switchonoptimization switch-on optimization boolean True switch.thermostat_hc1_switch-on_optimization switch.thermostat_hc1_switchonoptimization 6 1 1 30 1
FW200 thermostat 106 hc1.heatup heatup enum [slow|medium|fast] True select.thermostat_hc1_heatup select.thermostat_hc1_heatup 6 1 1 200 1
FW200 thermostat 106 hc1.minflowtemp min flow temperature uint8 (>=5<=70) C True number.thermostat_hc1_min_flow_temperature number.thermostat_hc1_minflowtemp 6 1 1 11 1
FW200 thermostat 106 hc1.maxflowtemp max flow temperature uint8 (>=30<=90) C True number.thermostat_hc1_max_flow_temperature number.thermostat_hc1_maxflowtemp 6 1 1 12 1
FW200 thermostat 106 hc1.designtemp design temperature uint8 (>=30<=90) C True number.thermostat_hc1_design_temperature number.thermostat_hc1_designtemp 6 1 1 9 1
FW200 thermostat 106 hc1.roominfluence room influence enum [off|intern|extern|auto] True select.thermostat_hc1_room_influence select.thermostat_hc1_roominfluence 6 1 1 13 1
FW200 thermostat 106 hc1.roominflfactor room influence factor uint8 (>=0<=100) % True number.thermostat_hc1_room_influence_factor number.thermostat_hc1_roominflfactor 6 1 10 14 1
FW200 thermostat 106 hc1.heatingtype heating type enum [off|heatingcurve|radiator|convector|floor] True select.thermostat_hc1_heating_type select.thermostat_hc1_heatingtype 6 1 1 19 1
FW200 thermostat 106 hc1.controlmode control mode enum [off|unmixed|unmixed IPM|mixed IPM] True select.thermostat_hc1_control_mode select.thermostat_hc1_controlmode 6 1 1 25 1
FW200 thermostat 106 dhw.charge charge boolean True switch.thermostat_dhw_charge switch.thermostat_dhw_charge 6 9 1 5 1
FR100 thermostat 107 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
FR100 thermostat 107 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
FR100 thermostat 107 datetime date/time string False sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
FR100 thermostat 107 hybridstrategy hybrid control strategy enum [co2 optimized|cost optimized|outside temp switched|co2 cost mix] True select.thermostat_hybrid_control_strategy select.thermostat_hybridstrategy 6 0 1 54 1
FR100 thermostat 107 switchovertemp outside switchover temperature int8 (>=-20<=20) C True number.thermostat_outside_switchover_temperature number.thermostat_switchovertemp 6 0 1 55 1
FR100 thermostat 107 energycostratio energy cost ratio uint8 (>=0<=20) True number.thermostat_energy_cost_ratio number.thermostat_energycostratio 6 0 1/10 56 1
FR100 thermostat 107 fossilefactor fossile energy factor uint8 (>=0<=5) True number.thermostat_fossile_energy_factor number.thermostat_fossilefactor 6 0 1/10 57 1
FR100 thermostat 107 electricfactor electric energy factor uint8 (>=0<=5) True number.thermostat_electric_energy_factor number.thermostat_electricfactor 6 0 1/10 58 1
FR100 thermostat 107 delayboiler delay boiler support uint8 (>=5<=120) minutes True number.thermostat_delay_boiler_support number.thermostat_delayboiler 6 0 1 59 1
FR100 thermostat 107 tempdiffboiler temp diff boiler support uint8 (>=1<=99) C True number.thermostat_temp_diff_boiler_support number.thermostat_tempdiffboiler 6 0 1 60 1
FR100 thermostat 107 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/10 0 1
FR100 thermostat 107 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
FR100 thermostat 107 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
FR100 thermostat 107 hc1.mode operating mode enum [nofrost|eco|heat|auto] True select.thermostat_hc1_operating_mode select.thermostat_hc1_mode 6 1 1 3 1
FR100 thermostat 107 hc1.modetype mode type enum [nofrost|eco|heat] False sensor.thermostat_hc1_mode_type sensor.thermostat_hc1_modetype 6 1 1 4 1
FR100 thermostat 107 hc1.heattemp heat temperature uint8 (>=0<=127) C True number.thermostat_hc1_heat_temperature number.thermostat_hc1_heattemp 6 1 1/2 198 1
FR100 thermostat 107 hc1.ecotemp eco temperature uint8 (>=0<=127) C True number.thermostat_hc1_eco_temperature number.thermostat_hc1_ecotemp 6 1 1/2 5 1
FR100 thermostat 107 hc1.nofrosttemp nofrost temperature int8 (>=-63<=63) C True number.thermostat_hc1_nofrost_temperature number.thermostat_hc1_nofrosttemp 6 1 1/2 17 1
FR100 thermostat 107 hc1.control control device enum [off|FB10|FB100] True select.thermostat_hc1_control_device select.thermostat_hc1_control 6 1 1 41 1
FR100 thermostat 107 hc1.program program enum [prog a|prog b|prog c|prog d|prog e|prog f] True select.thermostat_hc1_program select.thermostat_hc1_program 6 1 1 26 1
FR100 thermostat 107 hc1.remotetemp room temperature from remote cmd [] (>=-1<=101) C True sensor.thermostat_hc1_room_temperature_from_remote sensor.thermostat_hc1_remotetemp 6 1 1/10 42 1
FR100 thermostat 107 hc1.targetflowtemp target flow temperature uint8 (>=0<=254) C False sensor.thermostat_hc1_target_flow_temperature sensor.thermostat_hc1_targetflowtemp 6 1 1 18 1
FR100 thermostat 107 hc1.summertemp summer temperature uint8 (>=9<=25) C True number.thermostat_hc1_summer_temperature number.thermostat_hc1_summertemp 6 1 1/2 8 1
FR100 thermostat 107 hc1.roomsensor room sensor enum [extern|intern|auto] True select.thermostat_hc1_room_sensor select.thermostat_hc1_roomsensor 6 1 1 199 1
FR100 thermostat 107 hc1.holidaymode holiday mode enum [nofrost|eco|heat|auto] True select.thermostat_hc1_holiday_mode select.thermostat_hc1_holidaymode 6 1 1 59 1
FR100 thermostat 107 hc1.switchonoptimization switch-on optimization boolean True switch.thermostat_hc1_switch-on_optimization switch.thermostat_hc1_switchonoptimization 6 1 1 30 1
FR100 thermostat 107 hc1.heatup heatup enum [slow|medium|fast] True select.thermostat_hc1_heatup select.thermostat_hc1_heatup 6 1 1 200 1
FR100 thermostat 107 hc1.minflowtemp min flow temperature uint8 (>=5<=70) C True number.thermostat_hc1_min_flow_temperature number.thermostat_hc1_minflowtemp 6 1 1 11 1
FR100 thermostat 107 hc1.maxflowtemp max flow temperature uint8 (>=30<=90) C True number.thermostat_hc1_max_flow_temperature number.thermostat_hc1_maxflowtemp 6 1 1 12 1
FR100 thermostat 107 hc1.designtemp design temperature uint8 (>=30<=90) C True number.thermostat_hc1_design_temperature number.thermostat_hc1_designtemp 6 1 1 9 1
FR100 thermostat 107 hc1.roominfluence room influence enum [off|intern|extern|auto] True select.thermostat_hc1_room_influence select.thermostat_hc1_roominfluence 6 1 1 13 1
FR100 thermostat 107 hc1.roominflfactor room influence factor uint8 (>=0<=100) % True number.thermostat_hc1_room_influence_factor number.thermostat_hc1_roominflfactor 6 1 10 14 1
FR100 thermostat 107 hc1.heatingtype heating type enum [off|heatingcurve|radiator|convector|floor] True select.thermostat_hc1_heating_type select.thermostat_hc1_heatingtype 6 1 1 19 1
FR100 thermostat 107 hc1.controlmode control mode enum [off|unmixed|unmixed IPM|mixed IPM] True select.thermostat_hc1_control_mode select.thermostat_hc1_controlmode 6 1 1 25 1
FR100 thermostat 107 dhw.charge charge boolean True switch.thermostat_dhw_charge switch.thermostat_dhw_charge 6 9 1 5 1
FR110 thermostat 108 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
FR110 thermostat 108 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
FR110 thermostat 108 datetime date/time string False sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
FR110 thermostat 108 hybridstrategy hybrid control strategy enum [co2 optimized|cost optimized|outside temp switched|co2 cost mix] True select.thermostat_hybrid_control_strategy select.thermostat_hybridstrategy 6 0 1 54 1
FR110 thermostat 108 switchovertemp outside switchover temperature int8 (>=-20<=20) C True number.thermostat_outside_switchover_temperature number.thermostat_switchovertemp 6 0 1 55 1
FR110 thermostat 108 energycostratio energy cost ratio uint8 (>=0<=20) True number.thermostat_energy_cost_ratio number.thermostat_energycostratio 6 0 1/10 56 1
FR110 thermostat 108 fossilefactor fossile energy factor uint8 (>=0<=5) True number.thermostat_fossile_energy_factor number.thermostat_fossilefactor 6 0 1/10 57 1
FR110 thermostat 108 electricfactor electric energy factor uint8 (>=0<=5) True number.thermostat_electric_energy_factor number.thermostat_electricfactor 6 0 1/10 58 1
FR110 thermostat 108 delayboiler delay boiler support uint8 (>=5<=120) minutes True number.thermostat_delay_boiler_support number.thermostat_delayboiler 6 0 1 59 1
FR110 thermostat 108 tempdiffboiler temp diff boiler support uint8 (>=1<=99) C True number.thermostat_temp_diff_boiler_support number.thermostat_tempdiffboiler 6 0 1 60 1
FR110 thermostat 108 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/10 0 1
FR110 thermostat 108 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
FR110 thermostat 108 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
FR110 thermostat 108 hc1.mode operating mode enum [nofrost|eco|heat|auto] True select.thermostat_hc1_operating_mode select.thermostat_hc1_mode 6 1 1 3 1
FR110 thermostat 108 hc1.modetype mode type enum [nofrost|eco|heat] False sensor.thermostat_hc1_mode_type sensor.thermostat_hc1_modetype 6 1 1 4 1
FR110 thermostat 108 hc1.heattemp heat temperature uint8 (>=0<=127) C True number.thermostat_hc1_heat_temperature number.thermostat_hc1_heattemp 6 1 1/2 198 1
FR110 thermostat 108 hc1.ecotemp eco temperature uint8 (>=0<=127) C True number.thermostat_hc1_eco_temperature number.thermostat_hc1_ecotemp 6 1 1/2 5 1
FR110 thermostat 108 hc1.nofrosttemp nofrost temperature int8 (>=-63<=63) C True number.thermostat_hc1_nofrost_temperature number.thermostat_hc1_nofrosttemp 6 1 1/2 17 1
FR110 thermostat 108 hc1.control control device enum [off|FB10|FB100] True select.thermostat_hc1_control_device select.thermostat_hc1_control 6 1 1 41 1
FR110 thermostat 108 hc1.program program enum [prog a|prog b|prog c|prog d|prog e|prog f] True select.thermostat_hc1_program select.thermostat_hc1_program 6 1 1 26 1
FR110 thermostat 108 hc1.remotetemp room temperature from remote cmd [] (>=-1<=101) C True sensor.thermostat_hc1_room_temperature_from_remote sensor.thermostat_hc1_remotetemp 6 1 1/10 42 1
FR110 thermostat 108 hc1.targetflowtemp target flow temperature uint8 (>=0<=254) C False sensor.thermostat_hc1_target_flow_temperature sensor.thermostat_hc1_targetflowtemp 6 1 1 18 1
FR110 thermostat 108 hc1.summertemp summer temperature uint8 (>=9<=25) C True number.thermostat_hc1_summer_temperature number.thermostat_hc1_summertemp 6 1 1/2 8 1
FR110 thermostat 108 hc1.roomsensor room sensor enum [extern|intern|auto] True select.thermostat_hc1_room_sensor select.thermostat_hc1_roomsensor 6 1 1 199 1
FR110 thermostat 108 hc1.holidaymode holiday mode enum [nofrost|eco|heat|auto] True select.thermostat_hc1_holiday_mode select.thermostat_hc1_holidaymode 6 1 1 59 1
FR110 thermostat 108 hc1.switchonoptimization switch-on optimization boolean True switch.thermostat_hc1_switch-on_optimization switch.thermostat_hc1_switchonoptimization 6 1 1 30 1
FR110 thermostat 108 hc1.heatup heatup enum [slow|medium|fast] True select.thermostat_hc1_heatup select.thermostat_hc1_heatup 6 1 1 200 1
FR110 thermostat 108 hc1.minflowtemp min flow temperature uint8 (>=5<=70) C True number.thermostat_hc1_min_flow_temperature number.thermostat_hc1_minflowtemp 6 1 1 11 1
FR110 thermostat 108 hc1.maxflowtemp max flow temperature uint8 (>=30<=90) C True number.thermostat_hc1_max_flow_temperature number.thermostat_hc1_maxflowtemp 6 1 1 12 1
FR110 thermostat 108 hc1.designtemp design temperature uint8 (>=30<=90) C True number.thermostat_hc1_design_temperature number.thermostat_hc1_designtemp 6 1 1 9 1
FR110 thermostat 108 hc1.roominfluence room influence enum [off|intern|extern|auto] True select.thermostat_hc1_room_influence select.thermostat_hc1_roominfluence 6 1 1 13 1
FR110 thermostat 108 hc1.roominflfactor room influence factor uint8 (>=0<=100) % True number.thermostat_hc1_room_influence_factor number.thermostat_hc1_roominflfactor 6 1 10 14 1
FR110 thermostat 108 hc1.heatingtype heating type enum [off|heatingcurve|radiator|convector|floor] True select.thermostat_hc1_heating_type select.thermostat_hc1_heatingtype 6 1 1 19 1
FR110 thermostat 108 hc1.controlmode control mode enum [off|unmixed|unmixed IPM|mixed IPM] True select.thermostat_hc1_control_mode select.thermostat_hc1_controlmode 6 1 1 25 1
FR110 thermostat 108 dhw.charge charge boolean True switch.thermostat_dhw_charge switch.thermostat_dhw_charge 6 9 1 5 1
FB10 thermostat 109 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
FB10 thermostat 109 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
FB10 thermostat 109 datetime date/time string True sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
FB10 thermostat 109 hybridstrategy hybrid control strategy enum [co2 optimized|cost optimized|outside temp switched|co2 cost mix] True select.thermostat_hybrid_control_strategy select.thermostat_hybridstrategy 6 0 1 54 1
FB10 thermostat 109 switchovertemp outside switchover temperature int8 (>=-20<=20) C True number.thermostat_outside_switchover_temperature number.thermostat_switchovertemp 6 0 1 55 1
FB10 thermostat 109 energycostratio energy cost ratio uint8 (>=0<=20) True number.thermostat_energy_cost_ratio number.thermostat_energycostratio 6 0 1/10 56 1
FB10 thermostat 109 fossilefactor fossile energy factor uint8 (>=0<=5) True number.thermostat_fossile_energy_factor number.thermostat_fossilefactor 6 0 1/10 57 1
FB10 thermostat 109 electricfactor electric energy factor uint8 (>=0<=5) True number.thermostat_electric_energy_factor number.thermostat_electricfactor 6 0 1/10 58 1
FB10 thermostat 109 delayboiler delay boiler support uint8 (>=5<=120) minutes True number.thermostat_delay_boiler_support number.thermostat_delayboiler 6 0 1 59 1
FB10 thermostat 109 tempdiffboiler temp diff boiler support uint8 (>=1<=99) C True number.thermostat_temp_diff_boiler_support number.thermostat_tempdiffboiler 6 0 1 60 1
FB10 thermostat 109 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/10 0 1
FB10 thermostat 109 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
FB10 thermostat 109 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
FB10 thermostat 109 hc1.mode operating mode enum [nofrost|eco|heat|auto] True select.thermostat_hc1_operating_mode select.thermostat_hc1_mode 6 1 1 3 1
FB10 thermostat 109 hc1.modetype mode type enum [nofrost|eco|heat] False sensor.thermostat_hc1_mode_type sensor.thermostat_hc1_modetype 6 1 1 4 1
FB10 thermostat 109 hc1.heattemp heat temperature uint8 (>=0<=127) C True number.thermostat_hc1_heat_temperature number.thermostat_hc1_heattemp 6 1 1/2 198 1
FB10 thermostat 109 hc1.ecotemp eco temperature uint8 (>=0<=127) C True number.thermostat_hc1_eco_temperature number.thermostat_hc1_ecotemp 6 1 1/2 5 1
FB10 thermostat 109 hc1.nofrosttemp nofrost temperature int8 (>=-63<=63) C True number.thermostat_hc1_nofrost_temperature number.thermostat_hc1_nofrosttemp 6 1 1/2 17 1
FB10 thermostat 109 hc1.control control device enum [off|FB10|FB100] True select.thermostat_hc1_control_device select.thermostat_hc1_control 6 1 1 41 1
FB10 thermostat 109 hc1.program program enum [prog a|prog b|prog c|prog d|prog e|prog f] True select.thermostat_hc1_program select.thermostat_hc1_program 6 1 1 26 1
FB10 thermostat 109 hc1.remotetemp room temperature from remote cmd [] (>=-1<=101) C True sensor.thermostat_hc1_room_temperature_from_remote sensor.thermostat_hc1_remotetemp 6 1 1/10 42 1
FB10 thermostat 109 hc1.targetflowtemp target flow temperature uint8 (>=0<=254) C False sensor.thermostat_hc1_target_flow_temperature sensor.thermostat_hc1_targetflowtemp 6 1 1 18 1
FB10 thermostat 109 hc1.summertemp summer temperature uint8 (>=9<=25) C True number.thermostat_hc1_summer_temperature number.thermostat_hc1_summertemp 6 1 1/2 8 1
FB10 thermostat 109 hc1.roomsensor room sensor enum [extern|intern|auto] True select.thermostat_hc1_room_sensor select.thermostat_hc1_roomsensor 6 1 1 199 1
FB10 thermostat 109 hc1.holidaymode holiday mode enum [nofrost|eco|heat|auto] True select.thermostat_hc1_holiday_mode select.thermostat_hc1_holidaymode 6 1 1 59 1
FB10 thermostat 109 hc1.switchonoptimization switch-on optimization boolean True switch.thermostat_hc1_switch-on_optimization switch.thermostat_hc1_switchonoptimization 6 1 1 30 1
FB10 thermostat 109 hc1.heatup heatup enum [slow|medium|fast] True select.thermostat_hc1_heatup select.thermostat_hc1_heatup 6 1 1 200 1
FB10 thermostat 109 hc1.minflowtemp min flow temperature uint8 (>=5<=70) C True number.thermostat_hc1_min_flow_temperature number.thermostat_hc1_minflowtemp 6 1 1 11 1
FB10 thermostat 109 hc1.maxflowtemp max flow temperature uint8 (>=30<=90) C True number.thermostat_hc1_max_flow_temperature number.thermostat_hc1_maxflowtemp 6 1 1 12 1
FB10 thermostat 109 hc1.designtemp design temperature uint8 (>=30<=90) C True number.thermostat_hc1_design_temperature number.thermostat_hc1_designtemp 6 1 1 9 1
FB10 thermostat 109 hc1.roominfluence room influence enum [off|intern|extern|auto] True select.thermostat_hc1_room_influence select.thermostat_hc1_roominfluence 6 1 1 13 1
FB10 thermostat 109 hc1.roominflfactor room influence factor uint8 (>=0<=100) % True number.thermostat_hc1_room_influence_factor number.thermostat_hc1_roominflfactor 6 1 10 14 1
FB10 thermostat 109 hc1.heatingtype heating type enum [off|heatingcurve|radiator|convector|floor] True select.thermostat_hc1_heating_type select.thermostat_hc1_heatingtype 6 1 1 19 1
FB10 thermostat 109 hc1.controlmode control mode enum [off|unmixed|unmixed IPM|mixed IPM] True select.thermostat_hc1_control_mode select.thermostat_hc1_controlmode 6 1 1 25 1
FB10 thermostat 109 dhw.charge charge boolean True switch.thermostat_dhw_charge switch.thermostat_dhw_charge 6 9 1 5 1
FB100 thermostat 110 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
FB100 thermostat 110 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
FB100 thermostat 110 datetime date/time string True sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
FB100 thermostat 110 hybridstrategy hybrid control strategy enum [co2 optimized|cost optimized|outside temp switched|co2 cost mix] True select.thermostat_hybrid_control_strategy select.thermostat_hybridstrategy 6 0 1 54 1
FB100 thermostat 110 switchovertemp outside switchover temperature int8 (>=-20<=20) C True number.thermostat_outside_switchover_temperature number.thermostat_switchovertemp 6 0 1 55 1
FB100 thermostat 110 energycostratio energy cost ratio uint8 (>=0<=20) True number.thermostat_energy_cost_ratio number.thermostat_energycostratio 6 0 1/10 56 1
FB100 thermostat 110 fossilefactor fossile energy factor uint8 (>=0<=5) True number.thermostat_fossile_energy_factor number.thermostat_fossilefactor 6 0 1/10 57 1
FB100 thermostat 110 electricfactor electric energy factor uint8 (>=0<=5) True number.thermostat_electric_energy_factor number.thermostat_electricfactor 6 0 1/10 58 1
FB100 thermostat 110 delayboiler delay boiler support uint8 (>=5<=120) minutes True number.thermostat_delay_boiler_support number.thermostat_delayboiler 6 0 1 59 1
FB100 thermostat 110 tempdiffboiler temp diff boiler support uint8 (>=1<=99) C True number.thermostat_temp_diff_boiler_support number.thermostat_tempdiffboiler 6 0 1 60 1
FB100 thermostat 110 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/10 0 1
FB100 thermostat 110 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
FB100 thermostat 110 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
FB100 thermostat 110 hc1.mode operating mode enum [nofrost|eco|heat|auto] True select.thermostat_hc1_operating_mode select.thermostat_hc1_mode 6 1 1 3 1
FB100 thermostat 110 hc1.modetype mode type enum [nofrost|eco|heat] False sensor.thermostat_hc1_mode_type sensor.thermostat_hc1_modetype 6 1 1 4 1
FB100 thermostat 110 hc1.heattemp heat temperature uint8 (>=0<=127) C True number.thermostat_hc1_heat_temperature number.thermostat_hc1_heattemp 6 1 1/2 198 1
FB100 thermostat 110 hc1.ecotemp eco temperature uint8 (>=0<=127) C True number.thermostat_hc1_eco_temperature number.thermostat_hc1_ecotemp 6 1 1/2 5 1
FB100 thermostat 110 hc1.nofrosttemp nofrost temperature int8 (>=-63<=63) C True number.thermostat_hc1_nofrost_temperature number.thermostat_hc1_nofrosttemp 6 1 1/2 17 1
FB100 thermostat 110 hc1.control control device enum [off|FB10|FB100] True select.thermostat_hc1_control_device select.thermostat_hc1_control 6 1 1 41 1
FB100 thermostat 110 hc1.program program enum [prog a|prog b|prog c|prog d|prog e|prog f] True select.thermostat_hc1_program select.thermostat_hc1_program 6 1 1 26 1
FB100 thermostat 110 hc1.remotetemp room temperature from remote cmd [] (>=-1<=101) C True sensor.thermostat_hc1_room_temperature_from_remote sensor.thermostat_hc1_remotetemp 6 1 1/10 42 1
FB100 thermostat 110 hc1.targetflowtemp target flow temperature uint8 (>=0<=254) C False sensor.thermostat_hc1_target_flow_temperature sensor.thermostat_hc1_targetflowtemp 6 1 1 18 1
FB100 thermostat 110 hc1.summertemp summer temperature uint8 (>=9<=25) C True number.thermostat_hc1_summer_temperature number.thermostat_hc1_summertemp 6 1 1/2 8 1
FB100 thermostat 110 hc1.roomsensor room sensor enum [extern|intern|auto] True select.thermostat_hc1_room_sensor select.thermostat_hc1_roomsensor 6 1 1 199 1
FB100 thermostat 110 hc1.holidaymode holiday mode enum [nofrost|eco|heat|auto] True select.thermostat_hc1_holiday_mode select.thermostat_hc1_holidaymode 6 1 1 59 1
FB100 thermostat 110 hc1.switchonoptimization switch-on optimization boolean True switch.thermostat_hc1_switch-on_optimization switch.thermostat_hc1_switchonoptimization 6 1 1 30 1
FB100 thermostat 110 hc1.heatup heatup enum [slow|medium|fast] True select.thermostat_hc1_heatup select.thermostat_hc1_heatup 6 1 1 200 1
FB100 thermostat 110 hc1.minflowtemp min flow temperature uint8 (>=5<=70) C True number.thermostat_hc1_min_flow_temperature number.thermostat_hc1_minflowtemp 6 1 1 11 1
FB100 thermostat 110 hc1.maxflowtemp max flow temperature uint8 (>=30<=90) C True number.thermostat_hc1_max_flow_temperature number.thermostat_hc1_maxflowtemp 6 1 1 12 1
FB100 thermostat 110 hc1.designtemp design temperature uint8 (>=30<=90) C True number.thermostat_hc1_design_temperature number.thermostat_hc1_designtemp 6 1 1 9 1
FB100 thermostat 110 hc1.roominfluence room influence enum [off|intern|extern|auto] True select.thermostat_hc1_room_influence select.thermostat_hc1_roominfluence 6 1 1 13 1
FB100 thermostat 110 hc1.roominflfactor room influence factor uint8 (>=0<=100) % True number.thermostat_hc1_room_influence_factor number.thermostat_hc1_roominflfactor 6 1 10 14 1
FB100 thermostat 110 hc1.heatingtype heating type enum [off|heatingcurve|radiator|convector|floor] True select.thermostat_hc1_heating_type select.thermostat_hc1_heatingtype 6 1 1 19 1
FB100 thermostat 110 hc1.controlmode control mode enum [off|unmixed|unmixed IPM|mixed IPM] True select.thermostat_hc1_control_mode select.thermostat_hc1_controlmode 6 1 1 25 1
FB100 thermostat 110 dhw.charge charge boolean True switch.thermostat_dhw_charge switch.thermostat_dhw_charge 6 9 1 5 1
FR10 thermostat 111 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
FR10 thermostat 111 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
FR10 thermostat 111 datetime date/time string False sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
FR10 thermostat 111 hybridstrategy hybrid control strategy enum [co2 optimized|cost optimized|outside temp switched|co2 cost mix] True select.thermostat_hybrid_control_strategy select.thermostat_hybridstrategy 6 0 1 54 1
FR10 thermostat 111 switchovertemp outside switchover temperature int8 (>=-20<=20) C True number.thermostat_outside_switchover_temperature number.thermostat_switchovertemp 6 0 1 55 1
FR10 thermostat 111 energycostratio energy cost ratio uint8 (>=0<=20) True number.thermostat_energy_cost_ratio number.thermostat_energycostratio 6 0 1/10 56 1
FR10 thermostat 111 fossilefactor fossile energy factor uint8 (>=0<=5) True number.thermostat_fossile_energy_factor number.thermostat_fossilefactor 6 0 1/10 57 1
FR10 thermostat 111 electricfactor electric energy factor uint8 (>=0<=5) True number.thermostat_electric_energy_factor number.thermostat_electricfactor 6 0 1/10 58 1
FR10 thermostat 111 delayboiler delay boiler support uint8 (>=5<=120) minutes True number.thermostat_delay_boiler_support number.thermostat_delayboiler 6 0 1 59 1
FR10 thermostat 111 tempdiffboiler temp diff boiler support uint8 (>=1<=99) C True number.thermostat_temp_diff_boiler_support number.thermostat_tempdiffboiler 6 0 1 60 1
FR10 thermostat 111 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/10 0 1
FR10 thermostat 111 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
FR10 thermostat 111 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
FR10 thermostat 111 hc1.mode operating mode enum [nofrost|eco|heat|auto] True select.thermostat_hc1_operating_mode select.thermostat_hc1_mode 6 1 1 3 1
FR10 thermostat 111 hc1.modetype mode type enum [nofrost|eco|heat] False sensor.thermostat_hc1_mode_type sensor.thermostat_hc1_modetype 6 1 1 4 1
FR10 thermostat 111 hc1.heattemp heat temperature uint8 (>=0<=127) C True number.thermostat_hc1_heat_temperature number.thermostat_hc1_heattemp 6 1 1/2 198 1
FR10 thermostat 111 hc1.ecotemp eco temperature uint8 (>=0<=127) C True number.thermostat_hc1_eco_temperature number.thermostat_hc1_ecotemp 6 1 1/2 5 1
FR10 thermostat 111 hc1.nofrosttemp nofrost temperature int8 (>=-63<=63) C True number.thermostat_hc1_nofrost_temperature number.thermostat_hc1_nofrosttemp 6 1 1/2 17 1
FR10 thermostat 111 hc1.control control device enum [off|FB10|FB100] True select.thermostat_hc1_control_device select.thermostat_hc1_control 6 1 1 41 1
FR10 thermostat 111 hc1.program program enum [prog a|prog b|prog c|prog d|prog e|prog f] True select.thermostat_hc1_program select.thermostat_hc1_program 6 1 1 26 1
FR10 thermostat 111 hc1.remotetemp room temperature from remote cmd [] (>=-1<=101) C True sensor.thermostat_hc1_room_temperature_from_remote sensor.thermostat_hc1_remotetemp 6 1 1/10 42 1
FR10 thermostat 111 hc1.targetflowtemp target flow temperature uint8 (>=0<=254) C False sensor.thermostat_hc1_target_flow_temperature sensor.thermostat_hc1_targetflowtemp 6 1 1 18 1
FR10 thermostat 111 hc1.summertemp summer temperature uint8 (>=9<=25) C True number.thermostat_hc1_summer_temperature number.thermostat_hc1_summertemp 6 1 1/2 8 1
FR10 thermostat 111 hc1.roomsensor room sensor enum [extern|intern|auto] True select.thermostat_hc1_room_sensor select.thermostat_hc1_roomsensor 6 1 1 199 1
FR10 thermostat 111 hc1.holidaymode holiday mode enum [nofrost|eco|heat|auto] True select.thermostat_hc1_holiday_mode select.thermostat_hc1_holidaymode 6 1 1 59 1
FR10 thermostat 111 hc1.switchonoptimization switch-on optimization boolean True switch.thermostat_hc1_switch-on_optimization switch.thermostat_hc1_switchonoptimization 6 1 1 30 1
FR10 thermostat 111 hc1.heatup heatup enum [slow|medium|fast] True select.thermostat_hc1_heatup select.thermostat_hc1_heatup 6 1 1 200 1
FR10 thermostat 111 hc1.minflowtemp min flow temperature uint8 (>=5<=70) C True number.thermostat_hc1_min_flow_temperature number.thermostat_hc1_minflowtemp 6 1 1 11 1
FR10 thermostat 111 hc1.maxflowtemp max flow temperature uint8 (>=30<=90) C True number.thermostat_hc1_max_flow_temperature number.thermostat_hc1_maxflowtemp 6 1 1 12 1
FR10 thermostat 111 hc1.designtemp design temperature uint8 (>=30<=90) C True number.thermostat_hc1_design_temperature number.thermostat_hc1_designtemp 6 1 1 9 1
FR10 thermostat 111 hc1.roominfluence room influence enum [off|intern|extern|auto] True select.thermostat_hc1_room_influence select.thermostat_hc1_roominfluence 6 1 1 13 1
FR10 thermostat 111 hc1.roominflfactor room influence factor uint8 (>=0<=100) % True number.thermostat_hc1_room_influence_factor number.thermostat_hc1_roominflfactor 6 1 10 14 1
FR10 thermostat 111 hc1.heatingtype heating type enum [off|heatingcurve|radiator|convector|floor] True select.thermostat_hc1_heating_type select.thermostat_hc1_heatingtype 6 1 1 19 1
FR10 thermostat 111 hc1.controlmode control mode enum [off|unmixed|unmixed IPM|mixed IPM] True select.thermostat_hc1_control_mode select.thermostat_hc1_controlmode 6 1 1 25 1
FR10 thermostat 111 dhw.charge charge boolean True switch.thermostat_dhw_charge switch.thermostat_dhw_charge 6 9 1 5 1
FW500 thermostat 116 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
FW500 thermostat 116 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
FW500 thermostat 116 datetime date/time string True sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
FW500 thermostat 116 hybridstrategy hybrid control strategy enum [co2 optimized|cost optimized|outside temp switched|co2 cost mix] True select.thermostat_hybrid_control_strategy select.thermostat_hybridstrategy 6 0 1 54 1
FW500 thermostat 116 switchovertemp outside switchover temperature int8 (>=-20<=20) C True number.thermostat_outside_switchover_temperature number.thermostat_switchovertemp 6 0 1 55 1
FW500 thermostat 116 energycostratio energy cost ratio uint8 (>=0<=20) True number.thermostat_energy_cost_ratio number.thermostat_energycostratio 6 0 1/10 56 1
FW500 thermostat 116 fossilefactor fossile energy factor uint8 (>=0<=5) True number.thermostat_fossile_energy_factor number.thermostat_fossilefactor 6 0 1/10 57 1
FW500 thermostat 116 electricfactor electric energy factor uint8 (>=0<=5) True number.thermostat_electric_energy_factor number.thermostat_electricfactor 6 0 1/10 58 1
FW500 thermostat 116 delayboiler delay boiler support uint8 (>=5<=120) minutes True number.thermostat_delay_boiler_support number.thermostat_delayboiler 6 0 1 59 1
FW500 thermostat 116 tempdiffboiler temp diff boiler support uint8 (>=1<=99) C True number.thermostat_temp_diff_boiler_support number.thermostat_tempdiffboiler 6 0 1 60 1
FW500 thermostat 116 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/10 0 1
FW500 thermostat 116 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
FW500 thermostat 116 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
FW500 thermostat 116 hc1.mode operating mode enum [nofrost|eco|heat|auto] True select.thermostat_hc1_operating_mode select.thermostat_hc1_mode 6 1 1 3 1
FW500 thermostat 116 hc1.modetype mode type enum [nofrost|eco|heat] False sensor.thermostat_hc1_mode_type sensor.thermostat_hc1_modetype 6 1 1 4 1
FW500 thermostat 116 hc1.heattemp heat temperature uint8 (>=0<=127) C True number.thermostat_hc1_heat_temperature number.thermostat_hc1_heattemp 6 1 1/2 198 1
FW500 thermostat 116 hc1.ecotemp eco temperature uint8 (>=0<=127) C True number.thermostat_hc1_eco_temperature number.thermostat_hc1_ecotemp 6 1 1/2 5 1
FW500 thermostat 116 hc1.nofrosttemp nofrost temperature int8 (>=-63<=63) C True number.thermostat_hc1_nofrost_temperature number.thermostat_hc1_nofrosttemp 6 1 1/2 17 1
FW500 thermostat 116 hc1.control control device enum [off|FB10|FB100] True select.thermostat_hc1_control_device select.thermostat_hc1_control 6 1 1 41 1
FW500 thermostat 116 hc1.program program enum [prog a|prog b|prog c|prog d|prog e|prog f] True select.thermostat_hc1_program select.thermostat_hc1_program 6 1 1 26 1
FW500 thermostat 116 hc1.remotetemp room temperature from remote cmd [] (>=-1<=101) C True sensor.thermostat_hc1_room_temperature_from_remote sensor.thermostat_hc1_remotetemp 6 1 1/10 42 1
FW500 thermostat 116 hc1.targetflowtemp target flow temperature uint8 (>=0<=254) C False sensor.thermostat_hc1_target_flow_temperature sensor.thermostat_hc1_targetflowtemp 6 1 1 18 1
FW500 thermostat 116 hc1.summertemp summer temperature uint8 (>=9<=25) C True number.thermostat_hc1_summer_temperature number.thermostat_hc1_summertemp 6 1 1/2 8 1
FW500 thermostat 116 hc1.roomsensor room sensor enum [extern|intern|auto] True select.thermostat_hc1_room_sensor select.thermostat_hc1_roomsensor 6 1 1 199 1
FW500 thermostat 116 hc1.holidaymode holiday mode enum [nofrost|eco|heat|auto] True select.thermostat_hc1_holiday_mode select.thermostat_hc1_holidaymode 6 1 1 59 1
FW500 thermostat 116 hc1.switchonoptimization switch-on optimization boolean True switch.thermostat_hc1_switch-on_optimization switch.thermostat_hc1_switchonoptimization 6 1 1 30 1
FW500 thermostat 116 hc1.heatup heatup enum [slow|medium|fast] True select.thermostat_hc1_heatup select.thermostat_hc1_heatup 6 1 1 200 1
FW500 thermostat 116 hc1.minflowtemp min flow temperature uint8 (>=5<=70) C True number.thermostat_hc1_min_flow_temperature number.thermostat_hc1_minflowtemp 6 1 1 11 1
FW500 thermostat 116 hc1.maxflowtemp max flow temperature uint8 (>=30<=90) C True number.thermostat_hc1_max_flow_temperature number.thermostat_hc1_maxflowtemp 6 1 1 12 1
FW500 thermostat 116 hc1.designtemp design temperature uint8 (>=30<=90) C True number.thermostat_hc1_design_temperature number.thermostat_hc1_designtemp 6 1 1 9 1
FW500 thermostat 116 hc1.roominfluence room influence enum [off|intern|extern|auto] True select.thermostat_hc1_room_influence select.thermostat_hc1_roominfluence 6 1 1 13 1
FW500 thermostat 116 hc1.roominflfactor room influence factor uint8 (>=0<=100) % True number.thermostat_hc1_room_influence_factor number.thermostat_hc1_roominflfactor 6 1 10 14 1
FW500 thermostat 116 hc1.heatingtype heating type enum [off|heatingcurve|radiator|convector|floor] True select.thermostat_hc1_heating_type select.thermostat_hc1_heatingtype 6 1 1 19 1
FW500 thermostat 116 hc1.controlmode control mode enum [off|unmixed|unmixed IPM|mixed IPM] True select.thermostat_hc1_control_mode select.thermostat_hc1_controlmode 6 1 1 25 1
FW500 thermostat 116 dhw.charge charge boolean True switch.thermostat_dhw_charge switch.thermostat_dhw_charge 6 9 1 5 1
FR50 thermostat 147 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
FR50 thermostat 147 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
FR50 thermostat 147 datetime date/time string False sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
FR50 thermostat 147 hybridstrategy hybrid control strategy enum [co2 optimized|cost optimized|outside temp switched|co2 cost mix] True select.thermostat_hybrid_control_strategy select.thermostat_hybridstrategy 6 0 1 54 1
FR50 thermostat 147 switchovertemp outside switchover temperature int8 (>=-20<=20) C True number.thermostat_outside_switchover_temperature number.thermostat_switchovertemp 6 0 1 55 1
FR50 thermostat 147 energycostratio energy cost ratio uint8 (>=0<=20) True number.thermostat_energy_cost_ratio number.thermostat_energycostratio 6 0 1/10 56 1
FR50 thermostat 147 fossilefactor fossile energy factor uint8 (>=0<=5) True number.thermostat_fossile_energy_factor number.thermostat_fossilefactor 6 0 1/10 57 1
FR50 thermostat 147 electricfactor electric energy factor uint8 (>=0<=5) True number.thermostat_electric_energy_factor number.thermostat_electricfactor 6 0 1/10 58 1
FR50 thermostat 147 delayboiler delay boiler support uint8 (>=5<=120) minutes True number.thermostat_delay_boiler_support number.thermostat_delayboiler 6 0 1 59 1
FR50 thermostat 147 tempdiffboiler temp diff boiler support uint8 (>=1<=99) C True number.thermostat_temp_diff_boiler_support number.thermostat_tempdiffboiler 6 0 1 60 1
FR50 thermostat 147 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/10 0 1
FR50 thermostat 147 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
FR50 thermostat 147 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
FR50 thermostat 147 hc1.mode operating mode enum [nofrost|eco|heat|auto] True select.thermostat_hc1_operating_mode select.thermostat_hc1_mode 6 1 1 3 1
FR50 thermostat 147 hc1.modetype mode type enum [nofrost|eco|heat] False sensor.thermostat_hc1_mode_type sensor.thermostat_hc1_modetype 6 1 1 4 1
FR50 thermostat 147 hc1.heattemp heat temperature uint8 (>=0<=127) C True number.thermostat_hc1_heat_temperature number.thermostat_hc1_heattemp 6 1 1/2 198 1
FR50 thermostat 147 hc1.ecotemp eco temperature uint8 (>=0<=127) C True number.thermostat_hc1_eco_temperature number.thermostat_hc1_ecotemp 6 1 1/2 5 1
FR50 thermostat 147 hc1.nofrosttemp nofrost temperature int8 (>=-63<=63) C True number.thermostat_hc1_nofrost_temperature number.thermostat_hc1_nofrosttemp 6 1 1/2 17 1
FR50 thermostat 147 hc1.control control device enum [off|FB10|FB100] True select.thermostat_hc1_control_device select.thermostat_hc1_control 6 1 1 41 1
FR50 thermostat 147 hc1.program program enum [prog a|prog b|prog c|prog d|prog e|prog f] True select.thermostat_hc1_program select.thermostat_hc1_program 6 1 1 26 1
FR50 thermostat 147 hc1.remotetemp room temperature from remote cmd [] (>=-1<=101) C True sensor.thermostat_hc1_room_temperature_from_remote sensor.thermostat_hc1_remotetemp 6 1 1/10 42 1
FR50 thermostat 147 hc1.targetflowtemp target flow temperature uint8 (>=0<=254) C False sensor.thermostat_hc1_target_flow_temperature sensor.thermostat_hc1_targetflowtemp 6 1 1 18 1
FR50 thermostat 147 hc1.summertemp summer temperature uint8 (>=9<=25) C True number.thermostat_hc1_summer_temperature number.thermostat_hc1_summertemp 6 1 1/2 8 1
FR50 thermostat 147 hc1.roomsensor room sensor enum [extern|intern|auto] True select.thermostat_hc1_room_sensor select.thermostat_hc1_roomsensor 6 1 1 199 1
FR50 thermostat 147 hc1.holidaymode holiday mode enum [nofrost|eco|heat|auto] True select.thermostat_hc1_holiday_mode select.thermostat_hc1_holidaymode 6 1 1 59 1
FR50 thermostat 147 hc1.switchonoptimization switch-on optimization boolean True switch.thermostat_hc1_switch-on_optimization switch.thermostat_hc1_switchonoptimization 6 1 1 30 1
FR50 thermostat 147 hc1.heatup heatup enum [slow|medium|fast] True select.thermostat_hc1_heatup select.thermostat_hc1_heatup 6 1 1 200 1
FR50 thermostat 147 hc1.minflowtemp min flow temperature uint8 (>=5<=70) C True number.thermostat_hc1_min_flow_temperature number.thermostat_hc1_minflowtemp 6 1 1 11 1
FR50 thermostat 147 hc1.maxflowtemp max flow temperature uint8 (>=30<=90) C True number.thermostat_hc1_max_flow_temperature number.thermostat_hc1_maxflowtemp 6 1 1 12 1
FR50 thermostat 147 hc1.designtemp design temperature uint8 (>=30<=90) C True number.thermostat_hc1_design_temperature number.thermostat_hc1_designtemp 6 1 1 9 1
FR50 thermostat 147 hc1.roominfluence room influence enum [off|intern|extern|auto] True select.thermostat_hc1_room_influence select.thermostat_hc1_roominfluence 6 1 1 13 1
FR50 thermostat 147 hc1.roominflfactor room influence factor uint8 (>=0<=100) % True number.thermostat_hc1_room_influence_factor number.thermostat_hc1_roominflfactor 6 1 10 14 1
FR50 thermostat 147 hc1.heatingtype heating type enum [off|heatingcurve|radiator|convector|floor] True select.thermostat_hc1_heating_type select.thermostat_hc1_heatingtype 6 1 1 19 1
FR50 thermostat 147 hc1.controlmode control mode enum [off|unmixed|unmixed IPM|mixed IPM] True select.thermostat_hc1_control_mode select.thermostat_hc1_controlmode 6 1 1 25 1
FR50 thermostat 147 dhw.charge charge boolean True switch.thermostat_dhw_charge switch.thermostat_dhw_charge 6 9 1 5 1
FR120 thermostat 191 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
FR120 thermostat 191 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
FR120 thermostat 191 datetime date/time string False sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
FR120 thermostat 191 hybridstrategy hybrid control strategy enum [co2 optimized|cost optimized|outside temp switched|co2 cost mix] True select.thermostat_hybrid_control_strategy select.thermostat_hybridstrategy 6 0 1 54 1
FR120 thermostat 191 switchovertemp outside switchover temperature int8 (>=-20<=20) C True number.thermostat_outside_switchover_temperature number.thermostat_switchovertemp 6 0 1 55 1
FR120 thermostat 191 energycostratio energy cost ratio uint8 (>=0<=20) True number.thermostat_energy_cost_ratio number.thermostat_energycostratio 6 0 1/10 56 1
FR120 thermostat 191 fossilefactor fossile energy factor uint8 (>=0<=5) True number.thermostat_fossile_energy_factor number.thermostat_fossilefactor 6 0 1/10 57 1
FR120 thermostat 191 electricfactor electric energy factor uint8 (>=0<=5) True number.thermostat_electric_energy_factor number.thermostat_electricfactor 6 0 1/10 58 1
FR120 thermostat 191 delayboiler delay boiler support uint8 (>=5<=120) minutes True number.thermostat_delay_boiler_support number.thermostat_delayboiler 6 0 1 59 1
FR120 thermostat 191 tempdiffboiler temp diff boiler support uint8 (>=1<=99) C True number.thermostat_temp_diff_boiler_support number.thermostat_tempdiffboiler 6 0 1 60 1
FR120 thermostat 191 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/10 0 1
FR120 thermostat 191 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
FR120 thermostat 191 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
FR120 thermostat 191 hc1.mode operating mode enum [nofrost|eco|heat|auto] True select.thermostat_hc1_operating_mode select.thermostat_hc1_mode 6 1 1 3 1
FR120 thermostat 191 hc1.modetype mode type enum [nofrost|eco|heat] False sensor.thermostat_hc1_mode_type sensor.thermostat_hc1_modetype 6 1 1 4 1
FR120 thermostat 191 hc1.heattemp heat temperature uint8 (>=0<=127) C True number.thermostat_hc1_heat_temperature number.thermostat_hc1_heattemp 6 1 1/2 198 1
FR120 thermostat 191 hc1.ecotemp eco temperature uint8 (>=0<=127) C True number.thermostat_hc1_eco_temperature number.thermostat_hc1_ecotemp 6 1 1/2 5 1
FR120 thermostat 191 hc1.nofrosttemp nofrost temperature int8 (>=-63<=63) C True number.thermostat_hc1_nofrost_temperature number.thermostat_hc1_nofrosttemp 6 1 1/2 17 1
FR120 thermostat 191 hc1.control control device enum [off|FB10|FB100] True select.thermostat_hc1_control_device select.thermostat_hc1_control 6 1 1 41 1
FR120 thermostat 191 hc1.program program enum [prog a|prog b|prog c|prog d|prog e|prog f] True select.thermostat_hc1_program select.thermostat_hc1_program 6 1 1 26 1
FR120 thermostat 191 hc1.remotetemp room temperature from remote cmd [] (>=-1<=101) C True sensor.thermostat_hc1_room_temperature_from_remote sensor.thermostat_hc1_remotetemp 6 1 1/10 42 1
FR120 thermostat 191 hc1.targetflowtemp target flow temperature uint8 (>=0<=254) C False sensor.thermostat_hc1_target_flow_temperature sensor.thermostat_hc1_targetflowtemp 6 1 1 18 1
FR120 thermostat 191 hc1.summertemp summer temperature uint8 (>=9<=25) C True number.thermostat_hc1_summer_temperature number.thermostat_hc1_summertemp 6 1 1/2 8 1
FR120 thermostat 191 hc1.roomsensor room sensor enum [extern|intern|auto] True select.thermostat_hc1_room_sensor select.thermostat_hc1_roomsensor 6 1 1 199 1
FR120 thermostat 191 hc1.holidaymode holiday mode enum [nofrost|eco|heat|auto] True select.thermostat_hc1_holiday_mode select.thermostat_hc1_holidaymode 6 1 1 59 1
FR120 thermostat 191 hc1.switchonoptimization switch-on optimization boolean True switch.thermostat_hc1_switch-on_optimization switch.thermostat_hc1_switchonoptimization 6 1 1 30 1
FR120 thermostat 191 hc1.heatup heatup enum [slow|medium|fast] True select.thermostat_hc1_heatup select.thermostat_hc1_heatup 6 1 1 200 1
FR120 thermostat 191 hc1.minflowtemp min flow temperature uint8 (>=5<=70) C True number.thermostat_hc1_min_flow_temperature number.thermostat_hc1_minflowtemp 6 1 1 11 1
FR120 thermostat 191 hc1.maxflowtemp max flow temperature uint8 (>=30<=90) C True number.thermostat_hc1_max_flow_temperature number.thermostat_hc1_maxflowtemp 6 1 1 12 1
FR120 thermostat 191 hc1.designtemp design temperature uint8 (>=30<=90) C True number.thermostat_hc1_design_temperature number.thermostat_hc1_designtemp 6 1 1 9 1
FR120 thermostat 191 hc1.roominfluence room influence enum [off|intern|extern|auto] True select.thermostat_hc1_room_influence select.thermostat_hc1_roominfluence 6 1 1 13 1
FR120 thermostat 191 hc1.roominflfactor room influence factor uint8 (>=0<=100) % True number.thermostat_hc1_room_influence_factor number.thermostat_hc1_roominflfactor 6 1 10 14 1
FR120 thermostat 191 hc1.heatingtype heating type enum [off|heatingcurve|radiator|convector|floor] True select.thermostat_hc1_heating_type select.thermostat_hc1_heatingtype 6 1 1 19 1
FR120 thermostat 191 hc1.controlmode control mode enum [off|unmixed|unmixed IPM|mixed IPM] True select.thermostat_hc1_control_mode select.thermostat_hc1_controlmode 6 1 1 25 1
FR120 thermostat 191 dhw.charge charge boolean True switch.thermostat_dhw_charge switch.thermostat_dhw_charge 6 9 1 5 1
FW120 thermostat 192 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
FW120 thermostat 192 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
FW120 thermostat 192 datetime date/time string True sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
FW120 thermostat 192 hybridstrategy hybrid control strategy enum [co2 optimized|cost optimized|outside temp switched|co2 cost mix] True select.thermostat_hybrid_control_strategy select.thermostat_hybridstrategy 6 0 1 54 1
FW120 thermostat 192 switchovertemp outside switchover temperature int8 (>=-20<=20) C True number.thermostat_outside_switchover_temperature number.thermostat_switchovertemp 6 0 1 55 1
FW120 thermostat 192 energycostratio energy cost ratio uint8 (>=0<=20) True number.thermostat_energy_cost_ratio number.thermostat_energycostratio 6 0 1/10 56 1
FW120 thermostat 192 fossilefactor fossile energy factor uint8 (>=0<=5) True number.thermostat_fossile_energy_factor number.thermostat_fossilefactor 6 0 1/10 57 1
FW120 thermostat 192 electricfactor electric energy factor uint8 (>=0<=5) True number.thermostat_electric_energy_factor number.thermostat_electricfactor 6 0 1/10 58 1
FW120 thermostat 192 delayboiler delay boiler support uint8 (>=5<=120) minutes True number.thermostat_delay_boiler_support number.thermostat_delayboiler 6 0 1 59 1
FW120 thermostat 192 tempdiffboiler temp diff boiler support uint8 (>=1<=99) C True number.thermostat_temp_diff_boiler_support number.thermostat_tempdiffboiler 6 0 1 60 1
FW120 thermostat 192 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/10 0 1
FW120 thermostat 192 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
FW120 thermostat 192 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
FW120 thermostat 192 hc1.mode operating mode enum [nofrost|eco|heat|auto] True select.thermostat_hc1_operating_mode select.thermostat_hc1_mode 6 1 1 3 1
FW120 thermostat 192 hc1.modetype mode type enum [nofrost|eco|heat] False sensor.thermostat_hc1_mode_type sensor.thermostat_hc1_modetype 6 1 1 4 1
FW120 thermostat 192 hc1.heattemp heat temperature uint8 (>=0<=127) C True number.thermostat_hc1_heat_temperature number.thermostat_hc1_heattemp 6 1 1/2 198 1
FW120 thermostat 192 hc1.ecotemp eco temperature uint8 (>=0<=127) C True number.thermostat_hc1_eco_temperature number.thermostat_hc1_ecotemp 6 1 1/2 5 1
FW120 thermostat 192 hc1.nofrosttemp nofrost temperature int8 (>=-63<=63) C True number.thermostat_hc1_nofrost_temperature number.thermostat_hc1_nofrosttemp 6 1 1/2 17 1
FW120 thermostat 192 hc1.control control device enum [off|FB10|FB100] True select.thermostat_hc1_control_device select.thermostat_hc1_control 6 1 1 41 1
FW120 thermostat 192 hc1.program program enum [prog a|prog b|prog c|prog d|prog e|prog f] True select.thermostat_hc1_program select.thermostat_hc1_program 6 1 1 26 1
FW120 thermostat 192 hc1.remotetemp room temperature from remote cmd [] (>=-1<=101) C True sensor.thermostat_hc1_room_temperature_from_remote sensor.thermostat_hc1_remotetemp 6 1 1/10 42 1
FW120 thermostat 192 hc1.targetflowtemp target flow temperature uint8 (>=0<=254) C False sensor.thermostat_hc1_target_flow_temperature sensor.thermostat_hc1_targetflowtemp 6 1 1 18 1
FW120 thermostat 192 hc1.summertemp summer temperature uint8 (>=9<=25) C True number.thermostat_hc1_summer_temperature number.thermostat_hc1_summertemp 6 1 1/2 8 1
FW120 thermostat 192 hc1.roomsensor room sensor enum [extern|intern|auto] True select.thermostat_hc1_room_sensor select.thermostat_hc1_roomsensor 6 1 1 199 1
FW120 thermostat 192 hc1.holidaymode holiday mode enum [nofrost|eco|heat|auto] True select.thermostat_hc1_holiday_mode select.thermostat_hc1_holidaymode 6 1 1 59 1
FW120 thermostat 192 hc1.switchonoptimization switch-on optimization boolean True switch.thermostat_hc1_switch-on_optimization switch.thermostat_hc1_switchonoptimization 6 1 1 30 1
FW120 thermostat 192 hc1.heatup heatup enum [slow|medium|fast] True select.thermostat_hc1_heatup select.thermostat_hc1_heatup 6 1 1 200 1
FW120 thermostat 192 hc1.minflowtemp min flow temperature uint8 (>=5<=70) C True number.thermostat_hc1_min_flow_temperature number.thermostat_hc1_minflowtemp 6 1 1 11 1
FW120 thermostat 192 hc1.maxflowtemp max flow temperature uint8 (>=30<=90) C True number.thermostat_hc1_max_flow_temperature number.thermostat_hc1_maxflowtemp 6 1 1 12 1
FW120 thermostat 192 hc1.designtemp design temperature uint8 (>=30<=90) C True number.thermostat_hc1_design_temperature number.thermostat_hc1_designtemp 6 1 1 9 1
FW120 thermostat 192 hc1.roominfluence room influence enum [off|intern|extern|auto] True select.thermostat_hc1_room_influence select.thermostat_hc1_roominfluence 6 1 1 13 1
FW120 thermostat 192 hc1.roominflfactor room influence factor uint8 (>=0<=100) % True number.thermostat_hc1_room_influence_factor number.thermostat_hc1_roominflfactor 6 1 10 14 1
FW120 thermostat 192 hc1.heatingtype heating type enum [off|heatingcurve|radiator|convector|floor] True select.thermostat_hc1_heating_type select.thermostat_hc1_heatingtype 6 1 1 19 1
FW120 thermostat 192 hc1.controlmode control mode enum [off|unmixed|unmixed IPM|mixed IPM] True select.thermostat_hc1_control_mode select.thermostat_hc1_controlmode 6 1 1 25 1
FW120 thermostat 192 dhw.charge charge boolean True switch.thermostat_dhw_charge switch.thermostat_dhw_charge 6 9 1 5 1
RT800, RC220 thermostat 3 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
RT800, RC220 thermostat 3 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
RT800, RC220 thermostat 3 datetime date/time string False sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
RT800, RC220 thermostat 3 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/2 0 1
RT800, RC220 thermostat 3 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
RT800, RC220 thermostat 3 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
RC100H, CR10H thermostat 200 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
RC100H, CR10H thermostat 200 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
RC100H, CR10H thermostat 200 datetime date/time string False sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
RC100H, CR10H thermostat 200 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/2 0 1
RC100H, CR10H thermostat 200 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
RC100H, CR10H thermostat 200 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
TR120RF, CR20RF thermostat 249 errorcode error code string False sensor.thermostat_error_code sensor.thermostat_errorcode 6 0 1 0 8
TR120RF, CR20RF thermostat 249 lastcode last error code string False sensor.thermostat_last_error_code sensor.thermostat_lastcode 6 0 1 8 25
TR120RF, CR20RF thermostat 249 datetime date/time string False sensor.thermostat_date/time sensor.thermostat_datetime 6 0 1 33 13
TR120RF, CR20RF thermostat 249 hc1.seltemp selected room temperature int16 (>=0<=30) C True number.thermostat_hc1_selected_room_temperature number.thermostat_hc1_seltemp 6 1 1/2 0 1
TR120RF, CR20RF thermostat 249 hc1.currtemp current room temperature int16 (>=-3199<=3199) C False sensor.thermostat_hc1_current_room_temperature sensor.thermostat_hc1_currtemp 6 1 1/10 1 1
TR120RF, CR20RF thermostat 249 hc1.haclimate mqtt discovery current room temperature enum [selTemp|roomTemp] (>=5<=30) False sensor.thermostat_hc1_mqtt_discovery_current_room_temperature sensor.thermostat_hc1_haclimate 6 1 1 2 1
MM10 mixer 69 hc1.flowtemphc flow temperature (TC1) uint16 (>=0<=3199) C False sensor.mixer_hc1_flow_temperature_(TC1) sensor.mixer_hc1_flowtemphc 7 1 1/10 0 1
MM10 mixer 69 hc1.valvestatus mixing valve actuator (VC1) int8 (>=-100<=100) % False sensor.mixer_hc1_mixing_valve_actuator_(VC1) sensor.mixer_hc1_valvestatus 7 1 1 1 1
MM10 mixer 69 hc1.flowsettemp setpoint flow temperature uint8 (>=0<=254) C True number.mixer_hc1_setpoint_flow_temperature number.mixer_hc1_flowsettemp 7 1 1 2 1
MM10 mixer 69 hc1.pumpstatus pump status (PC1) boolean True switch.mixer_hc1_pump_status_(PC1) switch.mixer_hc1_pumpstatus 7 1 1 3 1
MM10 mixer 69 hc1.activated activated boolean True switch.mixer_hc1_activated switch.mixer_hc1_activated 7 1 1 4 1
MM10 mixer 69 hc1.valvesettime time to set valve uint8 (>=10<=600) seconds True number.mixer_hc1_time_to_set_valve number.mixer_hc1_valvesettime 7 1 10 5 1
IPM mixer 100 hc1.flowtemphc flow temperature (TC1) uint16 (>=0<=3199) C False sensor.mixer_hc1_flow_temperature_(TC1) sensor.mixer_hc1_flowtemphc 7 1 1/10 0 1
IPM mixer 100 hc1.valvestatus mixing valve actuator (VC1) uint8 (>=0<=100) % False sensor.mixer_hc1_mixing_valve_actuator_(VC1) sensor.mixer_hc1_valvestatus 7 1 1 1 1
IPM mixer 100 hc1.flowsettemp setpoint flow temperature uint8 (>=0<=254) C True number.mixer_hc1_setpoint_flow_temperature number.mixer_hc1_flowsettemp 7 1 1 2 1
IPM mixer 100 hc1.pumpstatus pump status (PC1) boolean True switch.mixer_hc1_pump_status_(PC1) switch.mixer_hc1_pumpstatus 7 1 1 3 1
IPM mixer 100 hc1.flowtempvf flow temperature in header (T0/Vf) uint16 (>=0<=3199) C False sensor.mixer_hc1_flow_temperature_in_header_(T0/Vf) sensor.mixer_hc1_flowtempvf 7 1 1/10 6 1
IPM2 mixer 102 hc1.flowtemphc flow temperature (TC1) uint16 (>=0<=3199) C False sensor.mixer_hc1_flow_temperature_(TC1) sensor.mixer_hc1_flowtemphc 7 1 1/10 0 1
IPM2 mixer 102 hc1.valvestatus mixing valve actuator (VC1) uint8 (>=0<=100) % False sensor.mixer_hc1_mixing_valve_actuator_(VC1) sensor.mixer_hc1_valvestatus 7 1 1 1 1
IPM2 mixer 102 hc1.flowsettemp setpoint flow temperature uint8 (>=0<=254) C True number.mixer_hc1_setpoint_flow_temperature number.mixer_hc1_flowsettemp 7 1 1 2 1
IPM2 mixer 102 hc1.pumpstatus pump status (PC1) boolean True switch.mixer_hc1_pump_status_(PC1) switch.mixer_hc1_pumpstatus 7 1 1 3 1
IPM2 mixer 102 hc1.flowtempvf flow temperature in header (T0/Vf) uint16 (>=0<=3199) C False sensor.mixer_hc1_flow_temperature_in_header_(T0/Vf) sensor.mixer_hc1_flowtempvf 7 1 1/10 6 1
MM50 mixer 159 hc1.flowtemphc flow temperature (TC1) uint16 (>=0<=3199) C False sensor.mixer_hc1_flow_temperature_(TC1) sensor.mixer_hc1_flowtemphc 7 1 1/10 0 1
MM50 mixer 159 hc1.valvestatus mixing valve actuator (VC1) uint8 (>=0<=100) % False sensor.mixer_hc1_mixing_valve_actuator_(VC1) sensor.mixer_hc1_valvestatus 7 1 1 1 1
MM50 mixer 159 hc1.flowsettemp setpoint flow temperature uint8 (>=0<=254) C True number.mixer_hc1_setpoint_flow_temperature number.mixer_hc1_flowsettemp 7 1 1 2 1
MM50 mixer 159 hc1.pumpstatus pump status (PC1) boolean True switch.mixer_hc1_pump_status_(PC1) switch.mixer_hc1_pumpstatus 7 1 1 3 1
MM50 mixer 159 hc1.activated activated boolean True switch.mixer_hc1_activated switch.mixer_hc1_activated 7 1 1 4 1
MM50 mixer 159 hc1.valvesettime time to set valve uint8 (>=10<=600) seconds True number.mixer_hc1_time_to_set_valve number.mixer_hc1_valvesettime 7 1 10 5 1
MM50 mixer 159 hc1.flowtempoffset flow temperature offset for mixer uint8 (>=0<=20) K True number.mixer_hc1_flow_temperature_offset_for_mixer number.mixer_hc1_flowtempoffset 7 1 1 7 1
MM100 mixer 160 hc1.flowtemphc flow temperature (TC1) uint16 (>=0<=3199) C False sensor.mixer_hc1_flow_temperature_(TC1) sensor.mixer_hc1_flowtemphc 7 1 1/10 0 1
MM100 mixer 160 hc1.valvestatus mixing valve actuator (VC1) uint8 (>=0<=100) % False sensor.mixer_hc1_mixing_valve_actuator_(VC1) sensor.mixer_hc1_valvestatus 7 1 1 1 1
MM100 mixer 160 hc1.flowsettemp setpoint flow temperature uint8 (>=0<=254) C True number.mixer_hc1_setpoint_flow_temperature number.mixer_hc1_flowsettemp 7 1 1 2 1
MM100 mixer 160 hc1.pumpstatus pump status (PC1) boolean True switch.mixer_hc1_pump_status_(PC1) switch.mixer_hc1_pumpstatus 7 1 1 3 1
MM100 mixer 160 hc1.activated activated boolean True switch.mixer_hc1_activated switch.mixer_hc1_activated 7 1 1 4 1
MM100 mixer 160 hc1.valvesettime time to set valve uint8 (>=10<=600) seconds True number.mixer_hc1_time_to_set_valve number.mixer_hc1_valvesettime 7 1 10 5 1
MM100 mixer 160 hc1.flowtempoffset flow temperature offset for mixer uint8 (>=0<=20) K True number.mixer_hc1_flow_temperature_offset_for_mixer number.mixer_hc1_flowtempoffset 7 1 1 7 1
MM200 mixer 161 hc1.flowtemphc flow temperature (TC1) uint16 (>=0<=3199) C False sensor.mixer_hc1_flow_temperature_(TC1) sensor.mixer_hc1_flowtemphc 7 1 1/10 0 1
MM200 mixer 161 hc1.valvestatus mixing valve actuator (VC1) uint8 (>=0<=100) % False sensor.mixer_hc1_mixing_valve_actuator_(VC1) sensor.mixer_hc1_valvestatus 7 1 1 1 1
MM200 mixer 161 hc1.flowsettemp setpoint flow temperature uint8 (>=0<=254) C True number.mixer_hc1_setpoint_flow_temperature number.mixer_hc1_flowsettemp 7 1 1 2 1
MM200 mixer 161 hc1.pumpstatus pump status (PC1) boolean True switch.mixer_hc1_pump_status_(PC1) switch.mixer_hc1_pumpstatus 7 1 1 3 1
MM200 mixer 161 hc1.activated activated boolean True switch.mixer_hc1_activated switch.mixer_hc1_activated 7 1 1 4 1
MM200 mixer 161 hc1.valvesettime time to set valve uint8 (>=10<=600) seconds True number.mixer_hc1_time_to_set_valve number.mixer_hc1_valvesettime 7 1 10 5 1
MM200 mixer 161 hc1.flowtempoffset flow temperature offset for mixer uint8 (>=0<=20) K True number.mixer_hc1_flow_temperature_offset_for_mixer number.mixer_hc1_flowtempoffset 7 1 1 7 1
MZ100 mixer 193 hc1.flowtemphc flow temperature (TC1) uint16 (>=0<=3199) C False sensor.mixer_hc1_flow_temperature_(TC1) sensor.mixer_hc1_flowtemphc 7 1 1/10 0 1
MZ100 mixer 193 hc1.valvestatus mixing valve actuator (VC1) uint8 (>=0<=100) % False sensor.mixer_hc1_mixing_valve_actuator_(VC1) sensor.mixer_hc1_valvestatus 7 1 1 1 1
MZ100 mixer 193 hc1.flowsettemp setpoint flow temperature uint8 (>=0<=254) C True number.mixer_hc1_setpoint_flow_temperature number.mixer_hc1_flowsettemp 7 1 1 2 1
MZ100 mixer 193 hc1.pumpstatus pump status (PC1) boolean True switch.mixer_hc1_pump_status_(PC1) switch.mixer_hc1_pumpstatus 7 1 1 3 1
MZ100 mixer 193 hc1.activated activated boolean True switch.mixer_hc1_activated switch.mixer_hc1_activated 7 1 1 4 1
MZ100 mixer 193 hc1.valvesettime time to set valve uint8 (>=10<=600) seconds True number.mixer_hc1_time_to_set_valve number.mixer_hc1_valvesettime 7 1 10 5 1
MZ100 mixer 193 hc1.flowtempoffset flow temperature offset for mixer uint8 (>=0<=20) K True number.mixer_hc1_flow_temperature_offset_for_mixer number.mixer_hc1_flowtempoffset 7 1 1 7 1
HM210 mixer 248 hc1.flowtemphc flow temperature (TC1) uint16 (>=0<=3199) C False sensor.mixer_hc1_flow_temperature_(TC1) sensor.mixer_hc1_flowtemphc 7 1 1/10 0 1
HM210 mixer 248 hc1.valvestatus mixing valve actuator (VC1) uint8 (>=0<=100) % False sensor.mixer_hc1_mixing_valve_actuator_(VC1) sensor.mixer_hc1_valvestatus 7 1 1 1 1
HM210 mixer 248 hc1.flowsettemp setpoint flow temperature uint8 (>=0<=254) C True number.mixer_hc1_setpoint_flow_temperature number.mixer_hc1_flowsettemp 7 1 1 2 1
HM210 mixer 248 hc1.pumpstatus pump status (PC1) boolean True switch.mixer_hc1_pump_status_(PC1) switch.mixer_hc1_pumpstatus 7 1 1 3 1
HM210 mixer 248 hc1.activated activated boolean True switch.mixer_hc1_activated switch.mixer_hc1_activated 7 1 1 4 1
HM210 mixer 248 hc1.valvesettime time to set valve uint8 (>=10<=600) seconds True number.mixer_hc1_time_to_set_valve number.mixer_hc1_valvesettime 7 1 10 5 1
HM210 mixer 248 hc1.flowtempoffset flow temperature offset for mixer uint8 (>=0<=20) K True number.mixer_hc1_flow_temperature_offset_for_mixer number.mixer_hc1_flowtempoffset 7 1 1 7 1
SM10 solar 73 collectortemp collector temperature (TS1) int16 (>=-3199<=3199) C False sensor.solar_collector_temperature_(TS1) sensor.solar_collectortemp 8 0 1/10 0 1
SM10 solar 73 cylbottomtemp cylinder bottom temperature (TS2) int16 (>=-3199<=3199) C False sensor.solar_cylinder_bottom_temperature_(TS2) sensor.solar_cylbottomtemp 8 0 1/10 1 1
SM10 solar 73 solarpump pump (PS1) boolean False binary_sensor.solar_pump_(PS1) binary_sensor.solar_solarpump 8 0 1 2 1
SM10 solar 73 pumpworktime pump working time time (>=0<=16777214) minutes False sensor.solar_pump_working_time sensor.solar_pumpworktime 8 0 1 3 2
SM10 solar 73 cylmaxtemp maximum cylinder temperature uint8 (>=0<=254) C True number.solar_maximum_cylinder_temperature number.solar_cylmaxtemp 8 0 1 5 1
SM10 solar 73 collectorshutdown collector shutdown boolean False binary_sensor.solar_collector_shutdown binary_sensor.solar_collectorshutdown 8 0 1 6 1
SM10 solar 73 cylheated cyl heated boolean False binary_sensor.solar_cyl_heated binary_sensor.solar_cylheated 8 0 1 7 1
SM10 solar 73 solarpumpmod pump modulation (PS1) uint8 (>=0<=100) % False sensor.solar_pump_modulation_(PS1) sensor.solar_solarpumpmod 8 0 1 8 1
SM10 solar 73 pumpminmod minimum pump modulation uint8 (>=0<=100) % True number.solar_minimum_pump_modulation number.solar_pumpminmod 8 0 1 9 1
SM10 solar 73 turnondiff pump turn on difference uint8 (>=0<=254) C True number.solar_pump_turn_on_difference number.solar_turnondiff 8 0 1 10 1
SM10 solar 73 turnoffdiff pump turn off difference uint8 (>=0<=254) C True number.solar_pump_turn_off_difference number.solar_turnoffdiff 8 0 1 11 1
SM10 solar 73 solarpower actual solar power int16 (>=-31999<=31999) W False sensor.solar_actual_solar_power sensor.solar_solarpower 8 0 1 12 1
SM10 solar 73 energylasthour energy last hour uint24 (>=0<=1677721) Wh False sensor.solar_energy_last_hour sensor.solar_energylasthour 8 0 1/10 13 2
SM10 solar 73 maxflow maximum solar flow uint8 (>=0<=25) l/min True number.solar_maximum_solar_flow number.solar_maxflow 8 0 1/10 15 1
SM10 solar 73 dhw.mintemp minimum temperature uint8 (>=0<=254) C True number.solar_dhw_minimum_temperature number.solar_dhw_mintemp 8 9 1 0 1
SM10 solar 73 solarenabled solarmodule enabled boolean True switch.solar_solarmodule_enabled switch.solar_solarenabled 8 0 1 16 1
ISM1 solar 101 collectortemp collector temperature (TS1) int16 (>=-3199<=3199) C False sensor.solar_collector_temperature_(TS1) sensor.solar_collectortemp 8 0 1/10 0 1
ISM1 solar 101 cylbottomtemp cylinder bottom temperature (TS2) int16 (>=-3199<=3199) C False sensor.solar_cylinder_bottom_temperature_(TS2) sensor.solar_cylbottomtemp 8 0 1/10 1 1
ISM1 solar 101 solarpump pump (PS1) boolean False binary_sensor.solar_pump_(PS1) binary_sensor.solar_solarpump 8 0 1 2 1
ISM1 solar 101 pumpworktime pump working time time (>=0<=16777214) minutes False sensor.solar_pump_working_time sensor.solar_pumpworktime 8 0 1 3 2
ISM1 solar 101 cylmaxtemp maximum cylinder temperature uint8 (>=0<=254) C True number.solar_maximum_cylinder_temperature number.solar_cylmaxtemp 8 0 1 5 1
ISM1 solar 101 collectorshutdown collector shutdown boolean False binary_sensor.solar_collector_shutdown binary_sensor.solar_collectorshutdown 8 0 1 6 1
ISM1 solar 101 cylheated cyl heated boolean False binary_sensor.solar_cyl_heated binary_sensor.solar_cylheated 8 0 1 7 1
ISM1 solar 101 cylmiddletemp cylinder middle temperature (TS3) int16 (>=-3199<=3199) C False sensor.solar_cylinder_middle_temperature_(TS3) sensor.solar_cylmiddletemp 8 0 1/10 17 1
ISM1 solar 101 retheatassist return temperature heat assistance (TS4) int16 (>=-3199<=3199) C False sensor.solar_return_temperature_heat_assistance_(TS4) sensor.solar_retheatassist 8 0 1/10 18 1
ISM1 solar 101 heatassistvalve heat assistance valve (M1) boolean False binary_sensor.solar_heat_assistance_valve_(M1) binary_sensor.solar_heatassistvalve 8 0 1 19 1
ISM1 solar 101 energylasthour energy last hour uint24 (>=0<=1677721) Wh False sensor.solar_energy_last_hour sensor.solar_energylasthour 8 0 1/10 13 2
ISM2 solar 103 collectortemp collector temperature (TS1) int16 (>=-3199<=3199) C False sensor.solar_collector_temperature_(TS1) sensor.solar_collectortemp 8 0 1/10 0 1
ISM2 solar 103 cylbottomtemp cylinder bottom temperature (TS2) int16 (>=-3199<=3199) C False sensor.solar_cylinder_bottom_temperature_(TS2) sensor.solar_cylbottomtemp 8 0 1/10 1 1
ISM2 solar 103 solarpump pump (PS1) boolean False binary_sensor.solar_pump_(PS1) binary_sensor.solar_solarpump 8 0 1 2 1
ISM2 solar 103 pumpworktime pump working time time (>=0<=16777214) minutes False sensor.solar_pump_working_time sensor.solar_pumpworktime 8 0 1 3 2
ISM2 solar 103 cylmaxtemp maximum cylinder temperature uint8 (>=0<=254) C True number.solar_maximum_cylinder_temperature number.solar_cylmaxtemp 8 0 1 5 1
ISM2 solar 103 collectorshutdown collector shutdown boolean False binary_sensor.solar_collector_shutdown binary_sensor.solar_collectorshutdown 8 0 1 6 1
ISM2 solar 103 cylheated cyl heated boolean False binary_sensor.solar_cyl_heated binary_sensor.solar_cylheated 8 0 1 7 1
ISM2 solar 103 cylmiddletemp cylinder middle temperature (TS3) int16 (>=-3199<=3199) C False sensor.solar_cylinder_middle_temperature_(TS3) sensor.solar_cylmiddletemp 8 0 1/10 17 1
ISM2 solar 103 retheatassist return temperature heat assistance (TS4) int16 (>=-3199<=3199) C False sensor.solar_return_temperature_heat_assistance_(TS4) sensor.solar_retheatassist 8 0 1/10 18 1
ISM2 solar 103 heatassistvalve heat assistance valve (M1) boolean False binary_sensor.solar_heat_assistance_valve_(M1) binary_sensor.solar_heatassistvalve 8 0 1 19 1
ISM2 solar 103 energylasthour energy last hour uint24 (>=0<=1677721) Wh False sensor.solar_energy_last_hour sensor.solar_energylasthour 8 0 1/10 13 2
SM50 solar 162 collectortemp collector temperature (TS1) int16 (>=-3199<=3199) C False sensor.solar_collector_temperature_(TS1) sensor.solar_collectortemp 8 0 1/10 0 1
SM50 solar 162 cylbottomtemp cylinder bottom temperature (TS2) int16 (>=-3199<=3199) C False sensor.solar_cylinder_bottom_temperature_(TS2) sensor.solar_cylbottomtemp 8 0 1/10 1 1
SM50 solar 162 solarpump pump (PS1) boolean False binary_sensor.solar_pump_(PS1) binary_sensor.solar_solarpump 8 0 1 2 1
SM50 solar 162 pumpworktime pump working time time (>=0<=16777214) minutes False sensor.solar_pump_working_time sensor.solar_pumpworktime 8 0 1 3 2
SM50 solar 162 cylmaxtemp maximum cylinder temperature uint8 (>=0<=254) C True number.solar_maximum_cylinder_temperature number.solar_cylmaxtemp 8 0 1 5 1
SM50 solar 162 collectorshutdown collector shutdown boolean False binary_sensor.solar_collector_shutdown binary_sensor.solar_collectorshutdown 8 0 1 6 1
SM50 solar 162 cylheated cyl heated boolean False binary_sensor.solar_cyl_heated binary_sensor.solar_cylheated 8 0 1 7 1
SM50 solar 162 solarpumpmod pump modulation (PS1) uint8 (>=0<=100) % False sensor.solar_pump_modulation_(PS1) sensor.solar_solarpumpmod 8 0 1 8 1
SM50 solar 162 pumpminmod minimum pump modulation uint8 (>=0<=100) % True number.solar_minimum_pump_modulation number.solar_pumpminmod 8 0 5 9 1
SM50 solar 162 turnondiff pump turn on difference uint8 (>=0<=25) C True number.solar_pump_turn_on_difference number.solar_turnondiff 8 0 1/10 10 1
SM50 solar 162 turnoffdiff pump turn off difference uint8 (>=0<=25) C True number.solar_pump_turn_off_difference number.solar_turnoffdiff 8 0 1/10 11 1
SM50 solar 162 collector2temp collector 2 temperature (TS7) int16 (>=-3199<=3199) C False sensor.solar_collector_2_temperature_(TS7) sensor.solar_collector2temp 8 0 1/10 20 1
SM50 solar 162 cylmiddletemp cylinder middle temperature (TS3) int16 (>=-3199<=3199) C False sensor.solar_cylinder_middle_temperature_(TS3) sensor.solar_cylmiddletemp 8 0 1/10 17 1
SM50 solar 162 retheatassist return temperature heat assistance (TS4) int16 (>=-3199<=3199) C False sensor.solar_return_temperature_heat_assistance_(TS4) sensor.solar_retheatassist 8 0 1/10 18 1
SM50 solar 162 heatassistvalve heat assistance valve (M1) boolean False binary_sensor.solar_heat_assistance_valve_(M1) binary_sensor.solar_heatassistvalve 8 0 1 19 1
SM50 solar 162 heatassistpower heat assistance valve power (M1) uint8 (>=0<=100) % False sensor.solar_heat_assistance_valve_power_(M1) sensor.solar_heatassistpower 8 0 1 21 1
SM50 solar 162 solarpump2 pump 2 (PS4) boolean False binary_sensor.solar_pump_2_(PS4) binary_sensor.solar_solarpump2 8 0 1 22 1
SM50 solar 162 solarpump2mod pump 2 modulation (PS4) uint8 (>=0<=100) % False sensor.solar_pump_2_modulation_(PS4) sensor.solar_solarpump2mod 8 0 1 23 1
SM50 solar 162 cyl2bottomtemp second cylinder bottom temperature (TS5) int16 (>=-3199<=3199) C False sensor.solar_second_cylinder_bottom_temperature_(TS5) sensor.solar_cyl2bottomtemp 8 0 1/10 24 1
SM50 solar 162 cyl3bottomtemp third cylinder bottom temperature (TS11) int16 (>=-3199<=3199) C False sensor.solar_third_cylinder_bottom_temperature_(TS11) sensor.solar_cyl3bottomtemp 8 0 1/10 25 1
SM50 solar 162 cyltoptemp cylinder top temperature (TS10) int16 (>=-3199<=3199) C False sensor.solar_cylinder_top_temperature_(TS10) sensor.solar_cyltoptemp 8 0 1/10 26 1
SM50 solar 162 heatexchangertemp heat exchanger temperature (TS6) int16 (>=-3199<=3199) C False sensor.solar_heat_exchanger_temperature_(TS6) sensor.solar_heatexchangertemp 8 0 1/10 27 1
SM50 solar 162 cylpumpmod cylinder pump modulation (PS5) uint8 (>=0<=100) % False sensor.solar_cylinder_pump_modulation_(PS5) sensor.solar_cylpumpmod 8 0 1 28 1
SM50 solar 162 valvestatus valve status boolean False binary_sensor.solar_valve_status binary_sensor.solar_valvestatus 8 0 1 29 1
SM50 solar 162 vs1status valve status VS1 boolean False binary_sensor.solar_valve_status_VS1 binary_sensor.solar_vs1status 8 0 1 30 1
SM50 solar 162 vs3status valve status VS3 boolean False binary_sensor.solar_valve_status_VS3 binary_sensor.solar_vs3status 8 0 1 31 1
SM50 solar 162 transferpump transfer pump boolean False binary_sensor.solar_transfer_pump binary_sensor.solar_transferpump 8 0 1 32 1
SM50 solar 162 transferpumpmod transfer pump modulation uint8 (>=0<=100) % False sensor.solar_transfer_pump_modulation sensor.solar_transferpumpmod 8 0 1 33 1
SM50 solar 162 collectormaxtemp maximum collector temperature uint8 (>=0<=254) C True number.solar_maximum_collector_temperature number.solar_collectormaxtemp 8 0 1 34 1
SM50 solar 162 collectormintemp minimum collector temperature uint8 (>=0<=254) C True number.solar_minimum_collector_temperature number.solar_collectormintemp 8 0 1 35 1
SM50 solar 162 energylasthour energy last hour uint24 (>=0<=1677721) Wh False sensor.solar_energy_last_hour sensor.solar_energylasthour 8 0 1/10 13 2
SM50 solar 162 energytoday total energy today uint24 (>=0<=16777214) Wh False sensor.solar_total_energy_today sensor.solar_energytoday 8 0 1 36 2
SM50 solar 162 energytotal total energy uint24 (>=0<=1677721) kWh False sensor.solar_total_energy sensor.solar_energytotal 8 0 1/10 38 2
SM50 solar 162 pump2worktime pump 2 working time time (>=0<=16777214) minutes False sensor.solar_pump_2_working_time sensor.solar_pump2worktime 8 0 1 40 2
SM50 solar 162 m1worktime differential control working time time (>=0<=16777214) minutes False sensor.solar_differential_control_working_time sensor.solar_m1worktime 8 0 1 42 2
SM50 solar 162 heattransfersystem heattransfer system boolean True switch.solar_heattransfer_system switch.solar_heattransfersystem 8 0 1 44 1
SM50 solar 162 externalcyl external cylinder boolean True switch.solar_external_cylinder switch.solar_externalcyl 8 0 1 45 1
SM50 solar 162 thermaldisinfect thermal disinfection boolean True switch.solar_thermal_disinfection switch.solar_thermaldisinfect 8 0 1 46 1
SM50 solar 162 heatmetering heatmetering boolean True switch.solar_heatmetering switch.solar_heatmetering 8 0 1 47 1
SM50 solar 162 activated activated boolean True switch.solar_activated switch.solar_activated 8 0 1 48 1
SM50 solar 162 solarpumpmode solar pump mode enum [constant|pwm|analog] True select.solar_solar_pump_mode select.solar_solarpumpmode 8 0 1 49 1
SM50 solar 162 solarpumpkick solar pump kick boolean True switch.solar_solar_pump_kick switch.solar_solarpumpkick 8 0 1 50 1
SM50 solar 162 plainwatermode plain water mode boolean True switch.solar_plain_water_mode switch.solar_plainwatermode 8 0 1 51 1
SM50 solar 162 doublematchflow doublematchflow boolean True switch.solar_doublematchflow switch.solar_doublematchflow 8 0 1 52 1
SM50 solar 162 pump2minmod minimum pump 2 modulation uint8 (>=0<=100) % True number.solar_minimum_pump_2_modulation number.solar_pump2minmod 8 0 1 53 1
SM50 solar 162 turnondiff2 pump 2 turn on difference uint8 (>=0<=25) C True number.solar_pump_2_turn_on_difference number.solar_turnondiff2 8 0 1/10 54 1
SM50 solar 162 turnoffdiff2 pump 2 turn off difference uint8 (>=0<=25) C True number.solar_pump_2_turn_off_difference number.solar_turnoffdiff2 8 0 1/10 55 1
SM50 solar 162 pump2kick pump kick 2 boolean True switch.solar_pump_kick_2 switch.solar_pump2kick 8 0 1 56 1
SM50 solar 162 climatezone climate zone uint8 (>=0<=254) True number.solar_climate_zone number.solar_climatezone 8 0 1 57 1
SM50 solar 162 collector1area collector 1 area uint16 (>=0<=3199) m² True number.solar_collector_1_area number.solar_collector1area 8 0 1/10 58 1
SM50 solar 162 collector1type collector 1 type enum [flat|vacuum] True select.solar_collector_1_type select.solar_collector1type 8 0 1 59 1
SM50 solar 162 collector2area collector 2 area uint16 (>=0<=3199) m² True number.solar_collector_2_area number.solar_collector2area 8 0 1/10 60 1
SM50 solar 162 collector2type collector 2 type enum [flat|vacuum] True select.solar_collector_2_type select.solar_collector2type 8 0 1 61 1
SM50 solar 162 cylpriority cylinder priority enum [cyl 1|cyl 2] True select.solar_cylinder_priority select.solar_cylpriority 8 0 1 62 1
SM50 solar 162 heatcntflowtemp heat counter flow temperature uint16 (>=0<=3199) C False sensor.solar_heat_counter_flow_temperature sensor.solar_heatcntflowtemp 8 0 1/10 63 1
SM50 solar 162 heatcntrettemp heat counter return temperature uint16 (>=0<=3199) C False sensor.solar_heat_counter_return_temperature sensor.solar_heatcntrettemp 8 0 1/10 64 1
SM50 solar 162 heatcnt heat counter impulses uint8 (>=0<=254) False sensor.solar_heat_counter_impulses sensor.solar_heatcnt 8 0 1 65 1
SM50 solar 162 swapflowtemp swap flow temperature (TS14) uint16 (>=0<=3199) C False sensor.solar_swap_flow_temperature_(TS14) sensor.solar_swapflowtemp 8 0 1/10 66 1
SM50 solar 162 swaprettemp swap return temperature (TS15) uint16 (>=0<=3199) C False sensor.solar_swap_return_temperature_(TS15) sensor.solar_swaprettemp 8 0 1/10 67 1
SM100, MS100 solar 163 collectortemp collector temperature (TS1) int16 (>=-3199<=3199) C False sensor.solar_collector_temperature_(TS1) sensor.solar_collectortemp 8 0 1/10 0 1
SM100, MS100 solar 163 cylbottomtemp cylinder bottom temperature (TS2) int16 (>=-3199<=3199) C False sensor.solar_cylinder_bottom_temperature_(TS2) sensor.solar_cylbottomtemp 8 0 1/10 1 1
SM100, MS100 solar 163 solarpump pump (PS1) boolean False binary_sensor.solar_pump_(PS1) binary_sensor.solar_solarpump 8 0 1 2 1
SM100, MS100 solar 163 pumpworktime pump working time time (>=0<=16777214) minutes False sensor.solar_pump_working_time sensor.solar_pumpworktime 8 0 1 3 2
SM100, MS100 solar 163 cylmaxtemp maximum cylinder temperature uint8 (>=0<=254) C True number.solar_maximum_cylinder_temperature number.solar_cylmaxtemp 8 0 1 5 1
SM100, MS100 solar 163 collectorshutdown collector shutdown boolean False binary_sensor.solar_collector_shutdown binary_sensor.solar_collectorshutdown 8 0 1 6 1
SM100, MS100 solar 163 cylheated cyl heated boolean False binary_sensor.solar_cyl_heated binary_sensor.solar_cylheated 8 0 1 7 1
SM100, MS100 solar 163 solarpumpmod pump modulation (PS1) uint8 (>=0<=100) % False sensor.solar_pump_modulation_(PS1) sensor.solar_solarpumpmod 8 0 1 8 1
SM100, MS100 solar 163 pumpminmod minimum pump modulation uint8 (>=0<=100) % True number.solar_minimum_pump_modulation number.solar_pumpminmod 8 0 5 9 1
SM100, MS100 solar 163 turnondiff pump turn on difference uint8 (>=0<=25) C True number.solar_pump_turn_on_difference number.solar_turnondiff 8 0 1/10 10 1
SM100, MS100 solar 163 turnoffdiff pump turn off difference uint8 (>=0<=25) C True number.solar_pump_turn_off_difference number.solar_turnoffdiff 8 0 1/10 11 1
SM100, MS100 solar 163 collector2temp collector 2 temperature (TS7) int16 (>=-3199<=3199) C False sensor.solar_collector_2_temperature_(TS7) sensor.solar_collector2temp 8 0 1/10 20 1
SM100, MS100 solar 163 cylmiddletemp cylinder middle temperature (TS3) int16 (>=-3199<=3199) C False sensor.solar_cylinder_middle_temperature_(TS3) sensor.solar_cylmiddletemp 8 0 1/10 17 1
SM100, MS100 solar 163 retheatassist return temperature heat assistance (TS4) int16 (>=-3199<=3199) C False sensor.solar_return_temperature_heat_assistance_(TS4) sensor.solar_retheatassist 8 0 1/10 18 1
SM100, MS100 solar 163 heatassistvalve heat assistance valve (M1) boolean False binary_sensor.solar_heat_assistance_valve_(M1) binary_sensor.solar_heatassistvalve 8 0 1 19 1
SM100, MS100 solar 163 heatassistpower heat assistance valve power (M1) uint8 (>=0<=100) % False sensor.solar_heat_assistance_valve_power_(M1) sensor.solar_heatassistpower 8 0 1 21 1
SM100, MS100 solar 163 solarpump2 pump 2 (PS4) boolean False binary_sensor.solar_pump_2_(PS4) binary_sensor.solar_solarpump2 8 0 1 22 1
SM100, MS100 solar 163 solarpump2mod pump 2 modulation (PS4) uint8 (>=0<=100) % False sensor.solar_pump_2_modulation_(PS4) sensor.solar_solarpump2mod 8 0 1 23 1
SM100, MS100 solar 163 cyl2bottomtemp second cylinder bottom temperature (TS5) int16 (>=-3199<=3199) C False sensor.solar_second_cylinder_bottom_temperature_(TS5) sensor.solar_cyl2bottomtemp 8 0 1/10 24 1
SM100, MS100 solar 163 cyl3bottomtemp third cylinder bottom temperature (TS11) int16 (>=-3199<=3199) C False sensor.solar_third_cylinder_bottom_temperature_(TS11) sensor.solar_cyl3bottomtemp 8 0 1/10 25 1
SM100, MS100 solar 163 cyltoptemp cylinder top temperature (TS10) int16 (>=-3199<=3199) C False sensor.solar_cylinder_top_temperature_(TS10) sensor.solar_cyltoptemp 8 0 1/10 26 1
SM100, MS100 solar 163 heatexchangertemp heat exchanger temperature (TS6) int16 (>=-3199<=3199) C False sensor.solar_heat_exchanger_temperature_(TS6) sensor.solar_heatexchangertemp 8 0 1/10 27 1
SM100, MS100 solar 163 cylpumpmod cylinder pump modulation (PS5) uint8 (>=0<=100) % False sensor.solar_cylinder_pump_modulation_(PS5) sensor.solar_cylpumpmod 8 0 1 28 1
SM100, MS100 solar 163 valvestatus valve status boolean False binary_sensor.solar_valve_status binary_sensor.solar_valvestatus 8 0 1 29 1
SM100, MS100 solar 163 vs1status valve status VS1 boolean False binary_sensor.solar_valve_status_VS1 binary_sensor.solar_vs1status 8 0 1 30 1
SM100, MS100 solar 163 vs3status valve status VS3 boolean False binary_sensor.solar_valve_status_VS3 binary_sensor.solar_vs3status 8 0 1 31 1
SM100, MS100 solar 163 transferpump transfer pump boolean False binary_sensor.solar_transfer_pump binary_sensor.solar_transferpump 8 0 1 32 1
SM100, MS100 solar 163 transferpumpmod transfer pump modulation uint8 (>=0<=100) % False sensor.solar_transfer_pump_modulation sensor.solar_transferpumpmod 8 0 1 33 1
SM100, MS100 solar 163 collectormaxtemp maximum collector temperature uint8 (>=0<=254) C True number.solar_maximum_collector_temperature number.solar_collectormaxtemp 8 0 1 34 1
SM100, MS100 solar 163 collectormintemp minimum collector temperature uint8 (>=0<=254) C True number.solar_minimum_collector_temperature number.solar_collectormintemp 8 0 1 35 1
SM100, MS100 solar 163 energylasthour energy last hour uint24 (>=0<=1677721) Wh False sensor.solar_energy_last_hour sensor.solar_energylasthour 8 0 1/10 13 2
SM100, MS100 solar 163 energytoday total energy today uint24 (>=0<=16777214) Wh False sensor.solar_total_energy_today sensor.solar_energytoday 8 0 1 36 2
SM100, MS100 solar 163 energytotal total energy uint24 (>=0<=1677721) kWh False sensor.solar_total_energy sensor.solar_energytotal 8 0 1/10 38 2
SM100, MS100 solar 163 pump2worktime pump 2 working time time (>=0<=16777214) minutes False sensor.solar_pump_2_working_time sensor.solar_pump2worktime 8 0 1 40 2
SM100, MS100 solar 163 m1worktime differential control working time time (>=0<=16777214) minutes False sensor.solar_differential_control_working_time sensor.solar_m1worktime 8 0 1 42 2
SM100, MS100 solar 163 heattransfersystem heattransfer system boolean True switch.solar_heattransfer_system switch.solar_heattransfersystem 8 0 1 44 1
SM100, MS100 solar 163 externalcyl external cylinder boolean True switch.solar_external_cylinder switch.solar_externalcyl 8 0 1 45 1
SM100, MS100 solar 163 thermaldisinfect thermal disinfection boolean True switch.solar_thermal_disinfection switch.solar_thermaldisinfect 8 0 1 46 1
SM100, MS100 solar 163 heatmetering heatmetering boolean True switch.solar_heatmetering switch.solar_heatmetering 8 0 1 47 1
SM100, MS100 solar 163 activated activated boolean True switch.solar_activated switch.solar_activated 8 0 1 48 1
SM100, MS100 solar 163 solarpumpmode solar pump mode enum [constant|pwm|analog] True select.solar_solar_pump_mode select.solar_solarpumpmode 8 0 1 49 1
SM100, MS100 solar 163 solarpumpkick solar pump kick boolean True switch.solar_solar_pump_kick switch.solar_solarpumpkick 8 0 1 50 1
SM100, MS100 solar 163 plainwatermode plain water mode boolean True switch.solar_plain_water_mode switch.solar_plainwatermode 8 0 1 51 1
SM100, MS100 solar 163 doublematchflow doublematchflow boolean True switch.solar_doublematchflow switch.solar_doublematchflow 8 0 1 52 1
SM100, MS100 solar 163 pump2minmod minimum pump 2 modulation uint8 (>=0<=100) % True number.solar_minimum_pump_2_modulation number.solar_pump2minmod 8 0 1 53 1
SM100, MS100 solar 163 turnondiff2 pump 2 turn on difference uint8 (>=0<=25) C True number.solar_pump_2_turn_on_difference number.solar_turnondiff2 8 0 1/10 54 1
SM100, MS100 solar 163 turnoffdiff2 pump 2 turn off difference uint8 (>=0<=25) C True number.solar_pump_2_turn_off_difference number.solar_turnoffdiff2 8 0 1/10 55 1
SM100, MS100 solar 163 pump2kick pump kick 2 boolean True switch.solar_pump_kick_2 switch.solar_pump2kick 8 0 1 56 1
SM100, MS100 solar 163 climatezone climate zone uint8 (>=0<=254) True number.solar_climate_zone number.solar_climatezone 8 0 1 57 1
SM100, MS100 solar 163 collector1area collector 1 area uint16 (>=0<=3199) m² True number.solar_collector_1_area number.solar_collector1area 8 0 1/10 58 1
SM100, MS100 solar 163 collector1type collector 1 type enum [flat|vacuum] True select.solar_collector_1_type select.solar_collector1type 8 0 1 59 1
SM100, MS100 solar 163 collector2area collector 2 area uint16 (>=0<=3199) m² True number.solar_collector_2_area number.solar_collector2area 8 0 1/10 60 1
SM100, MS100 solar 163 collector2type collector 2 type enum [flat|vacuum] True select.solar_collector_2_type select.solar_collector2type 8 0 1 61 1
SM100, MS100 solar 163 cylpriority cylinder priority enum [cyl 1|cyl 2] True select.solar_cylinder_priority select.solar_cylpriority 8 0 1 62 1
SM100, MS100 solar 163 heatcntflowtemp heat counter flow temperature uint16 (>=0<=3199) C False sensor.solar_heat_counter_flow_temperature sensor.solar_heatcntflowtemp 8 0 1/10 63 1
SM100, MS100 solar 163 heatcntrettemp heat counter return temperature uint16 (>=0<=3199) C False sensor.solar_heat_counter_return_temperature sensor.solar_heatcntrettemp 8 0 1/10 64 1
SM100, MS100 solar 163 heatcnt heat counter impulses uint8 (>=0<=254) False sensor.solar_heat_counter_impulses sensor.solar_heatcnt 8 0 1 65 1
SM100, MS100 solar 163 swapflowtemp swap flow temperature (TS14) uint16 (>=0<=3199) C False sensor.solar_swap_flow_temperature_(TS14) sensor.solar_swapflowtemp 8 0 1/10 66 1
SM100, MS100 solar 163 swaprettemp swap return temperature (TS15) uint16 (>=0<=3199) C False sensor.solar_swap_return_temperature_(TS15) sensor.solar_swaprettemp 8 0 1/10 67 1
SM200, MS200 solar 164 collectortemp collector temperature (TS1) int16 (>=-3199<=3199) C False sensor.solar_collector_temperature_(TS1) sensor.solar_collectortemp 8 0 1/10 0 1
SM200, MS200 solar 164 cylbottomtemp cylinder bottom temperature (TS2) int16 (>=-3199<=3199) C False sensor.solar_cylinder_bottom_temperature_(TS2) sensor.solar_cylbottomtemp 8 0 1/10 1 1
SM200, MS200 solar 164 solarpump pump (PS1) boolean False binary_sensor.solar_pump_(PS1) binary_sensor.solar_solarpump 8 0 1 2 1
SM200, MS200 solar 164 pumpworktime pump working time time (>=0<=16777214) minutes False sensor.solar_pump_working_time sensor.solar_pumpworktime 8 0 1 3 2
SM200, MS200 solar 164 cylmaxtemp maximum cylinder temperature uint8 (>=0<=254) C True number.solar_maximum_cylinder_temperature number.solar_cylmaxtemp 8 0 1 5 1
SM200, MS200 solar 164 collectorshutdown collector shutdown boolean False binary_sensor.solar_collector_shutdown binary_sensor.solar_collectorshutdown 8 0 1 6 1
SM200, MS200 solar 164 cylheated cyl heated boolean False binary_sensor.solar_cyl_heated binary_sensor.solar_cylheated 8 0 1 7 1
SM200, MS200 solar 164 solarpumpmod pump modulation (PS1) uint8 (>=0<=100) % False sensor.solar_pump_modulation_(PS1) sensor.solar_solarpumpmod 8 0 1 8 1
SM200, MS200 solar 164 pumpminmod minimum pump modulation uint8 (>=0<=100) % True number.solar_minimum_pump_modulation number.solar_pumpminmod 8 0 5 9 1
SM200, MS200 solar 164 turnondiff pump turn on difference uint8 (>=0<=25) C True number.solar_pump_turn_on_difference number.solar_turnondiff 8 0 1/10 10 1
SM200, MS200 solar 164 turnoffdiff pump turn off difference uint8 (>=0<=25) C True number.solar_pump_turn_off_difference number.solar_turnoffdiff 8 0 1/10 11 1
SM200, MS200 solar 164 collector2temp collector 2 temperature (TS7) int16 (>=-3199<=3199) C False sensor.solar_collector_2_temperature_(TS7) sensor.solar_collector2temp 8 0 1/10 20 1
SM200, MS200 solar 164 cylmiddletemp cylinder middle temperature (TS3) int16 (>=-3199<=3199) C False sensor.solar_cylinder_middle_temperature_(TS3) sensor.solar_cylmiddletemp 8 0 1/10 17 1
SM200, MS200 solar 164 retheatassist return temperature heat assistance (TS4) int16 (>=-3199<=3199) C False sensor.solar_return_temperature_heat_assistance_(TS4) sensor.solar_retheatassist 8 0 1/10 18 1
SM200, MS200 solar 164 heatassistvalve heat assistance valve (M1) boolean False binary_sensor.solar_heat_assistance_valve_(M1) binary_sensor.solar_heatassistvalve 8 0 1 19 1
SM200, MS200 solar 164 heatassistpower heat assistance valve power (M1) uint8 (>=0<=100) % False sensor.solar_heat_assistance_valve_power_(M1) sensor.solar_heatassistpower 8 0 1 21 1
SM200, MS200 solar 164 solarpump2 pump 2 (PS4) boolean False binary_sensor.solar_pump_2_(PS4) binary_sensor.solar_solarpump2 8 0 1 22 1
SM200, MS200 solar 164 solarpump2mod pump 2 modulation (PS4) uint8 (>=0<=100) % False sensor.solar_pump_2_modulation_(PS4) sensor.solar_solarpump2mod 8 0 1 23 1
SM200, MS200 solar 164 cyl2bottomtemp second cylinder bottom temperature (TS5) int16 (>=-3199<=3199) C False sensor.solar_second_cylinder_bottom_temperature_(TS5) sensor.solar_cyl2bottomtemp 8 0 1/10 24 1
SM200, MS200 solar 164 cyl3bottomtemp third cylinder bottom temperature (TS11) int16 (>=-3199<=3199) C False sensor.solar_third_cylinder_bottom_temperature_(TS11) sensor.solar_cyl3bottomtemp 8 0 1/10 25 1
SM200, MS200 solar 164 cyltoptemp cylinder top temperature (TS10) int16 (>=-3199<=3199) C False sensor.solar_cylinder_top_temperature_(TS10) sensor.solar_cyltoptemp 8 0 1/10 26 1
SM200, MS200 solar 164 heatexchangertemp heat exchanger temperature (TS6) int16 (>=-3199<=3199) C False sensor.solar_heat_exchanger_temperature_(TS6) sensor.solar_heatexchangertemp 8 0 1/10 27 1
SM200, MS200 solar 164 cylpumpmod cylinder pump modulation (PS5) uint8 (>=0<=100) % False sensor.solar_cylinder_pump_modulation_(PS5) sensor.solar_cylpumpmod 8 0 1 28 1
SM200, MS200 solar 164 valvestatus valve status boolean False binary_sensor.solar_valve_status binary_sensor.solar_valvestatus 8 0 1 29 1
SM200, MS200 solar 164 vs1status valve status VS1 boolean False binary_sensor.solar_valve_status_VS1 binary_sensor.solar_vs1status 8 0 1 30 1
SM200, MS200 solar 164 vs3status valve status VS3 boolean False binary_sensor.solar_valve_status_VS3 binary_sensor.solar_vs3status 8 0 1 31 1
SM200, MS200 solar 164 transferpump transfer pump boolean False binary_sensor.solar_transfer_pump binary_sensor.solar_transferpump 8 0 1 32 1
SM200, MS200 solar 164 transferpumpmod transfer pump modulation uint8 (>=0<=100) % False sensor.solar_transfer_pump_modulation sensor.solar_transferpumpmod 8 0 1 33 1
SM200, MS200 solar 164 collectormaxtemp maximum collector temperature uint8 (>=0<=254) C True number.solar_maximum_collector_temperature number.solar_collectormaxtemp 8 0 1 34 1
SM200, MS200 solar 164 collectormintemp minimum collector temperature uint8 (>=0<=254) C True number.solar_minimum_collector_temperature number.solar_collectormintemp 8 0 1 35 1
SM200, MS200 solar 164 energylasthour energy last hour uint24 (>=0<=1677721) Wh False sensor.solar_energy_last_hour sensor.solar_energylasthour 8 0 1/10 13 2
SM200, MS200 solar 164 energytoday total energy today uint24 (>=0<=16777214) Wh False sensor.solar_total_energy_today sensor.solar_energytoday 8 0 1 36 2
SM200, MS200 solar 164 energytotal total energy uint24 (>=0<=1677721) kWh False sensor.solar_total_energy sensor.solar_energytotal 8 0 1/10 38 2
SM200, MS200 solar 164 pump2worktime pump 2 working time time (>=0<=16777214) minutes False sensor.solar_pump_2_working_time sensor.solar_pump2worktime 8 0 1 40 2
SM200, MS200 solar 164 m1worktime differential control working time time (>=0<=16777214) minutes False sensor.solar_differential_control_working_time sensor.solar_m1worktime 8 0 1 42 2
SM200, MS200 solar 164 heattransfersystem heattransfer system boolean True switch.solar_heattransfer_system switch.solar_heattransfersystem 8 0 1 44 1
SM200, MS200 solar 164 externalcyl external cylinder boolean True switch.solar_external_cylinder switch.solar_externalcyl 8 0 1 45 1
SM200, MS200 solar 164 thermaldisinfect thermal disinfection boolean True switch.solar_thermal_disinfection switch.solar_thermaldisinfect 8 0 1 46 1
SM200, MS200 solar 164 heatmetering heatmetering boolean True switch.solar_heatmetering switch.solar_heatmetering 8 0 1 47 1
SM200, MS200 solar 164 activated activated boolean True switch.solar_activated switch.solar_activated 8 0 1 48 1
SM200, MS200 solar 164 solarpumpmode solar pump mode enum [constant|pwm|analog] True select.solar_solar_pump_mode select.solar_solarpumpmode 8 0 1 49 1
SM200, MS200 solar 164 solarpumpkick solar pump kick boolean True switch.solar_solar_pump_kick switch.solar_solarpumpkick 8 0 1 50 1
SM200, MS200 solar 164 plainwatermode plain water mode boolean True switch.solar_plain_water_mode switch.solar_plainwatermode 8 0 1 51 1
SM200, MS200 solar 164 doublematchflow doublematchflow boolean True switch.solar_doublematchflow switch.solar_doublematchflow 8 0 1 52 1
SM200, MS200 solar 164 pump2minmod minimum pump 2 modulation uint8 (>=0<=100) % True number.solar_minimum_pump_2_modulation number.solar_pump2minmod 8 0 1 53 1
SM200, MS200 solar 164 turnondiff2 pump 2 turn on difference uint8 (>=0<=25) C True number.solar_pump_2_turn_on_difference number.solar_turnondiff2 8 0 1/10 54 1
SM200, MS200 solar 164 turnoffdiff2 pump 2 turn off difference uint8 (>=0<=25) C True number.solar_pump_2_turn_off_difference number.solar_turnoffdiff2 8 0 1/10 55 1
SM200, MS200 solar 164 pump2kick pump kick 2 boolean True switch.solar_pump_kick_2 switch.solar_pump2kick 8 0 1 56 1
SM200, MS200 solar 164 climatezone climate zone uint8 (>=0<=254) True number.solar_climate_zone number.solar_climatezone 8 0 1 57 1
SM200, MS200 solar 164 collector1area collector 1 area uint16 (>=0<=3199) m² True number.solar_collector_1_area number.solar_collector1area 8 0 1/10 58 1
SM200, MS200 solar 164 collector1type collector 1 type enum [flat|vacuum] True select.solar_collector_1_type select.solar_collector1type 8 0 1 59 1
SM200, MS200 solar 164 collector2area collector 2 area uint16 (>=0<=3199) m² True number.solar_collector_2_area number.solar_collector2area 8 0 1/10 60 1
SM200, MS200 solar 164 collector2type collector 2 type enum [flat|vacuum] True select.solar_collector_2_type select.solar_collector2type 8 0 1 61 1
SM200, MS200 solar 164 cylpriority cylinder priority enum [cyl 1|cyl 2] True select.solar_cylinder_priority select.solar_cylpriority 8 0 1 62 1
SM200, MS200 solar 164 heatcntflowtemp heat counter flow temperature uint16 (>=0<=3199) C False sensor.solar_heat_counter_flow_temperature sensor.solar_heatcntflowtemp 8 0 1/10 63 1
SM200, MS200 solar 164 heatcntrettemp heat counter return temperature uint16 (>=0<=3199) C False sensor.solar_heat_counter_return_temperature sensor.solar_heatcntrettemp 8 0 1/10 64 1
SM200, MS200 solar 164 heatcnt heat counter impulses uint8 (>=0<=254) False sensor.solar_heat_counter_impulses sensor.solar_heatcnt 8 0 1 65 1
SM200, MS200 solar 164 swapflowtemp swap flow temperature (TS14) uint16 (>=0<=3199) C False sensor.solar_swap_flow_temperature_(TS14) sensor.solar_swapflowtemp 8 0 1/10 66 1
SM200, MS200 solar 164 swaprettemp swap return temperature (TS15) uint16 (>=0<=3199) C False sensor.solar_swap_return_temperature_(TS15) sensor.solar_swaprettemp 8 0 1/10 67 1
HP Module heatpump 252 airhumidity relative air humidity uint8 (>=0<=100) % False sensor.heatpump_relative_air_humidity sensor.heatpump_airhumidity 9 0 1 0 1
HP Module heatpump 252 dewtemperature dew point temperature uint8 (>=0<=254) C False sensor.heatpump_dew_point_temperature sensor.heatpump_dewtemperature 9 0 1 1 1
HP Module heatpump 252 curflowtemp current flow temperature int16 (>=-3199<=3199) C False sensor.heatpump_current_flow_temperature sensor.heatpump_curflowtemp 9 0 1/10 2 1
HP Module heatpump 252 rettemp return temperature int16 (>=-3199<=3199) C False sensor.heatpump_return_temperature sensor.heatpump_rettemp 9 0 1/10 3 1
HP Module heatpump 252 sysrettemp system return temperature int16 (>=-3199<=3199) C False sensor.heatpump_system_return_temperature sensor.heatpump_sysrettemp 9 0 1/10 4 1
HP Module heatpump 252 hpta4 drain pan temp (TA4) int16 (>=-3199<=3199) C False sensor.heatpump_drain_pan_temp_(TA4) sensor.heatpump_hpta4 9 0 1/10 5 1
HP Module heatpump 252 hptr1 compressor temperature (TR1) int16 (>=-3199<=3199) C False sensor.heatpump_compressor_temperature_(TR1) sensor.heatpump_hptr1 9 0 1/10 6 1
HP Module heatpump 252 hptr3 refrigerant temperature liquid side (condenser output) (TR3) int16 (>=-3199<=3199) C False sensor.heatpump_refrigerant_temperature_liquid_side_(condenser_output)_(TR3) sensor.heatpump_hptr3 9 0 1/10 7 1
HP Module heatpump 252 hptr4 evaporator inlet temperature (TR4) int16 (>=-3199<=3199) C False sensor.heatpump_evaporator_inlet_temperature_(TR4) sensor.heatpump_hptr4 9 0 1/10 8 1
HP Module heatpump 252 hptr5 compressor inlet temperature (TR5) int16 (>=-3199<=3199) C False sensor.heatpump_compressor_inlet_temperature_(TR5) sensor.heatpump_hptr5 9 0 1/10 9 1
HP Module heatpump 252 hptr6 compressor outlet temperature (TR6) int16 (>=-3199<=3199) C False sensor.heatpump_compressor_outlet_temperature_(TR6) sensor.heatpump_hptr6 9 0 1/10 10 1
HP Module heatpump 252 hptl2 air inlet temperature (TL2) int16 (>=-3199<=3199) C False sensor.heatpump_air_inlet_temperature_(TL2) sensor.heatpump_hptl2 9 0 1/10 11 1
HP Module heatpump 252 hppl1 low pressure side temperature (PL1) int16 (>=-3199<=3199) C False sensor.heatpump_low_pressure_side_temperature_(PL1) sensor.heatpump_hppl1 9 0 1/10 12 1
HP Module heatpump 252 hpph1 high pressure side temperature (PH1) int16 (>=-3199<=3199) C False sensor.heatpump_high_pressure_side_temperature_(PH1) sensor.heatpump_hpph1 9 0 1/10 13 1
HP Module heatpump 252 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.heatpump_heating_pump_modulation sensor.heatpump_heatingpumpmod 9 0 1 14 1
HP Module heatpump 252 hpcompspd compressor speed uint8 (>=0<=100) % False sensor.heatpump_compressor_speed sensor.heatpump_hpcompspd 9 0 1 15 1
HP Module heatpump 252 hybridstrategy hybrid control strategy enum [cost optimized|co2 optimized|outside temperature alt.|outside temperature parallel|heatpump preferred|boiler only] True select.heatpump_hybrid_control_strategy select.heatpump_hybridstrategy 9 0 1 16 1
HP Module heatpump 252 lownoisemode low noise mode enum [off|reduced output|switch off hp|perm. reduced] True select.heatpump_low_noise_mode select.heatpump_lownoisemode 9 0 1 17 1
HP Module heatpump 252 lownoisestart low noise starttime uint8 (>=0<=23) hours True number.heatpump_low_noise_starttime number.heatpump_lownoisestart 9 0 1 18 1
HP Module heatpump 252 lownoisestop low noise stoptime uint8 (>=0<=23) hours True number.heatpump_low_noise_stoptime number.heatpump_lownoisestop 9 0 1 19 1
HP Module heatpump 252 dhw.hybriddhw hybrid DHW enum [eco|high comfort] True select.heatpump_dhw_hybrid_DHW select.heatpump_dhw_hybriddhw 9 9 1 0 1
HP Module heatpump 252 energypricegas energy price gas uint8 (>=0<=254) ct/kWh True number.heatpump_energy_price_gas number.heatpump_energypricegas 9 0 1 20 1
HP Module heatpump 252 energypriceel energy price electric uint8 (>=0<=254) ct/kWh True number.heatpump_energy_price_electric number.heatpump_energypriceel 9 0 1 21 1
HP Module heatpump 252 energyfeedpv feed in PV uint8 (>=0<=254) ct/kWh True number.heatpump_feed_in_PV number.heatpump_energyfeedpv 9 0 1 22 1
HP Module heatpump 252 switchovertemp outside switchover temperature int8 (>=-126<=126) C True number.heatpump_outside_switchover_temperature number.heatpump_switchovertemp 9 0 1 23 1
HP Module heatpump 252 airpurgemode air purge mode boolean True switch.heatpump_air_purge_mode switch.heatpump_airpurgemode 9 0 1 24 1
HP Module heatpump 252 heatpumpoutput heatpump output uint8 (>=0<=100) % True number.heatpump_heatpump_output number.heatpump_heatpumpoutput 9 0 1 25 1
HP Module heatpump 252 coolingcircuit cooling circuit boolean True switch.heatpump_cooling_circuit switch.heatpump_coolingcircuit 9 0 1 26 1
HP Module heatpump 252 compstartmod compressor start modulation uint8 (>=0<=100) % True number.heatpump_compressor_start_modulation number.heatpump_compstartmod 9 0 1 27 1
HP Module heatpump 252 heatdrainpan heat drain pan boolean True switch.heatpump_heat_drain_pan switch.heatpump_heatdrainpan 9 0 1 28 1
HP Module heatpump 252 heatcable heating cable boolean True switch.heatpump_heating_cable switch.heatpump_heatcable 9 0 1 29 1
HP Module heatpump 252 nrgtotal total energy uint24 (>=0<=167772) kWh False sensor.heatpump_total_energy sensor.heatpump_nrgtotal 9 0 1/100 30 2
HP Module heatpump 252 dhw.nrg energy uint24 (>=0<=167772) kWh False sensor.heatpump_dhw_energy sensor.heatpump_dhw_nrg 9 9 1/100 1 2
HP Module heatpump 252 nrgheat energy heating uint24 (>=0<=167772) kWh False sensor.heatpump_energy_heating sensor.heatpump_nrgheat 9 0 1/100 32 2
HP Module heatpump 252 metertotal meter total uint24 (>=0<=167772) kWh False sensor.heatpump_meter_total sensor.heatpump_metertotal 9 0 1/100 34 2
HP Module heatpump 252 metercomp meter compressor uint24 (>=0<=167772) kWh False sensor.heatpump_meter_compressor sensor.heatpump_metercomp 9 0 1/100 36 2
HP Module heatpump 252 metereheat meter e-heater uint24 (>=0<=167772) kWh False sensor.heatpump_meter_e-heater sensor.heatpump_metereheat 9 0 1/100 38 2
HP Module heatpump 252 meterheat meter heating uint24 (>=0<=167772) kWh False sensor.heatpump_meter_heating sensor.heatpump_meterheat 9 0 1/100 40 2
HP Module heatpump 252 dhw.meter meter uint24 (>=0<=167772) kWh False sensor.heatpump_dhw_meter sensor.heatpump_dhw_meter 9 9 1/100 3 2
HP Module heatpump 252 heatingstarts heating control starts uint24 (>=0<=16777214) False sensor.heatpump_heating_control_starts sensor.heatpump_heatingstarts 9 0 1 42 2
HP Module heatpump 252 dhw.startshp starts hp uint24 (>=0<=16777214) False sensor.heatpump_dhw_starts_hp sensor.heatpump_dhw_startshp 9 9 1 5 2
HP Module heatpump 252 fuelheat fuel consumption heating uint32 (>=0<=1677721) kWh False sensor.heatpump_fuel_consumption_heating sensor.heatpump_fuelheat 9 0 1/10 44 2
HP Module heatpump 252 dhw.fueldhw fuel consumption uint32 (>=0<=1677721) kWh False sensor.heatpump_dhw_fuel_consumption sensor.heatpump_dhw_fueldhw 9 9 1/10 7 2
HP Module heatpump 252 elheat el. consumption heating uint32 (>=0<=1677721) kWh False sensor.heatpump_el._consumption_heating sensor.heatpump_elheat 9 0 1/10 46 2
HP Module heatpump 252 dhw.eldhw el. consumption uint32 (>=0<=1677721) kWh False sensor.heatpump_dhw_el._consumption sensor.heatpump_dhw_eldhw 9 9 1/10 9 2
HP Module heatpump 252 elgenheat el. generation heating uint32 (>=0<=1677721) kWh False sensor.heatpump_el._generation_heating sensor.heatpump_elgenheat 9 0 1/10 48 2
HP Module heatpump 252 dhw.elgendhw el generation uint32 (>=0<=1677721) kWh False sensor.heatpump_dhw_el_generation sensor.heatpump_dhw_elgendhw 9 9 1/10 11 2
Hybrid Manager HM200 heatpump 248 airhumidity relative air humidity uint8 (>=0<=100) % False sensor.heatpump_relative_air_humidity sensor.heatpump_airhumidity 9 0 1 0 1
Hybrid Manager HM200 heatpump 248 dewtemperature dew point temperature uint8 (>=0<=254) C False sensor.heatpump_dew_point_temperature sensor.heatpump_dewtemperature 9 0 1 1 1
Hybrid Manager HM200 heatpump 248 curflowtemp current flow temperature int16 (>=-3199<=3199) C False sensor.heatpump_current_flow_temperature sensor.heatpump_curflowtemp 9 0 1/10 2 1
Hybrid Manager HM200 heatpump 248 rettemp return temperature int16 (>=-3199<=3199) C False sensor.heatpump_return_temperature sensor.heatpump_rettemp 9 0 1/10 3 1
Hybrid Manager HM200 heatpump 248 sysrettemp system return temperature int16 (>=-3199<=3199) C False sensor.heatpump_system_return_temperature sensor.heatpump_sysrettemp 9 0 1/10 4 1
Hybrid Manager HM200 heatpump 248 hpta4 drain pan temp (TA4) int16 (>=-3199<=3199) C False sensor.heatpump_drain_pan_temp_(TA4) sensor.heatpump_hpta4 9 0 1/10 5 1
Hybrid Manager HM200 heatpump 248 hptr1 compressor temperature (TR1) int16 (>=-3199<=3199) C False sensor.heatpump_compressor_temperature_(TR1) sensor.heatpump_hptr1 9 0 1/10 6 1
Hybrid Manager HM200 heatpump 248 hptr3 refrigerant temperature liquid side (condenser output) (TR3) int16 (>=-3199<=3199) C False sensor.heatpump_refrigerant_temperature_liquid_side_(condenser_output)_(TR3) sensor.heatpump_hptr3 9 0 1/10 7 1
Hybrid Manager HM200 heatpump 248 hptr4 evaporator inlet temperature (TR4) int16 (>=-3199<=3199) C False sensor.heatpump_evaporator_inlet_temperature_(TR4) sensor.heatpump_hptr4 9 0 1/10 8 1
Hybrid Manager HM200 heatpump 248 hptr5 compressor inlet temperature (TR5) int16 (>=-3199<=3199) C False sensor.heatpump_compressor_inlet_temperature_(TR5) sensor.heatpump_hptr5 9 0 1/10 9 1
Hybrid Manager HM200 heatpump 248 hptr6 compressor outlet temperature (TR6) int16 (>=-3199<=3199) C False sensor.heatpump_compressor_outlet_temperature_(TR6) sensor.heatpump_hptr6 9 0 1/10 10 1
Hybrid Manager HM200 heatpump 248 hptl2 air inlet temperature (TL2) int16 (>=-3199<=3199) C False sensor.heatpump_air_inlet_temperature_(TL2) sensor.heatpump_hptl2 9 0 1/10 11 1
Hybrid Manager HM200 heatpump 248 hppl1 low pressure side temperature (PL1) int16 (>=-3199<=3199) C False sensor.heatpump_low_pressure_side_temperature_(PL1) sensor.heatpump_hppl1 9 0 1/10 12 1
Hybrid Manager HM200 heatpump 248 hpph1 high pressure side temperature (PH1) int16 (>=-3199<=3199) C False sensor.heatpump_high_pressure_side_temperature_(PH1) sensor.heatpump_hpph1 9 0 1/10 13 1
Hybrid Manager HM200 heatpump 248 heatingpumpmod heating pump modulation uint8 (>=0<=100) % False sensor.heatpump_heating_pump_modulation sensor.heatpump_heatingpumpmod 9 0 1 14 1
Hybrid Manager HM200 heatpump 248 hpcompspd compressor speed uint8 (>=0<=100) % False sensor.heatpump_compressor_speed sensor.heatpump_hpcompspd 9 0 1 15 1
Hybrid Manager HM200 heatpump 248 hybridstrategy hybrid control strategy enum [cost optimized|co2 optimized|outside temperature alt.|outside temperature parallel|heatpump preferred|boiler only] True select.heatpump_hybrid_control_strategy select.heatpump_hybridstrategy 9 0 1 16 1
Hybrid Manager HM200 heatpump 248 lownoisemode low noise mode enum [off|reduced output|switch off hp|perm. reduced] True select.heatpump_low_noise_mode select.heatpump_lownoisemode 9 0 1 17 1
Hybrid Manager HM200 heatpump 248 lownoisestart low noise starttime uint8 (>=0<=23) hours True number.heatpump_low_noise_starttime number.heatpump_lownoisestart 9 0 1 18 1
Hybrid Manager HM200 heatpump 248 lownoisestop low noise stoptime uint8 (>=0<=23) hours True number.heatpump_low_noise_stoptime number.heatpump_lownoisestop 9 0 1 19 1
Hybrid Manager HM200 heatpump 248 dhw.hybriddhw hybrid DHW enum [eco|high comfort] True select.heatpump_dhw_hybrid_DHW select.heatpump_dhw_hybriddhw 9 9 1 0 1
Hybrid Manager HM200 heatpump 248 energypricegas energy price gas uint8 (>=0<=254) ct/kWh True number.heatpump_energy_price_gas number.heatpump_energypricegas 9 0 1 20 1
Hybrid Manager HM200 heatpump 248 energypriceel energy price electric uint8 (>=0<=254) ct/kWh True number.heatpump_energy_price_electric number.heatpump_energypriceel 9 0 1 21 1
Hybrid Manager HM200 heatpump 248 energyfeedpv feed in PV uint8 (>=0<=254) ct/kWh True number.heatpump_feed_in_PV number.heatpump_energyfeedpv 9 0 1 22 1
Hybrid Manager HM200 heatpump 248 switchovertemp outside switchover temperature int8 (>=-126<=126) C True number.heatpump_outside_switchover_temperature number.heatpump_switchovertemp 9 0 1 23 1
Hybrid Manager HM200 heatpump 248 airpurgemode air purge mode boolean True switch.heatpump_air_purge_mode switch.heatpump_airpurgemode 9 0 1 24 1
Hybrid Manager HM200 heatpump 248 heatpumpoutput heatpump output uint8 (>=0<=100) % True number.heatpump_heatpump_output number.heatpump_heatpumpoutput 9 0 1 25 1
Hybrid Manager HM200 heatpump 248 coolingcircuit cooling circuit boolean True switch.heatpump_cooling_circuit switch.heatpump_coolingcircuit 9 0 1 26 1
Hybrid Manager HM200 heatpump 248 compstartmod compressor start modulation uint8 (>=0<=100) % True number.heatpump_compressor_start_modulation number.heatpump_compstartmod 9 0 1 27 1
Hybrid Manager HM200 heatpump 248 heatdrainpan heat drain pan boolean True switch.heatpump_heat_drain_pan switch.heatpump_heatdrainpan 9 0 1 28 1
Hybrid Manager HM200 heatpump 248 heatcable heating cable boolean True switch.heatpump_heating_cable switch.heatpump_heatcable 9 0 1 29 1
Hybrid Manager HM200 heatpump 248 nrgtotal total energy uint24 (>=0<=167772) kWh False sensor.heatpump_total_energy sensor.heatpump_nrgtotal 9 0 1/100 30 2
Hybrid Manager HM200 heatpump 248 dhw.nrg energy uint24 (>=0<=167772) kWh False sensor.heatpump_dhw_energy sensor.heatpump_dhw_nrg 9 9 1/100 1 2
Hybrid Manager HM200 heatpump 248 nrgheat energy heating uint24 (>=0<=167772) kWh False sensor.heatpump_energy_heating sensor.heatpump_nrgheat 9 0 1/100 32 2
Hybrid Manager HM200 heatpump 248 metertotal meter total uint24 (>=0<=167772) kWh False sensor.heatpump_meter_total sensor.heatpump_metertotal 9 0 1/100 34 2
Hybrid Manager HM200 heatpump 248 metercomp meter compressor uint24 (>=0<=167772) kWh False sensor.heatpump_meter_compressor sensor.heatpump_metercomp 9 0 1/100 36 2
Hybrid Manager HM200 heatpump 248 metereheat meter e-heater uint24 (>=0<=167772) kWh False sensor.heatpump_meter_e-heater sensor.heatpump_metereheat 9 0 1/100 38 2
Hybrid Manager HM200 heatpump 248 meterheat meter heating uint24 (>=0<=167772) kWh False sensor.heatpump_meter_heating sensor.heatpump_meterheat 9 0 1/100 40 2
Hybrid Manager HM200 heatpump 248 dhw.meter meter uint24 (>=0<=167772) kWh False sensor.heatpump_dhw_meter sensor.heatpump_dhw_meter 9 9 1/100 3 2
Hybrid Manager HM200 heatpump 248 heatingstarts heating control starts uint24 (>=0<=16777214) False sensor.heatpump_heating_control_starts sensor.heatpump_heatingstarts 9 0 1 42 2
Hybrid Manager HM200 heatpump 248 dhw.startshp starts hp uint24 (>=0<=16777214) False sensor.heatpump_dhw_starts_hp sensor.heatpump_dhw_startshp 9 9 1 5 2
Hybrid Manager HM200 heatpump 248 fuelheat fuel consumption heating uint32 (>=0<=1677721) kWh False sensor.heatpump_fuel_consumption_heating sensor.heatpump_fuelheat 9 0 1/10 44 2
Hybrid Manager HM200 heatpump 248 dhw.fueldhw fuel consumption uint32 (>=0<=1677721) kWh False sensor.heatpump_dhw_fuel_consumption sensor.heatpump_dhw_fueldhw 9 9 1/10 7 2
Hybrid Manager HM200 heatpump 248 elheat el. consumption heating uint32 (>=0<=1677721) kWh False sensor.heatpump_el._consumption_heating sensor.heatpump_elheat 9 0 1/10 46 2
Hybrid Manager HM200 heatpump 248 dhw.eldhw el. consumption uint32 (>=0<=1677721) kWh False sensor.heatpump_dhw_el._consumption sensor.heatpump_dhw_eldhw 9 9 1/10 9 2
Hybrid Manager HM200 heatpump 248 elgenheat el. generation heating uint32 (>=0<=1677721) kWh False sensor.heatpump_el._generation_heating sensor.heatpump_elgenheat 9 0 1/10 48 2
Hybrid Manager HM200 heatpump 248 dhw.elgendhw el generation uint32 (>=0<=1677721) kWh False sensor.heatpump_dhw_el_generation sensor.heatpump_dhw_elgendhw 9 9 1/10 11 2
WM10 switch 71 activated activated boolean False binary_sensor.switch_activated binary_sensor.switch_activated 11 0 1 0 1
WM10 switch 71 flowtemphc flow temperature (TC1) uint16 (>=0<=3199) C False sensor.switch_flow_temperature_(TC1) sensor.switch_flowtemphc 11 0 1/10 1 1
WM10 switch 71 status status int8 (>=-126<=126) False sensor.switch_status sensor.switch_status 11 0 1 2 1
Rego 3000 controller 240 datetime date/time string False sensor.controller_date/time sensor.controller_datetime 12 0 1 0 13
EM10 alert 74 setflowtemp set flow temperature uint8 (>=0<=254) C False sensor.alert_set_flow_temperature sensor.alert_setflowtemp 14 0 1 0 1
EM10 alert 74 setburnpow burner set power uint8 (>=0<=100) % False sensor.alert_burner_set_power sensor.alert_setburnpow 14 0 1 1 1
EM10, EM100 extension 243 flowtempvf flow temperature in header (T0/Vf) int16 (>=-3199<=3199) C False sensor.extension_flow_temperature_in_header_(T0/Vf) sensor.extension_flowtempvf 15 0 1/10 0 1
EM10, EM100 extension 243 input input uint8 (>=0<=25) V False sensor.extension_input sensor.extension_input 15 0 1/10 1 1
EM10, EM100 extension 243 outpow output IO1 uint8 (>=0<=100) % False sensor.extension_output_IO1 sensor.extension_outpow 15 0 1 2 1
EM10, EM100 extension 243 setpower request power uint8 (>=0<=100) % False sensor.extension_request_power sensor.extension_setpower 15 0 1 3 1
EM10, EM100 extension 243 setpoint set temp. uint8 (>=0<=254) C False sensor.extension_set_temp. sensor.extension_setpoint 15 0 1 4 1
EM10, EM100 extension 243 minv min volt. uint8 (>=0<=25) V True number.extension_min_volt. number.extension_minv 15 0 1/10 5 1
EM10, EM100 extension 243 maxv max volt. uint8 (>=0<=25) V True number.extension_max_volt. number.extension_maxv 15 0 1/10 6 1
EM10, EM100 extension 243 mint min temp. uint8 (>=0<=254) C True number.extension_min_temp. number.extension_mint 15 0 1 7 1
EM10, EM100 extension 243 maxt max temp. uint8 (>=0<=254) C True number.extension_max_temp. number.extension_maxt 15 0 1 8 1
EM10, EM100 extension 243 mode operating mode uint8 (>=0<=254) False sensor.extension_operating_mode sensor.extension_mode 15 0 1 9 1
T1RF extension 220 flowtempvf flow temperature in header (T0/Vf) int16 (>=-3199<=3199) C False sensor.extension_flow_temperature_in_header_(T0/Vf) sensor.extension_flowtempvf 15 0 1/10 0 1
T1RF extension 220 input input uint8 (>=0<=25) V False sensor.extension_input sensor.extension_input 15 0 1/10 1 1
T1RF extension 220 outpow output IO1 uint8 (>=0<=100) % False sensor.extension_output_IO1 sensor.extension_outpow 15 0 1 2 1
T1RF extension 220 setpower request power uint8 (>=0<=100) % False sensor.extension_request_power sensor.extension_setpower 15 0 1 3 1
T1RF extension 220 setpoint set temp. uint8 (>=0<=254) C False sensor.extension_set_temp. sensor.extension_setpoint 15 0 1 4 1
T1RF extension 220 minv min volt. uint8 (>=0<=25) V True number.extension_min_volt. number.extension_minv 15 0 1/10 5 1
T1RF extension 220 maxv max volt. uint8 (>=0<=25) V True number.extension_max_volt. number.extension_maxv 15 0 1/10 6 1
T1RF extension 220 mint min temp. uint8 (>=0<=254) C True number.extension_min_temp. number.extension_mint 15 0 1 7 1
T1RF extension 220 maxt max temp. uint8 (>=0<=254) C True number.extension_max_temp. number.extension_maxt 15 0 1 8 1
T1RF extension 220 mode operating mode uint8 (>=0<=254) False sensor.extension_operating_mode sensor.extension_mode 15 0 1 9 1
AM200 heatsource 228 ahs1.sysflowtemp system flow temperature int16 (>=-3199<=3199) C False sensor.heatsource_ahs1_system_flow_temperature sensor.heatsource_ahs1_sysflowtemp 17 19 1/10 0 1
AM200 heatsource 228 ahs1.sysrettemp system return temperature int16 (>=-3199<=3199) C False sensor.heatsource_ahs1_system_return_temperature sensor.heatsource_ahs1_sysrettemp 17 19 1/10 1 1
AM200 heatsource 228 ahs1.altflowtemp alternative hs flow temperature int16 (>=-3199<=3199) C False sensor.heatsource_ahs1_alternative_hs_flow_temperature sensor.heatsource_ahs1_altflowtemp 17 19 1/10 2 1
AM200 heatsource 228 ahs1.altrettemp alternative hs return temperature int16 (>=-3199<=3199) C False sensor.heatsource_ahs1_alternative_hs_return_temperature sensor.heatsource_ahs1_altrettemp 17 19 1/10 3 1
AM200 heatsource 228 ahs1.cyltoptemp cylinder top temperature int16 (>=-3199<=3199) C False sensor.heatsource_ahs1_cylinder_top_temperature sensor.heatsource_ahs1_cyltoptemp 17 19 1/10 4 1
AM200 heatsource 228 ahs1.cylcentertemp cylinder center temperature int16 (>=-3199<=3199) C False sensor.heatsource_ahs1_cylinder_center_temperature sensor.heatsource_ahs1_cylcentertemp 17 19 1/10 5 1
AM200 heatsource 228 ahs1.cylbottomtemp cylinder bottom temperature int16 (>=-3199<=3199) C False sensor.heatsource_ahs1_cylinder_bottom_temperature sensor.heatsource_ahs1_cylbottomtemp 17 19 1/10 6 1
AM200 heatsource 228 ahs1.fluegastemp flue gas temperature int16 (>=-3199<=3199) C False sensor.heatsource_ahs1_flue_gas_temperature sensor.heatsource_ahs1_fluegastemp 17 19 1/10 7 1
AM200 heatsource 228 ahs1.valvebuffer buffer valve uint8 (>=0<=100) % False sensor.heatsource_ahs1_buffer_valve sensor.heatsource_ahs1_valvebuffer 17 19 1 8 1
AM200 heatsource 228 ahs1.valvereturn return valve uint8 (>=0<=100) % False sensor.heatsource_ahs1_return_valve sensor.heatsource_ahs1_valvereturn 17 19 1 9 1
AM200 heatsource 228 ahs1.apumpmod alternative hs pump modulation uint8 (>=0<=100) % False sensor.heatsource_ahs1_alternative_hs_pump_modulation sensor.heatsource_ahs1_apumpmod 17 19 1 10 1
AM200 heatsource 228 ahs1.vr2config vr2 configuration enum [off|bypass] True select.heatsource_ahs1_vr2_configuration select.heatsource_ahs1_vr2config 17 19 1 11 1
AM200 heatsource 228 ahs1.ahsactivated alternate heat source activation boolean True switch.heatsource_ahs1_alternate_heat_source_activation switch.heatsource_ahs1_ahsactivated 17 19 1 12 1
AM200 heatsource 228 ahs1.apumpconfig primary pump config boolean True switch.heatsource_ahs1_primary_pump_config switch.heatsource_ahs1_apumpconfig 17 19 1 13 1
AM200 heatsource 228 ahs1.apumpsignal output for pr1 pump enum [off|pwm|pwm inverse] True select.heatsource_ahs1_output_for_pr1_pump select.heatsource_ahs1_apumpsignal 17 19 1 14 1
AM200 heatsource 228 ahs1.apumpmin min output pump pr1 uint8 (>=12<=50) % True number.heatsource_ahs1_min_output_pump_pr1 number.heatsource_ahs1_apumpmin 17 19 1 15 1
AM200 heatsource 228 ahs1.temprise ahs return temp rise boolean True switch.heatsource_ahs1_ahs_return_temp_rise switch.heatsource_ahs1_temprise 17 19 1 16 1
AM200 heatsource 228 ahs1.setreturntemp set temp return uint8 (>=40<=75) C True number.heatsource_ahs1_set_temp_return number.heatsource_ahs1_setreturntemp 17 19 1 17 1
AM200 heatsource 228 ahs1.mixruntime mixer run time uint16 (>=0<=600) seconds True number.heatsource_ahs1_mixer_run_time number.heatsource_ahs1_mixruntime 17 19 1 18 1
AM200 heatsource 228 ahs1.setflowtemp set flow temperature uint8 (>=40<=75) C True number.heatsource_ahs1_set_flow_temperature number.heatsource_ahs1_setflowtemp 17 19 1 19 1
AM200 heatsource 228 ahs1.bufbypass buffer bypass config enum [no|mixer|valve] True select.heatsource_ahs1_buffer_bypass_config select.heatsource_ahs1_bufbypass 17 19 1 20 1
AM200 heatsource 228 ahs1.bufmixruntime bypass mixer run time uint16 (>=0<=600) seconds True number.heatsource_ahs1_bypass_mixer_run_time number.heatsource_ahs1_bufmixruntime 17 19 1 21 1
AM200 heatsource 228 ahs1.bufconfig dhw buffer config enum [off|monovalent|bivalent] True select.heatsource_ahs1_dhw_buffer_config select.heatsource_ahs1_bufconfig 17 19 1 22 1
AM200 heatsource 228 ahs1.blockmode config htg. blocking mode enum [off|auto|blocking] True select.heatsource_ahs1_config_htg._blocking_mode select.heatsource_ahs1_blockmode 17 19 1 23 1
AM200 heatsource 228 ahs1.blockterm config of block terminal enum [n_o|n_c] True select.heatsource_ahs1_config_of_block_terminal select.heatsource_ahs1_blockterm 17 19 1 24 1
AM200 heatsource 228 ahs1.blockhyst hyst. for boiler block int8 (>=0<=50) C True number.heatsource_ahs1_hyst._for_boiler_block number.heatsource_ahs1_blockhyst 17 19 1 25 1
AM200 heatsource 228 ahs1.releasewait boiler release wait time uint8 (>=0<=240) minutes True number.heatsource_ahs1_boiler_release_wait_time number.heatsource_ahs1_releasewait 17 19 1 26 1
AM200 heatsource 228 ahs1.burner burner boolean False binary_sensor.heatsource_ahs1_burner binary_sensor.heatsource_ahs1_burner 17 19 1 27 1
AM200 heatsource 228 ahs1.apump alternative hs pump boolean False binary_sensor.heatsource_ahs1_alternative_hs_pump binary_sensor.heatsource_ahs1_apump 17 19 1 28 1
AM200 heatsource 228 ahs1.heatrequest heat request uint8 (>=0<=100) % False sensor.heatsource_ahs1_heat_request sensor.heatsource_ahs1_heatrequest 17 19 1 29 1
AM200 heatsource 228 ahs1.blockremain remaining blocktime uint8 (>=0<=254) minutes False sensor.heatsource_ahs1_remaining_blocktime sensor.heatsource_ahs1_blockremain 17 19 1 30 1
AM200 heatsource 228 ahs1.blockremaindhw remaining blocktime dhw uint8 (>=0<=254) minutes False sensor.heatsource_ahs1_remaining_blocktime_dhw sensor.heatsource_ahs1_blockremaindhw 17 19 1 31 1
Logavent HRV176 ventilation 231 outfresh outdoor fresh air int16 (>=-3199<=3199) C False sensor.ventilation_outdoor_fresh_air sensor.ventilation_outfresh 18 0 1/10 0 1
Logavent HRV176 ventilation 231 infresh indoor fresh air int16 (>=-3199<=3199) C False sensor.ventilation_indoor_fresh_air sensor.ventilation_infresh 18 0 1/10 1 1
Logavent HRV176 ventilation 231 outexhaust outdoor exhaust air int16 (>=-3199<=3199) C False sensor.ventilation_outdoor_exhaust_air sensor.ventilation_outexhaust 18 0 1/10 2 1
Logavent HRV176 ventilation 231 inexhaust indoor exhaust air int16 (>=-3199<=3199) C False sensor.ventilation_indoor_exhaust_air sensor.ventilation_inexhaust 18 0 1/10 3 1
Logavent HRV176 ventilation 231 ventinspeed in blower speed uint8 (>=0<=100) % False sensor.ventilation_in_blower_speed sensor.ventilation_ventinspeed 18 0 1 4 1
Logavent HRV176 ventilation 231 ventoutspeed out blower speed uint8 (>=0<=100) % False sensor.ventilation_out_blower_speed sensor.ventilation_ventoutspeed 18 0 1 5 1
Logavent HRV176 ventilation 231 ventmode ventilation mode enum [auto|off|L1|L2|L3|L4|demand|sleep|intense|bypass|party|fireplace] True select.ventilation_ventilation_mode select.ventilation_ventmode 18 0 1 6 1
Logavent HRV176 ventilation 231 airquality air quality (voc) uint16 (>=0<=31999) False sensor.ventilation_air_quality_(voc) sensor.ventilation_airquality 18 0 1 7 1
Logavent HRV176 ventilation 231 airhumidity relative air humidity uint8 (>=0<=100) % False sensor.ventilation_relative_air_humidity sensor.ventilation_airhumidity 18 0 1 8 1
Logavent HRV176 ventilation 231 bypass bypass boolean True switch.ventilation_bypass switch.ventilation_bypass 18 0 1 9 1
IPM water 100 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.water_dhw_selected_temperature number.water_dhw_seltemp 19 9 1 0 1
IPM water 100 dhw.temp current temperature uint16 (>=0<=3199) C False sensor.water_dhw_current_temperature sensor.water_dhw_temp 19 9 1/10 1 1
IPM water 100 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.water_dhw_current_extern_temperature sensor.water_dhw_curtemp2 19 9 1/10 2 1
IPM water 100 dhw.hydrTemp hydraulic header temperature uint16 (>=0<=3199) C False sensor.water_dhw_hydraulic_header_temperature sensor.water_dhw_hydrTemp 19 9 1/10 3 1
IPM water 100 dhw.pump pump boolean False binary_sensor.water_dhw_pump binary_sensor.water_dhw_pump 19 9 1 4 1
IPM water 100 dhw.flowtempoffset flow temperature offset uint8 (>=0<=254) C True number.water_dhw_flow_temperature_offset number.water_dhw_flowtempoffset 19 9 1 5 1
IPM water 100 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.water_dhw_hysteresis_on_temperature number.water_dhw_hyston 19 9 1 6 1
IPM water 100 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.water_dhw_hysteresis_off_temperature number.water_dhw_hystoff 19 9 1 7 1
IPM water 100 dhw.disinfectiontemp disinfection temperature uint8 (>=0<=254) C True number.water_dhw_disinfection_temperature number.water_dhw_disinfectiontemp 19 9 1 8 1
IPM water 100 dhw.circ circulation active boolean True switch.water_dhw_circulation_active switch.water_dhw_circ 19 9 1 9 1
IPM water 100 dhw.circmode circulation pump mode enum [off|on|auto|own prog] True select.water_dhw_circulation_pump_mode select.water_dhw_circmode 19 9 1 10 1
IPM2 water 102 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.water_dhw_selected_temperature number.water_dhw_seltemp 19 9 1 0 1
IPM2 water 102 dhw.temp current temperature uint16 (>=0<=3199) C False sensor.water_dhw_current_temperature sensor.water_dhw_temp 19 9 1/10 1 1
IPM2 water 102 dhw.curtemp2 current extern temperature uint16 (>=0<=3199) C False sensor.water_dhw_current_extern_temperature sensor.water_dhw_curtemp2 19 9 1/10 2 1
IPM2 water 102 dhw.hydrTemp hydraulic header temperature uint16 (>=0<=3199) C False sensor.water_dhw_hydraulic_header_temperature sensor.water_dhw_hydrTemp 19 9 1/10 3 1
IPM2 water 102 dhw.pump pump boolean False binary_sensor.water_dhw_pump binary_sensor.water_dhw_pump 19 9 1 4 1
IPM2 water 102 dhw.flowtempoffset flow temperature offset uint8 (>=0<=254) C True number.water_dhw_flow_temperature_offset number.water_dhw_flowtempoffset 19 9 1 5 1
IPM2 water 102 dhw.hyston hysteresis on temperature int8 (>=-126<=126) C True number.water_dhw_hysteresis_on_temperature number.water_dhw_hyston 19 9 1 6 1
IPM2 water 102 dhw.hystoff hysteresis off temperature int8 (>=-126<=126) C True number.water_dhw_hysteresis_off_temperature number.water_dhw_hystoff 19 9 1 7 1
IPM2 water 102 dhw.disinfectiontemp disinfection temperature uint8 (>=0<=254) C True number.water_dhw_disinfection_temperature number.water_dhw_disinfectiontemp 19 9 1 8 1
IPM2 water 102 dhw.circ circulation active boolean True switch.water_dhw_circulation_active switch.water_dhw_circ 19 9 1 9 1
IPM2 water 102 dhw.circmode circulation pump mode enum [off|on|auto|own prog] True select.water_dhw_circulation_pump_mode select.water_dhw_circmode 19 9 1 10 1
MM100 water 160 dhw.temp current temperature uint16 (>=0<=3199) C False sensor.water_dhw_current_temperature sensor.water_dhw_temp 19 9 1/10 1 1
MM100 water 160 dhw.tempstatus temperature switch in assigned dhw (MC1) int8 (>=-126<=126) False sensor.water_dhw_temperature_switch_in_assigned_dhw_(MC1) sensor.water_dhw_tempstatus 19 9 1 11 1
MM100 water 160 dhw.pump pump boolean False binary_sensor.water_dhw_pump binary_sensor.water_dhw_pump 19 9 1 4 1
MM100 water 160 dhw.maxtemp maximum temperature uint8 (>=0<=254) C True number.water_dhw_maximum_temperature number.water_dhw_maxtemp 19 9 1 12 1
MM100 water 160 dhw.difftemp start differential temperature int8 (>=-126<=126) C True number.water_dhw_start_differential_temperature number.water_dhw_difftemp 19 9 1 13 1
MM100 water 160 dhw.disinfectiontemp disinfection temperature uint8 (>=0<=254) C True number.water_dhw_disinfection_temperature number.water_dhw_disinfectiontemp 19 9 1 8 1
MM100 water 160 dhw.redtemp reduced temperature uint8 (>=0<=254) C True number.water_dhw_reduced_temperature number.water_dhw_redtemp 19 9 1 14 1
MM100 water 160 dhw.requiredtemp required temperature uint8 (>=0<=254) C True number.water_dhw_required_temperature number.water_dhw_requiredtemp 19 9 1 15 1
MM100 water 160 dhw.circ circulation active boolean True switch.water_dhw_circulation_active switch.water_dhw_circ 19 9 1 9 1
MM100 water 160 dhw.circmode circulation pump mode enum [off|on|auto|own prog] True select.water_dhw_circulation_pump_mode select.water_dhw_circmode 19 9 1 10 1
MM200 water 161 dhw.temp current temperature uint16 (>=0<=3199) C False sensor.water_dhw_current_temperature sensor.water_dhw_temp 19 9 1/10 1 1
MM200 water 161 dhw.tempstatus temperature switch in assigned dhw (MC1) int8 (>=-126<=126) False sensor.water_dhw_temperature_switch_in_assigned_dhw_(MC1) sensor.water_dhw_tempstatus 19 9 1 11 1
MM200 water 161 dhw.pump pump boolean False binary_sensor.water_dhw_pump binary_sensor.water_dhw_pump 19 9 1 4 1
MM200 water 161 dhw.maxtemp maximum temperature uint8 (>=0<=254) C True number.water_dhw_maximum_temperature number.water_dhw_maxtemp 19 9 1 12 1
MM200 water 161 dhw.difftemp start differential temperature int8 (>=-126<=126) C True number.water_dhw_start_differential_temperature number.water_dhw_difftemp 19 9 1 13 1
MM200 water 161 dhw.disinfectiontemp disinfection temperature uint8 (>=0<=254) C True number.water_dhw_disinfection_temperature number.water_dhw_disinfectiontemp 19 9 1 8 1
MM200 water 161 dhw.redtemp reduced temperature uint8 (>=0<=254) C True number.water_dhw_reduced_temperature number.water_dhw_redtemp 19 9 1 14 1
MM200 water 161 dhw.requiredtemp required temperature uint8 (>=0<=254) C True number.water_dhw_required_temperature number.water_dhw_requiredtemp 19 9 1 15 1
MM200 water 161 dhw.circ circulation active boolean True switch.water_dhw_circulation_active switch.water_dhw_circ 19 9 1 9 1
MM200 water 161 dhw.circmode circulation pump mode enum [off|on|auto|own prog] True select.water_dhw_circulation_pump_mode select.water_dhw_circmode 19 9 1 10 1
SM100, MS100 water 163 dhw.temp current temperature uint16 (>=0<=3199) C False sensor.water_dhw_current_temperature sensor.water_dhw_temp 19 9 1/10 1 1
SM100, MS100 water 163 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.water_dhw_storage_intern_temperature sensor.water_dhw_storagetemp1 19 9 1/10 16 1
SM100, MS100 water 163 dhw.coldtemp cold water uint16 (>=0<=3199) C False sensor.water_dhw_cold_water sensor.water_dhw_coldtemp 19 9 1/10 17 1
SM100, MS100 water 163 dhw.temp5 temperature 5 uint16 (>=0<=3199) C False sensor.water_dhw_temperature_5 sensor.water_dhw_temp5 19 9 1/10 18 1
SM100, MS100 water 163 dhw.rettemp return temperature uint16 (>=0<=3199) C False sensor.water_dhw_return_temperature sensor.water_dhw_rettemp 19 9 1/10 19 1
SM100, MS100 water 163 dhw.pump pump boolean False binary_sensor.water_dhw_pump binary_sensor.water_dhw_pump 19 9 1 4 1
SM100, MS100 water 163 dhw.maxtemp maximum temperature uint8 (>=0<=254) C True number.water_dhw_maximum_temperature number.water_dhw_maxtemp 19 9 1 12 1
SM100, MS100 water 163 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.water_dhw_selected_temperature number.water_dhw_seltemp 19 9 1 0 1
SM100, MS100 water 163 dhw.redtemp reduced temperature uint8 (>=0<=254) C True number.water_dhw_reduced_temperature number.water_dhw_redtemp 19 9 1 14 1
SM100, MS100 water 163 dhw.hottemp extra hot temperature uint8 (>=0<=254) C True number.water_dhw_extra_hot_temperature number.water_dhw_hottemp 19 9 1 20 1
SM100, MS100 water 163 dhw.dailytemp daily temperature uint8 (>=0<=254) C True number.water_dhw_daily_temperature number.water_dhw_dailytemp 19 9 1 21 1
SM100, MS100 water 163 dhw.disinfectiontemp disinfection temperature uint8 (>=0<=254) C True number.water_dhw_disinfection_temperature number.water_dhw_disinfectiontemp 19 9 1 8 1
SM100, MS100 water 163 dhw.circ circulation active boolean True switch.water_dhw_circulation_active switch.water_dhw_circ 19 9 1 9 1
SM100, MS100 water 163 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.water_dhw_circulation_pump_mode select.water_dhw_circmode 19 9 1 10 1
SM100, MS100 water 163 dhw.circtc circulation time controled boolean True switch.water_dhw_circulation_time_controled switch.water_dhw_circtc 19 9 1 22 1
SM100, MS100 water 163 dhw.keepwarm keep warm boolean True switch.water_dhw_keep_warm switch.water_dhw_keepwarm 19 9 1 23 1
SM100, MS100 water 163 dhw.status2 status 2 enum [|||no heat|||heat request||disinfecting|hold] False sensor.water_dhw_status_2 sensor.water_dhw_status2 19 9 1 24 1
SM100, MS100 water 163 dhw.pumpmod pump modulation uint8 (>=0<=100) % False sensor.water_dhw_pump_modulation sensor.water_dhw_pumpmod 19 9 1 25 1
SM100, MS100 water 163 dhw.flow flow rate uint16 (>=0<=3199) l/min False sensor.water_dhw_flow_rate sensor.water_dhw_flow 19 9 1/10 26 1
SM100, MS100 water 163 dhw.valvereturn return valve uint8 (>=0<=100) % True number.water_dhw_return_valve number.water_dhw_valvereturn 19 9 1 27 1
SM100, MS100 water 163 dhw.deltatret temp. diff. return valve uint8 (>=0<=254) K True number.water_dhw_temp._diff._return_valve number.water_dhw_deltatret 19 9 1 28 1
SM100, MS100 water 163 dhw.errordisp error display enum [off|normal|inverted] True select.water_dhw_error_display select.water_dhw_errordisp 19 9 1 29 1
SM200, MS200 water 164 dhw.temp current temperature uint16 (>=0<=3199) C False sensor.water_dhw_current_temperature sensor.water_dhw_temp 19 9 1/10 1 1
SM200, MS200 water 164 dhw.storagetemp1 storage intern temperature uint16 (>=0<=3199) C False sensor.water_dhw_storage_intern_temperature sensor.water_dhw_storagetemp1 19 9 1/10 16 1
SM200, MS200 water 164 dhw.coldtemp cold water uint16 (>=0<=3199) C False sensor.water_dhw_cold_water sensor.water_dhw_coldtemp 19 9 1/10 17 1
SM200, MS200 water 164 dhw.temp5 temperature 5 uint16 (>=0<=3199) C False sensor.water_dhw_temperature_5 sensor.water_dhw_temp5 19 9 1/10 18 1
SM200, MS200 water 164 dhw.rettemp return temperature uint16 (>=0<=3199) C False sensor.water_dhw_return_temperature sensor.water_dhw_rettemp 19 9 1/10 19 1
SM200, MS200 water 164 dhw.pump pump boolean False binary_sensor.water_dhw_pump binary_sensor.water_dhw_pump 19 9 1 4 1
SM200, MS200 water 164 dhw.maxtemp maximum temperature uint8 (>=0<=254) C True number.water_dhw_maximum_temperature number.water_dhw_maxtemp 19 9 1 12 1
SM200, MS200 water 164 dhw.seltemp selected temperature uint8 (>=0<=254) C True number.water_dhw_selected_temperature number.water_dhw_seltemp 19 9 1 0 1
SM200, MS200 water 164 dhw.redtemp reduced temperature uint8 (>=0<=254) C True number.water_dhw_reduced_temperature number.water_dhw_redtemp 19 9 1 14 1
SM200, MS200 water 164 dhw.hottemp extra hot temperature uint8 (>=0<=254) C True number.water_dhw_extra_hot_temperature number.water_dhw_hottemp 19 9 1 20 1
SM200, MS200 water 164 dhw.dailytemp daily temperature uint8 (>=0<=254) C True number.water_dhw_daily_temperature number.water_dhw_dailytemp 19 9 1 21 1
SM200, MS200 water 164 dhw.disinfectiontemp disinfection temperature uint8 (>=0<=254) C True number.water_dhw_disinfection_temperature number.water_dhw_disinfectiontemp 19 9 1 8 1
SM200, MS200 water 164 dhw.circ circulation active boolean True switch.water_dhw_circulation_active switch.water_dhw_circ 19 9 1 9 1
SM200, MS200 water 164 dhw.circmode circulation pump mode enum [off|1x3min|2x3min|3x3min|4x3min|5x3min|6x3min|continuous] True select.water_dhw_circulation_pump_mode select.water_dhw_circmode 19 9 1 10 1
SM200, MS200 water 164 dhw.circtc circulation time controled boolean True switch.water_dhw_circulation_time_controled switch.water_dhw_circtc 19 9 1 22 1
SM200, MS200 water 164 dhw.keepwarm keep warm boolean True switch.water_dhw_keep_warm switch.water_dhw_keepwarm 19 9 1 23 1
SM200, MS200 water 164 dhw.status2 status 2 enum [|||no heat|||heat request||disinfecting|hold] False sensor.water_dhw_status_2 sensor.water_dhw_status2 19 9 1 24 1
SM200, MS200 water 164 dhw.pumpmod pump modulation uint8 (>=0<=100) % False sensor.water_dhw_pump_modulation sensor.water_dhw_pumpmod 19 9 1 25 1
SM200, MS200 water 164 dhw.flow flow rate uint16 (>=0<=3199) l/min False sensor.water_dhw_flow_rate sensor.water_dhw_flow 19 9 1/10 26 1
SM200, MS200 water 164 dhw.valvereturn return valve uint8 (>=0<=100) % True number.water_dhw_return_valve number.water_dhw_valvereturn 19 9 1 27 1
SM200, MS200 water 164 dhw.deltatret temp. diff. return valve uint8 (>=0<=254) K True number.water_dhw_temp._diff._return_valve number.water_dhw_deltatret 19 9 1 28 1
SM200, MS200 water 164 dhw.errordisp error display enum [off|normal|inverted] True select.water_dhw_error_display select.water_dhw_errordisp 19 9 1 29 1
MP100 pool 204 pooltemp pool temperature int16 (>=-3199<=3199) C False sensor.pool_pool_temperature sensor.pool_pooltemp 20 0 1/10 -1 1
MP100 pool 204 poolshuntstatus pool shunt status opening/closing enum [stopped|opening|closing|open|close] False sensor.pool_pool_shunt_status_opening/closing sensor.pool_poolshuntstatus 20 0 1 -1 1
MP100 pool 204 poolshunt pool shunt open/close (0% = pool / 100% = heat) uint8 (>=0<=100) % False sensor.pool_pool_shunt_open/close_(0%=_pool/100%=_heat) sensor.pool_poolshunt 20 0 1 -1 1

Last update: April 26, 2025
Back to top